Item
Value
Battery charging capacity
20 A/100 kVA
Note: The input voltage has also
impact to the maximum charging
current. With the input voltage level
of 220 V and 100% load the maxi-
mum charging current is lower than
20 A.
Battery type
VRLA (valve regulated lead acid), 12 VDC
Battery quantity
36 (216 cells), 38 (228 cells) or 40 (240
cells) blocks
Note: Do not connect battery
strings with different battery quanti-
ty and voltage in parallel!
Recharge profile
ABM or float charge
End of discharge voltage
1.85 V/cell for 36 blocks
1.75 V/cell for 38 blocks
1.67 V/cell for 40 blocks
9.3 UPS system output
Table 26: UPS output
Item
Value
Number of output phases
3 phases, N
Output voltage regulation
± 1% (10% to 100% load)
Nominal output voltage
380 Vac, 400 Vac and 415 Vac nominal
Output voltage distortion, uTHD
< 2% maximum THD (linear load)
Output current
Output voltage balance
< 1% for 100% maximum load imbalance
(linear load)
Output voltage phase displacement
< 1.5° for 100% maximum load imbalance
(linear load)
Rated output frequency
50 or 60 Hz, user configurable
Frequency variation
± 0.1 Hz free running
Synchronous to bypass
± 4 Hz (default setting)
Frequency slew rate
3 Hz per second (default setting)
Load power factor (permitted range)
0.9 p.f. Leading
0.7 p.f. Lagging