Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
Table 2. UPS Cabinet Weights
Model
Weight kg (lb)
Shipping
Installed
Point Loading
Eaton 93PM-100-1
357 (786)
337 (743)
4 at 84 (186)
Eaton 93PM-100-2
414 (912)
394 (869)
4 at 98 (217)
Eaton 93PM-100-3
490 (1080)
470 (1037)
4 at 118 (259)
Eaton 93PM-100-1 UPS with Top Entry
Wiring Sidecar (no breakers)
429 (944)
406 (894)
4 at 102 (224)
Eaton 93PM-100-2 UPS with Top Entry
Wiring Sidecar (no breakers)
492 (1084)
469 (1034)
4 at 117 (259)
Eaton 93PM-100-3 UPS with Top Entry
Wiring Sidecar (no breakers)
562 (1238)
539 (1188)
4 at 135 (297)
Eaton 93PM-100-1 UPS with four breaker
Left or Right-Mounted SIAC-B
457 (1005)
433 (954)
4 at 108 (239)
Eaton 93PM-100-2 UPS with four breaker
Left or Right-Mounted SIAC-B
520 (1145)
496 (1094)
5 at 99 (219)
Eaton 93PM-100-3 UPS with four breaker
Left or Right-Mounted SIAC-B
590 (1299)
566 (1248)
4 at 142 (312)
Top Entry Wiring Sidecar (no breakers)
—
74 (162)
—
Four breaker SIAC-B
—
106 (233)
—
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are on top or in the back of the cabinet. Allow clearance in front of and on top or in
back of the cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in
Table 3. UPS Cabinet Clearances
From Front of Cabinet
914.4 mm (36") working space
From Top of Cabinet with Top Exhaust (Zones 1 and 3 – see
)
457.2 mm (18") minimum clearance for ventilation
From Top of Cabinet (Zones 2 and 3– see
)
457.2 mm (18") working space
From Top of Cabinet with rear service access (Zone 2– see
Can be less than 457.2 mm (18")
From Back of Cabinet with Rear Exhaust
254 mm (10") minimum clearance for ventilation
From Back of Cabinet with Top Exhaust
None Required
From Back of Cabinet – Seismic Installation
914.4 mm (36") working space
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required