The following is a step-by-step tutorial for replacing the batteries:   

1.

 

The front panel of the UPS can be removed by pushing where the arrows indicate in the 
pictures above. Next, unscrew the screws and remove the metal battery cover. 

2.

 

Remove the battery cartridge from the UPS. The voltage in all models will be less than 
48Vdc once the battery is disconnected from the UPS. 

3.

 

Replace the batteries. 

4.

 

Push the cartridge with the new batteries back into the UPS. 

5.

 

Reinstall the metal plate and the front panel. 

 

 

 

 

 

27

 

10.1 Power Range 700-3000 VA (LV) 

GENERAL 

Rated power 

700VA, 1000 VA, 1500 VA, 2000 VA, 3000 VA at p.f 0.7 

Technology 

On-line, double conversion topology with automatic bypass

 

INPUT 

Phase: 

Single phase with ground 

Bypass Voltage 

96-138 VAC (user selectable) 

Input Voltage range: 

60/70/80VAC-144 VAC 

Frequency: 

50/60 Hz. Auto selection 

Frequency window from mains 

45-65 Hz 

Synchronization window 

± 3Hz. 

Input current 

700 VA 5.8A, 1000 VA 8.2A, 1500 VA 12.4A, 2000 VA 16.5A 

3000 VA 24.7A 

Input Power factor: 

0.97 

OUTPUT 

Output Voltage: 

100/110/115/120/127 VAC, selectable from LCD panel 

Voltage regulation: 

± 2% 

Voltage distortion: 

< 5% THD at full non-linear load, < 3% THD at full linear load 

Frequency regulation 

± 0.25 Hz (battery or free running mode) 

* 60V at 40% load, 70V at 70%, 80V at 100%. 

10.2 Power Range 700-3000 VA (HV) 

GENERAL 

Rated power 

700VA, 1000 VA, 1500 VA, 2000 VA, 3000 VA at p.f 0.7 

Technology 

On-line, double conversion topology with automatic bypass 

INPUT 

Phase 

Single phase with ground 

Bypass Voltage:   

184-265 VAC (user selectable) 

Input Voltage range:   

120/140/160 VAC-276 VAC 

Frequency: 

50/60 Hz. Auto selection 

Frequency window from mains 

45-65 Hz 

Synchronization window 

± 2.5Hz. 

Input current 

700 VA 3A, 1000 VA 4A, 1500 VA 5.7A, 2000 VA 7.7A, 3000 VA 

12A 

Input Power factor: 

0.97 

9. Technical  Specifications 

Содержание 700VA

Страница 1: ...easures z Place the receiving antenna in a separate location or orientation z Ensure a greater distance is achieved between the receiver and the equipment z Ensure that your equipment is connected to...

Страница 2: ...isk of electric shock do not remove cover No user serviceable parts inside Refer servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is...

Страница 3: ...ly detailed requirements of the UPS units are described herein and installation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation...

Страница 4: ...eports any problems on the LCD display An advanced battery management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of...

Страница 5: ...operations are to be performed exactly as instructed in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operato...

Страница 6: ...he following illustration Vertical Installation Wall mounted installation 7 Installation with accessories of Rack mounted types Please install the types of units according to the following illustratio...

Страница 7: ...8 Installation with accessories of Stack types Please install the types of units according to the following illustration Stack installation 9 5 2 Rear panel views 700 1 5KVA REAR PANEL...

Страница 8: ...10 2K 3KVA REAR PANEL 11 RM 1U 700 1KVA Rear Panel...

Страница 9: ...12 RM 2U 700 1K 1 5KVA Rear Panel 13 RM 2U 2K 3KVA Rear Panel...

Страница 10: ...instantly shows a Site Wiring Fault rotate the connector Schuko see chapter 7 4 z After charging connect the loads to the UPS see the example in fig 3 z Do not connect any devices that have the possi...

Страница 11: ...ctions 2 TxD Output TxD Output 3 RxD Input RxD Inverter Off Input 5 Common Common 6 Output Ac Fail Output 8 Output Low Battery Output 9 Output 12 VDC Power Caution Max rated values 12Vdc 17 USB port o...

Страница 12: ...off the UPS 2 is a Enter button Use this button to check content of UPS and the method is listed below a Push the button at least 2 seconds to check content of UPS Each content can be displayed by pr...

Страница 13: ...URE xxC Shows approximate ambient temperature BAT PACK NUM x Shows External Battery Pack Number RATING xxxxVA Shows UPS Rating CPU VERSION xx x Shows CPU Version 21 UPS configurations 1 Various settin...

Страница 14: ...32 communication RS232 Control Set RS232 communication enable or disable Enable Disable Enable 23 Manual test of the UPS Manual UPS or Manual Battery tests can be conducted from the UPS configuration...

Страница 15: ...er second High internal DC bus Voltage Turn off protected loads Turn off UPS and call your local dealer Site wiring Fault 1 Beep per second Voltage detected Between Neutral and Ground UPS mains connec...

Страница 16: ...144 VAC Frequency 50 60 Hz Auto selection Frequency window from mains 45 65 Hz Synchronization window 3Hz Input current 700 VA 5 8A 1000 VA 8 2A 1500 VA 12 4A 2000 VA 16 5A 3000 VA 24 7A Input Power...

Страница 17: ...attery mode 700 1000 VA 50 db normal and battery mode 1500 3000 VA 29 STANDARDS Safety EN50091 1 1 Emissions EN50091 2 Immunity EN50091 2 B 700 1500VA A 2K 3KVA HV Model OUTPUT POWER 700VA 490 W 1000V...

Страница 18: ...o 90 3 hours to 90 3 hours to 90 Dimensions W x D x H mm 152 x 420 x 238 152 x 420 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360 Weight kg 13 5 16 2 17 31 6 33 31 19 Rack mount Model 2U OUTPUT...

Страница 19: ...20 x 238 152 x 420 x 238 225 x 425 x 360 225 x 425 x 360 Dimensions W x D x H mm RM2U 428 x 425 x 84 428 x 425 x 84 428 x 425 x 84 428 x 610 x 84 428 x 610 x 84 Tower 21 21 21 42 42 Weight Kg RM2U 22...

Отзывы: