17 Technical data
ESR5-NV3-300
12/19 MN049006EN
www.eaton.com
25
Ambient conditions
Ambient temperature (operation)
-20 °C - 55 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C - 70 °C
Max. permissible relative humidity (operation)
75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)
75 % (on average, 85% infrequently, non-condensing)
Maximum altitude
≤
2000 m (Above sea level)
Shock
15 g
Vibration (operation)
10 Hz - 150 Hz, 2 g
Certification / Approvals
Conformance
CE-compliant
Approvals
Safety data
Stop category according to IEC 60204
0 (undelayed contacts)
1 (delayed contacts)
Safety parameters for IEC 61508 - High demand
SIL
3 (for delayed contacts SIL 2)
PFH
d
1.89 x 10
-9
per hour
Demand rate
< 12 months
Proof test interval
240 months
Duration of use
240 months
The specifications apply assuming the following calculation basis
B
10d
230000 (at 3
A
AC-15)
Cycles
8760 per year
Safety parameters for IEC 61508 - Low demand
SIL
3 (for delayed contacts SIL 2)
PFD
avg
1.43 x 10
-4
Proof test interval
19 months
Duration of use
240 months
Safety characteristic data according to EN ISO 13849
Category
4 (undelayed contacts)
3 (delayed contacts)
Performance Level
e (for delayed contacts PL d)
Duration of use
240 months
For applications in PL e, the required demand rate for the safety function is once per month.
Calculation basis:
B
10d
230000 (at 3
A
AC-15)
Cycles
8760 per year
Safety parameters for EN 62061
SILCL
3 (for delayed contacts SILCL 2)
ID 0600000000
Product Safety
Functional
Safety
Содержание 171858
Страница 1: ...Manual ESR5 NV3 300 Safety relay 12 19 MN049006EN...
Страница 4: ......