IB131009EN
Instruction Book
Page 1
SECTION 1: INTRODUCTION
The purpose of this book is to provide instructions for
unpacking, storage, installation, operation and mainte-
nance of Types W-VAC, W-VACR, and W-VACW
Vacuum Circuit Breakers. They are a horizontal drawout
type removable interrupting element design, unless
there is an “R” in the designation.The “R” as in W-VACR
indicates a fixed breaker configuration. They were
designed specifically to IEC 56 Standards for reliable
performance. All types can be applied in single tier or
double tier switchgear applications, with the basic
breaker element applicable to retrofitting. Reliable con-
trol and protection are achieved though the use of the
W-VAC family of breakers.
1-1 W-VAC, W-VACR AND W-VACW RATINGS
SATISFACTORY PERFORMANCE OF THESE
BREAKERS IS CONTINGENT UP-ON PROPER
APPLICATION, CORRECT INSTALLATION AND
ADEQUATE MAINTENANCE. THIS INSTRUCTION
BOOK MUST BE CAREFULLY READ AND FOL-
LOWED IN ORDER TO OBTAIN OPTIMUM PERFOR-
MANCE FOR LONG USEFUL LIFE OF THE CIRCUIT
BREAKERS.
TYPES W-VAC, W-VACR AND W-VACW BREAKERS
ARE PROTECTIVE DEVICES, AS SUCH, THEY ARE
MAXIMUM RATED DEVICES. THEREFORE, THEY
SHOULD NOT UNDER ANY CIRCUMSTANCES BE
APPLIED OUTSIDE THEIR NAMEPLATE RATINGS.
Table 1.1 Type W-VAC and W-VACW Vacuum Circuit Breaker Ratings
Circuit
Breaker
Type
Rated
Voltage
at
50-60HZ
Frequency
Rated Short Circuit
Breaking Current
& Short Circuit
Duration
Rated Insulation Level
Short
Circuit
Making
Current
Rated Nominal Current
Lighting
Pulse
Withstand
Voltage
Power
Frequency
Withstand
Voltage
kV
Hz
kA
Sec
kV
kV
kA
(Peak) Amperes
36W-VAC25 3.6 50/60 25 3
40
10
63
630, 1250, 2000,3150
72W-VAC16 7.2 50/60 16 3
60
20
40
630, 800, 1250
72W-VAC20 7.2 50/60 20 3
60
20
50
630, 800, 1250, 1600
72W-VAC25 7.2 50/60 25 3
60
20
63
630, 800, 1250, 1600, 2000,3150
72W-VAC32 7.2 50/60 31.5 3
60
20
79
1250, 2000
72W-VAC40 7.2 50/60 40 3
60
20 100
3150
120W-VAC16 12 50/60 16 3
75
28
40
630, 800, 1250
120W-VAC20 12 50/60 20 3
75
28
50
630, 800, 1250, 1600
120W-VAC25 12 50/60 25 3
75
28
63
630, 800, 1250, 1600, 2000,3150
120W-VAC32 12 50/60 31.5 3
75
28
79
1250, 2000
120W-VAC40 12 50/60 40 3
75
28
100
1250, 2000,3150
120W-VAC50 12 50/60 50 3
75
28
125
3150
150W-VAC16 15 50/60 16 3
95
36
40
630, 800, 1250
150W-VAC20 15 50/60 20 3
95
36
50
630, 800, 1250, 1600
150W-VAC25 15 50/60 25 3
95
36
63
630, 800, 1250, 1600, 2000,3150
150W-VAC32 15 50/60 31.5 3
95
36
79
1250, 2000
150W-VAC40 15 50/60 40 3
95
36
100
3150
150W-VAC50 15 50/60 50 3
95
36
125
3150
175W-VAC16 17.5 50/60
16
3
95
38
40 630, 800, 1250
175W-VAC20 17.5 50/60
20
3
95
38
50 630, 800, 1250, 1600
175W-VAC25 17.5 50/60
25
3
95
38
63 630, 800, 1250, 1600, 2000,3150
175W-VAC32 17.5 50/60 31.5 3
95
38
79 630, 800, 1250, 1600
175W-VAC40 17.5 50/60
40
3
95
38
100
3150
120W-VACW16 12
50/60
16
3
75
42
40 630, 800, 1250
120W-VACW20 12
50/60
20
3
75
42
50 630, 800, 1250, 1600
120W-VACW25 12
50/60
25
3
75
42
63 630, 800, 1250, 1600, 2000
120W-VACW32 12
50/60
31.5
3
75
42
79 1250, 1600, 2000
120W-VACW40 12
50/60
40
3
75
42
100 1250, 2000
150W-VACW16 15
50/60
16
3
95
42
40 630, 800, 1250
150W-VACW20 15
50/60
20
3
95
42
50 630, 800, 1250, 1600
150W-VACW25 15
50/60
25
3
95
42
63 630, 800, 1250, 1600, 2000
150W-VACW32 15
50/60
31.5
3
95
42
79 1250, 2000
150W-VACW40 15
50/60
40
3
95
42
100 1250, 2000
WARNING