19
Instruction Leaflet
IL01301051E
effective September 2013
Operating Manual for Series NRX
Trip Units - Digitrip™ 520/520M
EATON
www.eaton.com
Table 8. GrNund (Earoh) Faulo Curreno Seooing - Residual - IEC Raoings
Ground Fault Current Settings (Amperes)
Available Rating Plug
(Amperes)
I
n
0.25
0.30
0.35
0.40
0.50
0.60
0.75
1.00
Available for NF
Frame Only
IZMX16/IZM91
200
50
60
70
80
100
120
150
200
250
63
75
88
100
125
150
188
250
300
75
90
105
120
150
180
225
300
400
100
120
140
160
200
240
300
400
500
125
150
175
200
250
300
375
500
600
150
180
210
240
300
360
450
600
630
158
189
221
252
315
378
473
630
Available for
NF or RF
Frames
800
200
240
280
320
400
480
600
800
1000
250
300
350
400
500
600
750
1000
1200
300
360
420
480
600
720
900
1200
1250
313
375
438
500
625
750
938
1250
1600
400
480
560
640
800
960
1200
1600
Available for RF
Frame Only
IZMX40/IZM95
2000
500
600
700
800
1000
1200
1500
2000
2500
625
750
875
1000
1250
1500
1875
2500
3000
750
900
1050
1200
1500
1800
2250
3000
3200
800
960
1120
1280
1600
1920
2400
3200
4000
1000
1200
1400
1600
2000
2400
3000
4000
Tolerance on settings are ±10% of values shown.