WARNING
Power is present inside the UPS cabinet.
6 4 4 Transfer from Bypass to normal mode
To transfer the critical load to Normal mode:
1. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
2. If not already selected, select UPS on the System Control screen.
3. On the UPS System Control screen, select the BYPASS
NORMAL command, then press the RETURN
pushbutton.
All of the UPSs transfer to Normal mode. If the power module is not available, the system remains on
bypass and an alarm sounds.
The NORMAL status indicator is illuminated.
WARNING
Power is present inside the UPS cabinet.
6 4 5 Single uPS Shutdown
To shut down the UPS:
1. Open the MOB for the UPS being shut down.
2. Select the CONTROLS symbol on the main menu bar. The System Control screen is displayed.
3. If not already selected, select UPS on the System Control screen.
4. On the UPS System Control screen, select the NORMAL
UPS OFF command, then press the RETURN
pushbutton.
The output and bypass backfeed contactors open, and the power module is turned off on the UPS being
shut down.
Logic power remains on.
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
5. Open the UPS input and, if installed, the bypass feeder circuit breakers for the UPS being shut down.
6. If EBCs are installed, open all battery breakers
The UPS is now completely shut down.
Eaton 9EHD UPS (20-40 kVA, 380/400/415V) Installation and Operation Manual
67