Eaton 150 VCP-WL Скачать руководство пользователя страница 13

IB131021EN

                                                       

    Page vii                  

Effective Mar 2018

3-1

GENERAL

Type  VCP-WL  Vacuum  Circuit  Breaker  Elements  are 
subjected  to  complete  factory  production  tests  and 
inspection  before  being  packed.  They  are  shipped  in 
packages  designed  to  provide  maximum  protection  to the 
equipment  during  shipment  and  storage  and  at  the  same 
time to provide convenient handling.

3-2

RECEIVING

If the circuit breaker element is not to be used immediately 
but  is  to  be  placed  in  storage;  maximum  protection  can  be 
obtained by keeping it packed as shipped.

Upon  receipt  of  the  equipment,  inspect  the  containers  for 
any  signs  of  damage  or  rough  handling.  Open  the 
containers carefully to avoid any damage to the con-tents. 
Use  a  nail  puller  rather  than  a  crow  bar  when  required. 
When opening the containers, be careful to save any loose 
items  or  hardware  that  may  be  otherwise  discarded  with 
the packing material. Check the contents of each package 
against the packing list.

Examine  the  circuit  breaker  element  for  any  signs  of 
shipping  damage  such  as  broken,  missing  or  loose 
hardware,  damaged  or  deformed  insulation  and  other 
components.  File  claims  immediately  with  the  carrier  if 
damage  or  loss  is  detected  and  notify  the  nearest  Eaton 
Office.

3-3

HANDLING

 

CAUTION

DO  NOT  USE  ANY  LIFTING  DEVICE  AS  A  PLATFORM 
FOR  PERFORMING  MAINTENANCE,  REPAIR  OR 
ADJUSTMENT  OF  THE  BREAKER  OR  FOR  OPENING, 
CLOSING  THE  CONTACTS  OR  CHARGING  THE 
SPRINGS.  THE  CIRCUIT  BREAKER  ELEMENT  MAY 
SLIP OR FALL CAUSING SEVERE PERSONAL INJURY. 
ALWAYS  PERFORM  MAINTENANCE,  REPAIR  AND 
ADJUSTMENTS  ON  A  SOLID  WORK  SURFACE 
CAPABLE 

OF 

SUPPORTING 

THE 

BREAKER 

ELEMENT.

When  a  breaker  element  is  ready  for  installation,  a  lifting 
yoke in conjunction with an overhead lifter or portable floor 
lifter  can  be  used  to  move  a  breaker  element.  When  a 
breaker element is to be lifted, position the lifting yoke over 
the  breaker  element  and  insert  the  lifter  tabs  into  the 

breaker element side openings  with  the  lifting  hole  toward 
the interrupters. Once the lifting yoke is securely seated in 
the  holes,  the  breaker  element  can  be  carefully  lifted  and 
moved.

3-4

STORAGE

If  the  circuit  breaker  element  is  to  be  placed  in  storage, 
maximum protection can be obtained by keeping it packed 
as shipped. Before placing it in storage, checks should be 
made  to  make  sure  that  the  breaker  element  is  free  from 
shipping damage and is in satisfactory operating condition.

The  circuit  breaker  element  is  shipped  with  its  contacts 
open and capacitor bank discharged. The indicators on the 
front panel should confirm this.

Outdoor  storage  of  the  breaker  element  is  NOT 
recommended.  If  unavoidable,  the  outdoor  location  must 
be  well  drained  and  a  temporary  shelter  from  sun,  rain, 
snow,  corrosive  fumes,  dirt,  falling  objects  and  excessive 
moisture must be provided. Containers should be arranged 
to  permit  free  circulation  of  air  on  all  sides  and  temporary 
heaters  should  be  used  to  minimize  condensation. 
Moisture can cause rusting of metal parts and deterioration 
of  high  voltage  insulation.  A  heat  level  of  approximately 
400  watts  for  each  100  cubic  feet  of  volume  is 
recommended  with  the  heaters  distributed  uniformly 
throughout the structure near the floor.

Indoor  storage  should  be  in  a  building  with  sufficient  heat 
and air circulation to prevent condensation. If the building is 
not  heated,  the  same  general  rule  for  heat  as  for  outdoor 
storage should be applied.

3-5

TOOLS AND ACCESSORIES

Tools  and  accessories,  both  standard  and  optional  are 
available for use with the circuit breaker element
(Figure 

3-1

).

Содержание 150 VCP-WL

Страница 1: ...Effective Mar 2018 Instructions for Installation Operation and Maintenance of Type VCP WL Vacuum Circuit Breakers IB131021EN...

Страница 2: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 3: ...Effective Mar 2018 IB131021EN...

Страница 4: ...QUIPMENT TO FAIL RESULTING IN DEATH BODILY INJURY AND PROPERTY DAMAGE ALL SAFETY CODES SAFETY STANDARDS AND OR REGULATIONS AS THEY MAY BE APPLIED TO THIS TYPE OF EQUIPMENT MUST BE STRICTLY ADHERED TO...

Страница 5: ...CIRCUIT BREAKER STRUCTURE INTERFACING 21 SECTION 5 DESCRIPTION ANDOPERATION 23 5 1 INTRODUCTION 23 5 2 INTERRUPTER ASSEMBLY 23 5 3 ELECTROMAGNETIC MECHANISM 26 5 4 CONTROL SCHEMES 29 5 5 INTERLOCKS AN...

Страница 6: ...REAKER FRONT COVER ARRANGEMENT 13 FIGURE 4 1A INSERTION OF THE DRAWOUT EXTENSION RAILS 15 FIGURE 4 1B LIFTING AND SETTING THE BREAKER IN THE HOUSING 15 FIGURE 4 1C BPI PAN ASSEMBLY 17 FIGURE 4 2 ENGAG...

Страница 7: ...power facilities or claims against the purchaser or user by its customers resulting from the use of the information and descriptions contained herein 1 1 2 SAFETY PRECAUTIONS All safety codes safety...

Страница 8: ...AND OR MINIMOD IS CONTINGENT UPON PROPER APPLICATION CORRECT INSTALLATION AND ADEQUATE MAINTENANCE THIS INSTRUCTION BOOK MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO OBTAIN OPTIMUM PERFORMANCE FOR...

Страница 9: ...pping Delay Y Current Values Withstand Test Voltage Continuous Current at 60 Hz Short Circuit Current at Rated Max kV I Closing and Latching Capability 2 7 K Times Rated Short Circuit Current Closing...

Страница 10: ...Page iv IB131021EN Effective Mar 2018 OUTLINES AND DIMENSIONS 1 4 Figure 1 1 Type VCP WL Circuit Breaker Outlines and Dimensions Front View...

Страница 11: ...ective Mar 2018 Side View SECTION 2 SAFE PRACTICES 2 1 RECOMMENDATIONS Type VCP WL Vacuum Circuit Breaker Elements are equipped with high speed high energy operating mechanisms and are designed with s...

Страница 12: ...on the extension rails while performing such activities as charging closing and tripping Carelessness could cause the circuit breaker to fall from the rails resulting in personal injury to those in th...

Страница 13: ...yoke in conjunction with an overhead lifter or portable floor lifter can be used to move a breaker element When a breaker element is to be lifted position the lifting yoke over the breaker element and...

Страница 14: ...ng Transport Dolly Used to insert or withdraw breaker from lower compartment without portable lifter or move breaker from one location to another Style 6510C71G11 for VCP WL Electrical Levering In Dev...

Страница 15: ...Figure 3 1 Typical VCP WL Tools and Accessories Note Products shown for representation only New products may include design improvements and alternate nameplate configurations...

Страница 16: ...it Breaker Newer model Breakers may not have the escutcheon as shown 1 Front Panel 5 Mechanism Enclosure 2 Levering Latch 6 Lifting Yoke Opening 3 Wheel 7 Primary Disconnect 4 Ground Contact Figure 3...

Страница 17: ...IB131021EN Page xi Effective Mar 2018 1 Electro Magnetic Actuator 5 Closing Coil Capacitor Bank 2 Auxiliary Switch 6 Optional Under Voltage Relay 3 Power Supplies 4 Controller 1 2 4 3 5 6...

Страница 18: ...Page xii IB131021EN Effective Mar 2018 Figure 3 4 VCP WL Mechanism Details 1 Yoke 2 Output Plates 3 Cam Blocks 4 Cross Members 1 2 3 4...

Страница 19: ...ar 2018 Figure 3 5 Typical Rear View VCP WL Vacuum Circuit Breaker Element Vacuum Interrupter 1 Drive Rod Housing 2 Drive Rod Assembly 3 Bell Cranks 4 Figure 3 6 Typical VCP WL Vacuum Circuit Breaker...

Страница 20: ...v IB131021EN Effective Mar 2018 Nameplate 5 Breaker Charged Discharged Indicator 1 Operation Counter 6 Manual Close Button 2 Open Closed Indicator 7 Manual Open Button 3 Emergency Open Handle 4 1 2 3...

Страница 21: ...xceed the values specified Record the values obtained for future reference 4 5 NAMEPLATE Compare the circuit breaker nameplate information with switchgear drawings for compatibility 4 6 ELECTRICAL OPE...

Страница 22: ...er compartment see Figure 4 1A and Figure 4 1B Figure 4 1A Insertion of the Drawout Extension Rails F i g u r e 4 1 B Lifting and Setting the Breaker in the Housing Checking pan operation A T o o p e...

Страница 23: ...ER THE CIRCUIT BREAKER FROM TEST OR CONNECTED POSITIONS CORRECT OPERATION OF SOME OF THE INTERLOCKS IS DEPENDENT ON USE OF THE PROVIDED LEVERING CRANK PERSONAL INJURY OR EQUIPMENT DAMAGE COULD RESULT...

Страница 24: ...CODE PLATES 2 LEVERING SYSTEM 12 PROVISION FOR PADLOCKING 3 AUTOMATIC SECONDARY 13 METAL FRAMEWORK 4 RACKING SCREW 14 BREAKER RAIL 5 MOVING BLOCK 15 MR2 INTEGRAL RACKING PROVISIONS 6 SLIDER 7 BREAKER...

Страница 25: ...ewing position when the breaker is fully connected BPI breaker position indication Label Represents positive indication of breaker location at any position through use of a colored label mounted on th...

Страница 26: ...and engage the secondary contacts following the procedure described in paragraph 4 8 1 As soon as the cap bank is charged the condition will be indicated by a Breaker Charged Discharged Indicator on...

Страница 27: ...ure 4 3 Typical VCP WL Circuit Breaker Bottom View Ground Contact 5 Trip Floor Tripper 1 Secondary Disconnect 6 Code Plates 2 Close Floor Tripper 7 MOC Operator 3 Extension Rail Interlock 4 1 2 3 5 7...

Страница 28: ...erences The following interlocks are provided to ensure safe and proper operation Code Plates Code plates are provided to prevent the insertion of a circuit breaker into a structure of a higher power...

Страница 29: ...ers will automatically begin to open uncovering fixed primary contacts TOC switches will also operate once the CONNECTED position is reached if TOC switches are provided in the structure Remove the le...

Страница 30: ...ce The flexible shunt is a non sliding current transfer system between the movable stem and the bottom conductor which eliminates the need for maintenance Figure 5 1 Multiple finger floating type prim...

Страница 31: ...checked during standard inspection and maintenance intervals as discussed in Section 6 of this document to ensure it is within the specified limits on each phase The contact wipe can be increased if i...

Страница 32: ...agraph 6 5 for information on Contact Erosion F i g u r e 5 3 M e a s u r ement of Contact Stroke Figure 5 4 Loosening the Drive Rod Housing Jam Nut Figure 5 5 Measurement of Contact Open Gap 5 3 ELEC...

Страница 33: ...acitors which store energy to open and close the circuit breaker The controller has an internal capacitor which stores energy for a tripping operation The controller charges an external capacitor bank...

Страница 34: ...rom initiation of close signal to contact make 65 milliseconds MAX Opening Time from initiation of trip signal to contact break 3 cycle 20 40 milliseconds 5 cycle 20 70 milliseconds Re closing Time fr...

Страница 35: ...IB131021EN Page xxix Effective Mar 2018 5 4 CONTROL SCHEMES The basic control scheme for the VCP WL circuit breaker is shown in Figure 5 5 below...

Страница 36: ...f a circuit breaker from its compartment refer to paragraph 4 8 1 in this manual The levering device consists of a drive screw a drive nut two side rails and a sliding cage In the TEST position the nu...

Страница 37: ...into the TEST position It remains engaged in all other circuit breaker positions within the cell Figures 4 2 and 4 4 5 9 MOC AND TOC SWITCH OPERATIONS The MOC mechanism operated control switch operato...

Страница 38: ...cteristics if there are any customer uncertainties in the records of the magnitude duration or other fault details increased inspection frequency should be considered Follow the steps presented in Par...

Страница 39: ...1 4 20 72 5 16 18 144 12 lb ft 3 8 16 300 25 lb ft 1 2 13 540 45 lb ft CAUTION OVER TORQUING CAN CAUSE PERMANENT DAMAGE WHILE UNDER TORQUING WILL NOT PROVIDE THE PROPER CLAMPING FORCE AND MAY EVENTUAL...

Страница 40: ...rmation or Excessive Wear Manual Operation No loose or missing Parts No dust or foreign matter Smooth operation and no excessive wear No excessive deformation or wear Smooth operation Visual and by fe...

Страница 41: ...have sufficient volt ampere capacity It is recommended that the equipment be capable of delivering 25 milliamperes for one minute ONLY AC HIGH POTENTIAL TESTS ARE RECOMMENDED WE DO NOT RECOMMEND DC PO...

Страница 42: ...lead of the test machine to one of the poles of the breaker Connect the remaining poles and breaker frame to ground Start the machine with output potential at zero and increase to the test voltage Ma...

Страница 43: ...E EQUIPMENT WHILE IT IS ENERGIZED NEVER PUT YOUR HANDS NEAR THE MECHANISM WHEN THE CIRCUIT BREAKER IS IN THE CHARGED OR CLOSED POSITION DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENE...

Страница 44: ...witch wiring problem Inspect for loose wires at red Push to Open push button Controller wiring problem Inspect for loose wires into terminals controller Circuit breaker makes no attempt to open with e...

Страница 45: ...ATON Service Center Circuit breaker interlock is preventing close Ensure circuit breaker is fully racked in or out of enclosure Verify that the emergency open handle rod assembly is changing state of...

Страница 46: ...ded destroyed in a similar manner as the switchgear that it is contained within The breaker raw materials in general are made from Copper Steel Aluminum and plastic 6 13 FAILURE REPORTING It is import...