NO Configuration
For Normally Open operation, configure as in
with external switch wired to Pins 3 and 4 of CN7.
18AWG Twisted wire is to be used for EPO connections.
Figure 76. Normally Open Connections
REPO
Switch
(NO)
Twisted
Wires
3
3
REPO TB
NOTE
REPO switch rating is 24 Vdc. 1A minimum
NOTE
The REPO switch must be a latching type switch not tied to any other cicuits.
4
4
2
1
NC Configuration
For Normally Closed operation, add a jumper between Pins 3 and 4 of CN7 and the EPO switch should be
connected to Pins 1 and 2 and should be closed during normal operation of the UPS (see
).
Figure 77. EPO Normally Closed Connections
REPO
Switch
(NO)
Twisted
Wires
1
3
REPO TB
2
4
2
1
NOTE
REPO switch rating is 24 Vdc. 1A minimum
NOTE
The REPO switch must be a latching type switch not tied to any other cicuits.
Maintenance Bypass:
The signal from an external bypass switch, to isolate the Eaton 9PXM system for
maintenance purposes, tells the UPS to go into Internal Bypass mode.
On Generator:
The signal allows the UPS to optimize its operation with the generator by transferring the UPS
from High Efficiency mode to Normal (double conversion) mode as long as High Efficiency is set as the default
mode of UPS operation. See IN/Out setting.
Содержание 9PXM8S4K
Страница 1: ...p n P 164000669 Revision 10 Eaton 9PXM UPS 4 20kVA Users Guide Eaton 9PXM UPS...
Страница 4: ......
Страница 8: ...viii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Table of Contents...
Страница 12: ...xii 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 List of Tables...
Страница 20: ...8 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Physical Features...
Страница 54: ...42 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 System Wiring Diagram...
Страница 98: ...86 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Display Menu Screens...
Страница 104: ...92 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Communication Slots...
Страница 114: ...102 4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 Receptacle Circuit Breaker Ratings...
Страница 119: ...4 20kVA Users Guide P 164000669 4 20kVA Users Guide P 164000669 Rev 10 107 Two Year Limited Warranty...
Страница 120: ...P 16400066910 P 164000669 10...