INM 9479-ET(G)-CSL Rev 1

Specific Conditions of Use (Special Conditions)

The following conditions relate to safe installation and/or use of the equipment.

8 .1

 For Group I, the modules shall each be mounted within an enclosure providing a 

degree of protection of at least IP54. 

 

 

 

 

 

This shall be in accordance with EN 60529, and the modules installed in a manner 

that does not impair the existing creepage and clearance distances. The enclosure 

shall also comply with the appropriate requirements of Clauses 7.4.2 and 7.5, or 8.2 

of EN 60079-0.

8 .2

 For Group II, the RJ45 connectors shall be fitted with either a plug or blanking 

plug.Alternatively, the module shall be mounted in an enclosure providing a degree 

of 

protection 

of 

at 

least 

IP20. 

      

This shall be in accordance with EN 60529, and the modules installed in a manner 

that does not impair the existing creepage and clearance distances. The enclosure 

shall also comply with the appropriate requirements of Clauses 7.4.2 and 7.5, or 8.3 

of EN 60079-0.

8 .3

 For Group III, the module shall be mounted inside a suitably certified enclosure 

which provides a minimum degree of protection of at least IP54. The module shall 

be installed in a manner that does not impair the existing creepage and clearance 

distances.

8 .4

 The supply to the modules must be derived from a suitably certified, intrinsically 

safe supply.

8 .5

 The values of Co and Lo shall apply when one of the two conditions below is 

given:
- The total Li of the external circuit (excluding the cable) is < 1% of the Lo value, or
- The total Ci of the external circuit (excluding the cable) is < 1% of the Co value.
The above parameters are reduced to 50% when both of the two conditions below 

are given:
- The total Li of the external circuit (excluding the cable) > 1% of the Lo, and
- The total Ci of the external circuit (excluding the cable) > 1% of the Co.
Note: the reduced capacitance of the external circuit (including cable) shall not be 

greater than 1µF for Group I and IIB/III and 600 nF for IIC.

8 .6

 The equipment shall be mounted on an earthed metal bracket or housing.

Marking

Each device is marked in accordance with the Directive and CE marked with the 

Notified Body Identification Number.

  

9479-ETG-CSL Product Label

Содержание 9479-ETG-CSL

Страница 1: ...9479 ET G CSL CSL Intrinsically Safe Gigabit Ethernet WLAN AP Bridge March 2021 INM 9479 ET G CSL Rev 1 Instruction manual MTL Industrial Network Solutions...

Страница 2: ...CLARATION OF CONFORMITY A printed version of the Declaration of Conformity has been provided separately within the original shipment of goods However you can find a copy of the latest version at http...

Страница 3: ...AL 4 7 WASTE REMOVAL INFORMATION 4 8 INSTALLATION 5 9 ATEX IECEx CERTIFICATION INFORMATION 6 10 SPECIFICATION 8 11 APPROVALS 9 12 NETWORK SETUP 10 12 1 Network Configuration 10 13 WI_FI SETUP 12 14 DH...

Страница 4: ...assemblies may not be used in explosion hazard area applications if they have been used previously in general electrical installations WARNING The responsibility for planning installation commissioni...

Страница 5: ...ia IIC T4 Ga Ex ia ia Da IIIC T135 C Db non mining Ex ia I Ma M1 mining ET version Ta 40 C to 70 C Zone 1 Zone 21 mounting Zone 0 Zone 20 with a suitable Ex ia Power Supply Note PoEx is a simple adap...

Страница 6: ...net connections these can allow daisy chaining of units together Power 12V DC is supplied to the module either locally or using Power over Ethernet PoEx from the LAN port This requires the PoEx output...

Страница 7: ...unction Gigabit Function 1 Tx BI_DA 2 Tx BI_DA 3 Rx BI_DB 4 PoEx 12V BI_DC 5 PoEx 12V BI_DC 6 Rx BI_DB 7 PoEx 0V BI_DD 8 PoEx 0V BI_DD Note PoEx only on LAN1 2 ports when 10 100 ET version only PoEx n...

Страница 8: ...C Bulkhead Socket SMA Plug length 1000mm RG316 Cable Assembly 5 DIMENSIONS Width 42mm Height 160mm Depth 140mm Weight 1500g Mounting Din Rail 6 ENVIRONMENTAL Operating Temperature 40 C 70 C Storage Te...

Страница 9: ...1 to the main power supply pins Con1 see connections section As the 9479 supports Auto MDI MDI X a straight connected RJ45 Cat5e cable is used to connect to any device It is recommended that Cat5e cab...

Страница 10: ...1 and EN 60079 26 Installation a Reference to the IEC code of practice IEC 60079 14 In addition particular industries or end users may have specific requirements relating to the safety of their instal...

Страница 11: ...3 For Group III the module shall be mounted inside a suitably certified enclosure which provides a minimum degree of protection of at least IP54 The module shall be installed in a manner that does not...

Страница 12: ...put 802 11n 2 4GHz 18 to 20 5 dBm 5GHz 15 to 18 dBm per antenna output in 2T 2R mode RX Sensitivity 802 11n 2 4GHz 92 to 73 dBm 5GHz 96 to 72 dBm Data Rates 802 11n up to 300Mbps 2T 2R 802 11a h 6 to...

Страница 13: ...IICT4 hazardous area 9479 ET Certification Code Ex ia IIBT4 Ga 9479 ETG Ex ia IICT4 Ga 9479 ET Ex ia ia Da IIIC T135 C Db non mining Ex ia I Ma M1 mining Ta 40 C to 70 C Certificate numbers ATEX CML 1...

Страница 14: ...ADD NETWORK button to create a new IP network Click the REMOVE button under the action heading to remove the selected network Click the EDIT button under the action heading to open the network configu...

Страница 15: ...the local area network DNS Server s The IP addresses of the DNS server s you want to use If you selected the DHCP protocol you can choose to use the value defined in the menu TOOLS System or you can...

Страница 16: ...figure the wireless network settings by default the radio will be disabled and you will need to turn in on Country The regulation rules of the selected country will determine the channels and transmis...

Страница 17: ...ferent frequency ranges HT high throughput mode In HT mode you can aggregate adjacent channels 2 in 802 11n 2 or 4 in 802 11ac in order to increase bandwidth One of the channels is the one selected in...

Страница 18: ...nd selecting All for this option Both are also required for 802 11n MIMO mode For single antenna use select Only 1 and connect the antenna to the AUX socket however performance will be reduced with a...

Страница 19: ...nning will not real this SSID on the AP Network This option allows selecting the network where the interface is added Mesh ID only in mess mode This option replaces the ESSID when the Mesh mode is sel...

Страница 20: ...ace DHCP pool first address if enabled First IP Address of the DHCP pool This is interpreted as an offset relative to network address DHCP pool size if enabled Maximum number of leased addresses Lease...

Страница 21: ...he network If this option is checked the DHCP server wont check for another server before start IPv4 Netmask This option override the default netmask value sent to DHCP clients DHCP Options This field...

Страница 22: ...vice Information page allows a quick overview of the unit s useful information and the currently installed firmware information 15 2 Network Interfaces This Page shows a summary of the currently confi...

Страница 23: ...e number of bytes of transmission and reception on the interface Packets graph Displays the number of processed dropped and error packets of transmission and reception on the interface Broadcast Multi...

Страница 24: ...the setup Network Page Subnet The subnet that this interface connects to and the number of subnet bits Threshold Minimum TTL required to forward data to this interface EN Multicasting is enabled on t...

Страница 25: ...erface toward the RP where data comes in Multicast Group The block of groups associated to this RP Priority Priority of the RP for elections Locally configured groups have a priority of 1 Hold Time Th...

Страница 26: ...ges will be left unchanged 19 Password These Pages allow you to change the Password on both the Root and the user accounts On initial power up both passwords are set empty this will allow you to enter...

Страница 27: ...This allows you to set the time zone you are in Device Location This is a user definable device location field Server name If there is a NTP server reachable on the network the unit can use it to con...

Страница 28: ...g This log displays a summary of the units configuration Kernal Log This log displays messages from the Linux kernel only System Log This log displays messages from both the kernel and from the runnin...

Страница 29: ...IP Address and UDP port where the log messages will be sent using the syslog protocol Leave empty to disable Log Settings These sections are used to configure logging for various services the message...

Страница 30: ...s to a file You are then able to restore the previously saved file back into the unit This will load up all of its previous settings Reset Clicking this button will restore its factory default setting...

Страница 31: ...27 INM 9479 ET G CSL Rev 1 This page is left intentionally blank...

Страница 32: ...Off Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San Bovio 3 20090 Segrate Mil...

Отзывы: