Batteries
2006/66/EC on batteries and accumulators and waste batteries and
accumulators
Packaging
94/62/EC on packaging and packaging waste
9
9..3
3
U
UPPSS eennvviirroonnm
meennttaall ssp
peecciiffiiccaattiioonnss
Table 25. UPS environmental specifications
Acoustic noise at 1 m
Rear exhaust
Top exhaust
74 dB(A)
77 dB(A)
Temperature range, operation
Eaton 93PM G2 xxx(200) and 93PM G2 xxx(300)
models
+5 °C ... +40 °C
Recommended range *
+20 °C ... +25 °C
Temperature range, operation
Eaton 93PM G2 xxx(240) and 93PM G2 xxx(360)
models
+5 °C ... +35 °C
Recommended range *
+20 °C ... +25 °C
Temperature range, storage and transportation
-25 °C ... +55 °C
Relative Humidity
Recommended range *
5 % - 95 %
20 % - 60%
Condensation
No condensation allowed
Maximum rate of temperature change **
1.67 °C / 5min
Operating altitude
1000 m without derating
Up to 2000 m with 1% derating per each additional
100 m above 1000 m
Over voltage category
OVC III
Pollution degree
PD 2
* ) For maximum lifetime for UPS and batteries, keep the environment in the recommended range.
** ) Limit based on ASHRAE 90.1-2013. Rapidly increasing temperature may cause condensation on
colder surfaces.
For more technical details please refer to the technical specification of the 93PM G2.
EATON 93PM G2 UPS
USER’S AND INSTALLATION GUIDE
P-164000956 - February 2021
www.eaton.eu
9
91
1