98
Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
88..22..33
EEnnvviirroonnm
meennttaall aanndd S
Saaffeettyy S
Sppeecciiffiiccaattiioonnss
Operating Temperature
41°F to 104°F (5°C to 40°C).
Transit Temperature
-13°F to 140°F (-25°C to 60°C)
Storage Temperature
-13°F to 131°F (-25°C to 55°C)
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Transit Altitude
15000m (49213 ft)
Ventilation
50 kW:
Natural convection air cooling for rear exhaust
Natural convection air cooling for top exhaust
50 kW with 208V/480V input transformer:
Forced air cooling for top exhaust
Forced air cooling for rear exhaust
100 kW:
Natural convection air cooling for rear exhaust
Forced air cooling for top exhaust
100 kW with 208V/480V input transformer:
Forced air cooling for top exhaust
Forced air cooling for rear exhaust
150 kW:
Forced air cooling for rear exhaust
Forced air cooling for top exhaust
200 kW:
Forced air cooling for rear exhaust
Forced air cooling for top exhaust
Relative Humidity
(operating and storage)
5–95%, noncondensing
Acoustical Noise
Not applicable
Safety Conformance
UL1778 5
th
edition
Agency Markings
cULus
EMC (Class A)
FCC Part 15 Class A and 62040-2 c3
Содержание 93PM IAC-D