Eaton 9PX Lithium-Ion User Guide DPD-9PX2206—Rev 01
25
CChhaapptteerr 55 OOppeerraattiioonn
55..11
SSttaarrtt--uupp aanndd N
Noorrm
maall OOppeerraattiioonn
NOTE
If you ordered a HotSwap MBP or a PPDM, refer to the specific user manual to check
the startup sequence of the UPS with this accessory.
To start the UPS:
1. Verify that the internal batteries are connected. See section .
2. If optional EBMs are installed, verify that the EBM are connected to the UPS. See section
.
3. Verify that the UPS power cord is plugged in.
4. The UPS front panel display illuminates and shows EATON logo.
5. Verify that the UPS status screen shows
.
6. Press the
button on the UPS front panel for at least 3 seconds. The UPS front panel display changes
status to "UPS starting...".
7. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before
continuing. See section
. If the
indicator is on, do not proceed until all
alarms are clear. Check the UPS status from the front panel to view the active alarms. Correct the alarms
and restart if necessary.
8. Verify that the
indicator illuminates solid, indicating that the UPS is operating normally and any loads
are powered and protected. The UPS should be in Online mode.
55..22
SSttaarrttiinngg tthhee UUPPSS oonn BBaatttteerryy
Before using this feature, the UPS must have been powered by utility power with output enabled at least once.
Battery start can be disabled. See Coldstart setting in
.
To Start the UPS on battery:
1. Press the
button on the UPS front panel until the UPS front panel display illuminates and shows a
status of "UPS starting...".
The UPS cycles through Standby mode to Battery mode. The
indicator illuminates solid.
The UPS supplies power to your equipment.
2. Check the UPS front panel display for active alarms or notices. Resolve any active alarms before
continuing. See
.
Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if
necessary.
55..33
UUPPSS SShhuuttddoow
wnn
To shut down the UPS:
1. Press the
button on the front panel for three seconds. A confirmation message will appear. When
confirmed, the UPS starts to beep and shows a status of "UPS shutting OFF...". The UPS then transfers to
Standby mode.
2. Set the upstream circuit breaker (not provided) to the "O" position (Off) to switch off the utility power.
Содержание 9PX6K-L
Страница 16: ...10 Eaton 9PX Lithium Ion User Guide DPD 9PX2206 Rev 01 User Settings...
Страница 26: ...20 Eaton 9PX Lithium Ion User Guide DPD 9PX2206 Rev 01 Detecting Other Accessories...
Страница 32: ...26 Eaton 9PX Lithium Ion User Guide DPD 9PX2206 Rev 01 UPS Shutdown...
Страница 40: ...34 Eaton 9PX Lithium Ion User Guide DPD 9PX2206 Rev 01 Recycling The Used Equipment...
Страница 44: ...38 Eaton 9PX Lithium Ion User Guide DPD 9PX2206 Rev 01 Compliance Contact...
Страница 49: ...Eaton 9PX Lithium Ion User Guide DPD 9PX2206 Rev 01 43 Model Specifications...
Страница 50: ...DPD 9PX220601 DPD 9PX2206 01...