4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10
37
44..22
U
UP
PS
S EElleeccttrriiccaall IInnssttaallllaattiioonn
Only qualified service personnel (such as a licensed electrician) should perform the electrical installation. Risk of
electrical shock.
To prevent electrical shock or damage to the equipment, verify that the Eaton 9PXM UPS is OFF before you
remove the terminal covers. The circuit breaker or disconnect switch must also be OFF at the AC input service
panel.
To install the UPS without an external bypass switch:
1.
Install the AC terminal upper covers supplied in the accessory kit of the UPS (See
) . The AC
input terminal block is located on the lower right side and the AC output on the upper right side of the UPS
rear panel.
Figure 33. UPS Power Terminals
AC Input Terminals
Terminal Cover
Terminal Cover
AC Output Terminals
Содержание 9PXM8S4K
Страница 1: ...p n P 164000669 Revision 10 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS...
Страница 4: ......
Страница 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Table of Contents...
Страница 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 List of Tables...
Страница 20: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Physical Features...
Страница 54: ...42 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 System Wiring Diagram...
Страница 98: ...86 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Display Menu Screens...
Страница 104: ...92 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Communication Slots...
Страница 114: ...102 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Receptacle Circuit Breaker Ratings...
Страница 119: ...4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 107 Two Year Limited Warranty...
Страница 120: ...P 16400066910 P 164000669 10...