Страница 1: ...600 A 15 25 kV class PUSH OP deadbreak connector installation instructions COOPER POWER SERIES Deadbreak Apparatus Connectors MN650057EN Effective May 2017 Supersedes May 2014 S600 13 3...

Страница 2: ...TING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In no event...

Страница 3: ...ON Introduction 1 Handling and storage 1 Standards 1 INSTALLATION INSTRUCTIONS Equipment required 2 Cable preparation 2 Install PUSH OP connector on apparatus bushing 5 iii 600 A 15 25 KV CLASS PUSH O...

Страница 4: ...formation DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low voltage line...

Страница 5: ...carrier immediately Handling and storage Be careful during handling and storage of the PUSH OP deadbreak connector to minimize the possibility of damage If the connector is to be stored for any lengt...

Страница 6: ...ded longitudinally corrugated wire shielded or UniShield use Eaton s SA series adapter kit with the same cutback dimensions as concentric neutral below If another manufacturer s metallic shield adapte...

Страница 7: ...d with the connector Start crimping just below the first line from the spade end of the connector Rotate each successive crimp working towards the cable adapter Do not overlap crimps Clean excess inhi...

Страница 8: ...e the alignment segment from the LRTP Recycle the align ment segment See Figure 9 for illustration of completed LRTP installation Step 8 Install probe Place tin plated copper PUSH OP probe with stud o...

Страница 9: ...2 Release operating eye from clampstick Push forward on push plate firmly with clampstick until a bump is felt and latch plate fully engages locking teeth Refer to Figure 13a Pull on push plate with c...

Страница 10: ...push plate while threading locking pin as this can cause the latch plate to become disengaged from the locking teeth This condition can cause the PUSH OP deadbreak connector to come off of the bushing...

Страница 11: ...e to LRTP grounding tab and shroud grounding tab Connect drain wire to PUSH OP body grounding tab and shroud grounding tab Connect one strand of cable concentric neutral to shroud grounding tab Connec...