Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
www.eaton.com/powerquality
7-1
Chapter 7
Communication
This chapter describes the communication features of the Eaton 93PM UPS. For terminal wiring information,
see paragraph 3.2.4 and paragraph 4.7. For location of the customer interface panel and terminals, see
Figure 4-9 and Figure 4-10.
7.1
Minislot Cards
The Eaton 93PM UPS has four standard, factory-installed Minislot communication bays. See Figure 4-9 for bay
locations. The UPS is compatible with the following Minislot cards (see Figure 7-1):
l
The Power Xpert
®
Gateway Minislot (PXGMS) UPS Card provides Web-enabled, real-time monitoring of
Eaton 93PM uninterruptible power systems (UPSs) through standard Web pages, Power Xpert software,
Intelligent Power Manager (IPM), Intelligent Power Protector (IPP), or third-party software. As an integral
part of the Eaton Power Xpert Architecture
®
, the PXGMS UPS Card provides a central point to connect UPSs
to the Ethernet network.
Network managers can view critical downstream device information, such as status, power, energy, and
power quality data with an easy-to-use interface.
l
Industrial Relay Card-Minislot (IRC-MS)– can be used to indicate the operating status of the UPS system
using the customer's monitoring equipment. The Industrial Relay Card uses five isolated normally-open or
normally-closed dry relay contacts to indicate the UPS status. Normal, Bypass, Battery, and Alarm modes
can be monitored. See Table 7-1 for default triggers. The contact ratings and wire range are listed in the
IRC-MS installation guide. One input can be activated by a switch or dry contact. The voltage source is
provided by the card, no external voltage source is needed.
For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph 1.8). Refer
to the manual supplied with the Minislot card for user instructions.
Figure 7-1. Optional Minislot Cards
NOTE
Only one Power Xpert
®
Gateway Minislot UPS Card can be used at one time.
Table 7-1. IRC-MS Default Triggers
Relay
Trigger
K1
UPS supporting the load
K2
UPS on Battery
K3
Summary alarm
K4
UPS on bypass
K5
UPS battery low
Ident
Power
Act
100
PXGMS UPS
Restart
TX
RX
Setup
CMN
Status
DHCP
EMP
Ethernet 10/100
+
-
Industrial Relay
Card-Minislot (IRC-MS)
Power Xpert
®
Gateway
Minislot UPS Card
Содержание 93PM UPS
Страница 1: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Страница 2: ......
Страница 3: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Страница 25: ...Section 1 Installation...
Страница 26: ......
Страница 87: ...Section 2 Operation...
Страница 88: ......
Страница 145: ......
Страница 146: ...P 164000540 4 P 164000540 4...