Page 25
620-00082-01-us (en)
ENGLISH
6. Appendices
6.1 Technical specifications
Tower
5P 750
5P 1000
5P 1500
Rack
5P 550 R
5P 750 R
5P 1000 R
5P 1500 R
Output Power @ 120 V
550 VA
420 W
750 VA
600 W
1000 VA
770 W
1440 VA
1100 W
Output Power capacity
@ 125 V
550 VA
420 W
750 VA
600 W
1000 VA
770 W
1440 VA
1100 W
Output Power @ 100 V
458 VA
350 W
625 VA
500 W
833 VA
641 W
1080 VA
825 W
AC Input power
•
Rated input voltage
•
Input voltage range
•
Input frequency range
Single phase 100-125 V
80 to 162 V
(1)
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
(2)
Output on battery power
•
Voltage
•
Frequency
100/120 V (-10/+6 %)
(3)
50/60 Hz ±0.1 Hz
Battery
(sealed lead acid,
maintenance free)
•
Standard
Tower
2 x 12 V
7 Ah
2 x 12 V
9 Ah
3 x 12 V
9 Ah
Rack
2 x 6 V
9 Ah
4 x 6 V
7 Ah
4 x 6 V
9 Ah
6 x 6 V
9 Ah
Environment
•
Operating
temperature range
•
Storage
temperature range
•
Relative humidity
•
Noise level
0 to 35 °C
0 to 40 °C
-15 to +50 °C
0 to 90 % (without condensation)
< 40 dBA
(1)
The high and low thresholds can be adjusted using UPS settings.
(2)
Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).
(3)
Adjustable to 100/120/125 V, must be set to the identical AC power source value.
For 5P Models - "CAUTION - To reduce the risk of fire, connect only to a circuit provided with 20 amperes
maximum branch circuit overcurrent protection in accordance with the National Electric Code,
ANSI/NFPA 70".
This product is designed for IT power distribution system.
Filter
Transformer
"AVR"
Charger
Inverter
Battery