UPS Installation Plan and Unpacking
3-2
Eaton
®
Power Xpert
®
9395C UPS Installation and Operation Manual
P-164000821—Rev 01
www.eaton.com/powerquality
l
The other aspect is the rate of change of temperature and/or RH, which can occur during transitions within
the cooling system. Examples: changing the mixture ratio of inside versus outside air, or external changes in
the outside air when going from nighttime into day, and back to night.
When ignored, either one of these aspects can create an undesirable microclimate at the UPS location. If the
environment created by this microclimate exceeds the Eaton 9395C-1100 UPS operating specification, the UPS
reliability, over time, will be reduced. These same environmental extremes will also create reliability concerns
for any servers that are exposed to them.
3.2.2
Installation Considerations
The UPS system installation must meet the following guidelines:
l
The system must be installed on a level floor suitable for computer or electronic equipment.
l
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the maximum weight requirements shown in Table 3-1
and the size requirements shown in Figure 3-1 through Figure 3-9. Dimensions are in millimeters (inches).
Table 3-1 includes the weights of the heaviest cabinet configuration. Actual weights may be less due to the
installed configuration. Weights are in kilograms (pounds).
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper air
circulation. The clearances required around the UPS cabinet are shown in Table 3-2. Dimensions are in
millimeters (inches).
The basic environmental requirements for operation of the UPS are:
l
Recommended Operating Range: 20–25°C (68–77°F)
l
Maximum Relative Humidity: 95%, non-condensing
Table 3-1. UPS Cabinet Maximum Weights
Model
Section
Maximum Weight
kg (lb)
Shipping
Installed
Eaton 9395C-1000/1000
Eaton 9395C-1000/1100
Eaton 9395C-1100/1100
UPS (Total)
2539.8 (5599)
2401.8 [5295]
ISBM
817.4 (1802)
773.4 (1705)
PM
1722.4 (3797)
1628.4 (3590)
NOTE Table 3-4 describes power ratings
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18”) minimum clearance for ventilation
From Front of Cabinet
1067mm (42") working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required