46
Eaton 93PM Universal Integrated Battery Cabinet (IBC-LW and IBC-LHW) Installation Manual P-164000541—Rev 04
Figure 21. IBC Top Entry Conduit and Wire Entry Locations
Top Entry Conduit Landing
(Remove plate to drill or punch
conduit holes.)
44..44
B
Baatttteerryy B
Brreeaakkeerr IInnssttaannttaanneeoouuss TTrriipp S
Seettttiinngg
NOTE
The specified default instantaneous trip setting provides the maximum protection for
the batteries. Failure to adhere to 5x instantaneous trip setting voids the battery
warranty.
To verify the trip setting:
1.
Verify the UPS system is not in reserve mode or operating on battery. Refer to the applicable Eaton 93PM
UPS installation and operation manual, listed in paragraph
, for UPS operating
procedures.
2.
Verify the battery breaker instantaneous trip setting is set to 5 on all three trip dials (see
).
3.
If dials are not set to 5, set each to 5.
4.
Proceed to paragraph