I.L. 17562
PR 0.3 Effective 8/99
DANGER
The contactor control circuit is to be reconnected. At this time the motor associated with the
application can be started. It is important to ensure that all safety precautions associated with
rotating equipment and the associated driven mechanism be taken. Failure to do so can result in
serious or fatal injury and/or equipment damage.
q
Disconnect all ac power from the system.
q
Reconnect the contactor lead to MP-3000 trip relay terminal 12.
q
Check all rotating components and driven mechanisms associated with the motor for secure
connections.
q
Clear away any loose or foreign objects.
q
Clear all personnel from the area of the motor and driven mechanisms.
q
Turn on all ac power.
q
Make sure the MP-3000 Protection LED is on, and that the display says READY--3.
q
Follow any startup procedures for the load equipment.
q
Start the motor using the external start switch or contacts.
q
Using the information supplied by the application engineer or equipment manufacturer, verify
that the motor is operating properly.
q
With the motor running, use a clamp-on type ammeter to measure the ac current on each of
the motor phases.
q
Verify that the I
A,
I
B,
and I
C
currents, as indicated by the MP-3000 on the MONT I Page of the
Monitor mode are within about 5% of the ammeter values.
q
If the current during this test is well below FLA, or if the cts are far from the optimum ratio,
errors may be larger. This test is intended to show incorrectly set ct ratios or faulty wiring,
rather than precision of measurements.
q
If a ground Ct is connected, check ground current IG. Investigate the cause of any abnormal
ground leakage current flow.
q
Check the percent unbalance display %UB for consistency with the ammeter measurements,
given the acceptable error ranges.
q
A negative sign on the unbalance display indicates that the relay is programmed for a
reversing motor, and that it believes the motor is running in reverse. Since an MP-3000
programmed for a reversing starter won't trip for reversed phase sequence, this gives a
convenient check that the phase sequence is properly wired.
q
If the analog transducer output is connected, determine which measurement it is transmitting
- view setpoint P11L1.
q
Check that the analog output current corresponds to the displayed value of the selected
parameter.
q
If a PowerNet data communications host is connected, upload the starting current profile and
check for coordination with cold-start protection curves on the PowerNet display.
q
It is wise to verify the ability of the MP-3000 to open the contactor and trip the motor. The
easiest way is by remote trip, via remote trip contact or data communications. Many other
internal functions can be manipulated to force a relay trip. One technique is to connect a
shorting jumper across the relay current terminals for one of the three phases - this should
produce an unbalance trip, or a thermal trip after some time.
Содержание 66D2032G01
Страница 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Страница 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Страница 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Страница 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Страница 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Страница 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Страница 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Страница 77: ...I L 17562 Page 77 PR 0 3 Effective 8 99 Figure 6 6 Typical Ct Circuits and Motor Control Wiring...
Страница 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Страница 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Страница 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Страница 88: ...Page 88 I L 17562 PR 0 3 Effective 8 99 Figure 8 1 System Overview Figure 8 2 Torques from Sequence Currents...
Страница 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Страница 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Страница 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Страница 103: ...I L 17562 Page 103 PR 0 3 Effective 8 99 Figure 9 4 Motor Protection Curve Example without RTDs...
Страница 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Страница 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Страница 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...