Eaton 9PX Lithium-Ion

P-164001006—Rev 01

6.

Activate the external remote shut down contact to test the function. Always test the RPO function before
applying your critical load to avoid accidental load loss.

Programmable Signal Outputs

The 9PX incorporates 4 programmable signal outputs: one relay output, three optocouplers outputs (pin- 1/7/8).
Signal outputs can be configured (see Settings > Com settings > Output Signals in

Table 6

to report the

following information:

Signal

Default Assignment

Description

On battery (On bat)

DB9-Pin 8

UPS is in battery mode

Low battery (Low bat)

DB9-Pin 1

Battery is nearly empty

Battery fault (Bat fault)

-

Battery fault

Bypass

Relay output

(1)

UPS is operating in Bypass mode

UPS OK

DB9-Pin 7

Load is powered (from inverter or bypass), with
no alarm

Load powered

-

Load is powered (from inverter or bypass)

Load protected

-

UPS is on inverter, with no alarm and ready to go
to battery

General alarm

-

Choose events that will trigger this alarm
trough the LCD

(Settings > Com settings > General alarm )
for more information on possible events
please look at page 16.

Ext charger ON

-

Control an optional external battery charger on
and off.

OVL pre-alarm

-

Overload pre-alarm

(1) Relay output:

 

Normally Closed
Normally Open
Common

1
2
3

3

Connectivity Cards

Connectivity cards allow the UPS to communicate in a variety of networking environments and with different
types of devices. The 9PX models have one available communication bay for the following connectivity cards:

Network-M2 card

— has SNMP and HTTP capabilities as well as monitoring through a Web browser

interface; connects to a Gigabit Ethernet network. In addition, a Environmental Monitoring Probe can be
attached to obtain humidity, temperature, smoke alarm, and security information.

INDGW-M2 card

- has SNMP and HTTP capabilities and a Modbus to facilitate remote monitoring of the

UPS system through any Building Management System.

Relay-MS card

- has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery

UPS Remote Control Functions

Содержание 9PX1000IRTANZ-L

Страница 1: ...p n P 164001006 Revision 01 Eaton 9PX Lithium Ion Advanced Users Guide 9PX1000IRTANZ L 9PX1500IRTANZ L 9PX2000IRTAU L 9PX3000IRTANZ L 9PXEBM48RT1U L 9PXEBM72RT1U L Eaton 9PX Lithium Ion...

Страница 2: ...K OF ELECTRIC SHOCK Observe the warning associated with the risk of electric shock symbol CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as importan...

Страница 3: ...rical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply...

Страница 4: ...less than 25 C This charges the battery thus avoiding possible irreversible damage During the replacement of the Battery Module it is imperative to use the same type and number of element as the origi...

Страница 5: ...Connecting the EBM s 18 3 6 Detecting other Accessories 20 3 7 UPS Connection without Hotswap MBP Module 21 3 8 Connection with a Hotswap MBP Module Optional Accessory 22 4 4 C Co om mm mu un niic ca...

Страница 6: ...swap MBP 37 6 5 Recycling The Used Equipment 37 7 7 T Tr ro ou ub blle es sh ho oo ot tiin ng g 3 39 9 7 1 Typical Alarms and Faults 39 7 2 Silencing the Alarm 40 7 3 Service and Support 40 7 4 CE Com...

Страница 7: ...N has implemented an environmental protection policy Products are developed according to an eco design approach Substances This product does not contain CFCs HCFCs or asbestos Packing To improve waste...

Страница 8: ...can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With the Eato...

Страница 9: ...Table 2 Weights and Dimensions Model Dimensions D x W x H inch mm Weight lb kg 9PX1000IRTANZ L 17 7 x 17 3 x 3 4 450 x 440 x 86 5 34 3 15 6 9PX1500IRTANZ L 17 7 x 17 3 x 3 4 450 x 440 x 86 5 34 8 15 8...

Страница 10: ...ut contact 4 Connector for additional battery module 5 Primary group outlets for connection of critical equipment 6 Group 1 programmable outlets for connection of equipment 7 Group 2 programmable outl...

Страница 11: ...3 UPS Accessories Part number Description 9PXEBM48RT1U L 9PXEBM72RT1U L Extended Battery Module Network M2 Network Card INDGW M2 Industrial Gateway Card Modbus TCP RTU Relay MS Relay Card BINTSYS Batt...

Страница 12: ...ge Indicator Status Description Green On The UPS is operating normally on Online or on High Efficiency mode Orange On The UPS is on Battery mode Orange On The UPS is on Bypass mode Red On The UPS has...

Страница 13: ...n 60mn The alarm triggers when the set percentage of battery capacity or remaining back up time is reached High Efficiency mode The UPS is operating on High Efficiency mode The UPS is powering and pro...

Страница 14: ...ent Log Event filter Selects faults alarms and or events to display Event list Displays the events stored Reset fault list Clears events Fault log Fault list Displays the faults stored Reset fault lis...

Страница 15: ...BP Inv BP Inv Short circuit Inv Stop Inv BP Inv BP Inv IT Inv BP Inv Inv Stop Input volt hysteresis Sets input voltage hysteresis from 1 to 10V 10V High Efficiency mode Enabled Disabled Power the out...

Страница 16: ...the UPS in case of phase vs neutral wires swapping Disabled Power off Alert Enabled Disabled If Enabled activates a confirmation screen that requires user confirmation after pressing the power button...

Страница 17: ...l alarm Ext charger ON OVL pre alarm Relay Bypass DB9 1 On bat Low bat Bat fault Bypass UPS OK Load protected Load powered General alarm Ext charger ON OVL pre alarm DB9 1 Low bat DB9 7 On bat Low bat...

Страница 18: ...s 99s Sets delay before noticing on battery information to software 0s General alarm On battery Battery fault Internal fault Overload pre alarm Internal fault Ambient temp Fan lock Bypass overload Cur...

Страница 19: ...on the shipping carton label If the date has passed and the batteries were never recharged do not use the UPS Contact your service representative 3 3 2 2 C Ch he ec ck kiin ng g t th he e A Ac cc ce...

Страница 20: ...leaflet 22 Safety instructions 23 Quick start 24 Mounting kit for 19 inch enclosures 25 2 supports for tower position Elements supplied depending on the version or optional 26 NMC communication card o...

Страница 21: ...pplied depending on the version or optional 26 NMC communication card optional standard on Network Bundle options 27 HotSwap MBPmodule optional 28 Connection cables between Hotswap MBP module and UPS...

Страница 22: ...ts 3 3 3 3 T To ow we er r I In ns st ta alllla at tiio on n Tip If you ordered other UPS accessories refer to specific user manuals to check the tower installation with the UPS To install the cabinet...

Страница 23: ...Rev 01 17 Adjustment of the angle of vision of the LCD panel 3 3 4 4 R Ra ac ck k I In ns st ta alllla at tiio on n Rack mounting of UPS EBM and accessory modules Follow steps 1 to 4 for module mounti...

Страница 24: ...he UPS This is normal and will not harm personnel Insert the EBM cable into the UPS battery connector quickly and firmly 1 Plug the EBM power cable s into the battery connector s Up to 4 EBMs may be c...

Страница 25: ...omm Battery Comm Battery Comm EBM Communications wiring UPS EBM 1 EBM 2 EBM 3 EBM 4 NOTE The EBM communication wiring connections are directional and must be connected in the correct sequence to ensur...

Страница 26: ...mmunication wiring connections are directional and must be connected in the correct sequence to ensure proper detection regulation and lifecycle monitoring of the integrated battery management system...

Страница 27: ...oads to the outlets marked 5 and the non priority loads to the outlets marked 6 7 that can be programmed For the 9PX 3000RTAU model connect any high power devices to the 16 A outlet To program shutdow...

Страница 28: ...is still supplied 2 Set switch 33 back to Normal position The HotSwap MBP module has a rotary switch 33 with two positions Normal the load is supplied by the UPS LED 31 is on Bypass the load is suppl...

Страница 29: ...Installation of the communication cards 2 It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 2 secured by screws 2 Insert the communication card in...

Страница 30: ...rameter see Settings Com Settings Shutdown commands on page 16 the unit may startup automatically IMPORTANT Warning Signal inputs have no function by default please choose a function through the LCD S...

Страница 31: ...ctor type Terminal 14 AWG maximum wires External breaker specification 60 V DC 30V AC 20mA max RPO 11 ROO Remote Control Connection and Test 1 Check the UPS is shut down and the electrical supply netw...

Страница 32: ...alarm Choose events that will trigger this alarm trough the LCD Settings Com settings General alarm for more information on possible events please look at page 16 Ext charger ON Control an optional e...

Страница 33: ...te Eaton Intelligent Power Software suite is available from eaton com download Eaton Software suite provides up to date graphics of UPS power and system data and power flow It also gives you a complet...

Страница 34: ...28 Eaton 9PX Lithium Ion P 164001006 Rev 01 UPS Remote Control Functions...

Страница 35: ...start setting in ON OFF Settings in Table 6 To start the UPS on battery 1 Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS starting The U...

Страница 36: ...d your equipment is not protected however the utility power continues to be passively filtered by the UPS The indicator illuminates Depending on overload conditions the UPS remains in Bypass mode for...

Страница 37: ...imit and Bypass Voltage High Limit settings Bypass frequency is within nominal frequency 5 You can prohibit Bypass Never or always allow Bypass with no specification checking Always For Always on UPS...

Страница 38: ...ect Event log 2 Scroll through the listed events 5 5 1 10 0 R Re et tr riie ev viin ng g t th he e F Fa au ullt t L Lo og g To retrieve the Fault log through the display 1 Press any button to activate...

Страница 39: ...rical shock or burn from high short circuit current Observe the following precautions 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts...

Страница 40: ...hands to support the battery pack See Recycling the used equipment on page 38 for proper disposal 7 Verify that the replacement batteries have the same rating as the batteries being replaced 8 Put th...

Страница 41: ...gs Reset section before restarting the unit 6 6 3 3 B Ba at tt te er ry y S Se et tt tiin ng gs s R Re es se et t After replacement of the internal UPS batteries and extended battery modules and befor...

Страница 42: ...If optional EBMs are installed verify that the EBM are connected to the UPS See section 3 Verify that the UPS power cord is plugged in 4 The UPS front panel display illuminates and shows EATON logo 5...

Страница 43: ...cates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your local re...

Страница 44: ...38 Eaton 9PX Lithium Ion P 164001006 Rev 01 Recycling The Used Equipment...

Страница 45: ...To check the Event log or Fault log 1 Press any button on the front panel display to activate the menu options 2 Press the button to select Event log or Fault log 3 Scroll through the listed events or...

Страница 46: ...UPS transferred to Bypass mode the UPS will return to normal operation when the temperature drops 5 C below the warning level If the condition persists shut down the UPS Clear vents and remove any he...

Страница 47: ...k or distributor Units damaged in shipment as a result of improper packaging are not covered under warranty A replacement or repair unit will be shipped freight prepaid for all warrantied units IMPORT...

Страница 48: ...42 Eaton 9PX Lithium Ion P 164001006 Rev 01 CE Compliance Contact...

Страница 49: ...able 8 Extended Battery Module List Model Configuration Battery Voltage For Power Module 9PXEBM48RT1U L Rack Tower 48Vdc 1000 1500VA 9PXEBM72RT1U L Rack Tower 72Vdc 2200 3000VA Table 9 Weights and Dim...

Страница 50: ...IEC C14 IEC10A 9PX1500IRTANZ L 9PX2000IRTAU L IEC C20 IEC16A 9PX3000IRTANZ L Table 12 Electrical Output All Models Normal Mode Battery Mode Voltage Regulation 1 2 Efficiency 98 High Efficiency mode 9...

Страница 51: ...ower Factor Up to 0 9 Load Crest Ratio Up to 3 1 Table 13 Electrical Output Connections Model Output Connection Output Cable 9PX1000IRTANZ L 4 IEC10A 2 IEC10A group 1 2 IEC10A group 2 9PX1500IRTANZ L...

Страница 52: ...F with batteries 25 to 55 C 13 to 130 F without batteries Transit Temperature 25 to 55 C 13 to 130 F Relative Humidity 0 to 96 no condensing Operating Altitude Up to 3 000 meters 9 843 ft above sea l...

Страница 53: ...Eaton 9PX Lithium Ion P 164001006 Rev 01 47 Model Specifications...

Страница 54: ...P 16400100601 P 164001006 01...

Отзывы: