Eaton 12-110-1250y Скачать руководство пользователя страница 16

12

Specifications

Eaton 1250W / 1500W / 1800W  Inverter Operation and Installation Guide 

   IM SP180164 / Rev D     www.eaton.com

Table 15.  Mechanical Specifications

Vibration

Per SAE J1455 Rev JAN2011, 

Sec 4.10.4.2, Fig. 6-8, 22 hr/axis

Must operate per specification 

during and after the test.

Table 16.  Environmental Specifications

Temperature cycling

Per SAE J1455, Rev. JUN2006, 

Sec. 4.1, Test 4.1.3.1, Fig. 2B

Must operate per specification 

during and after the test.

Thermal shock

Per SAE J1455, Rev. JUN2006, 

Sec. 4.1, Test 4.1.3.2 Fig. 2C

Must operate per specification 

after the test.

Humidity

Per SAE J1455, Rev. JUN2006, 

Sec. 4.2, Fig. 4B

Must operate per specification 

during and after the test.

Altitude - operating

Per SAE J1455, Rev. JUN2006, 

Sec. 4.9, Table 2

Must operate per specification 

during and after the test.

Altitude – non-operating

Per SAE J1455, Rev. JUN2006, 

Sec. 4.9, Table 2

Must operate per specification 

after the test.

Table 17.  Electromagnetic Specifications

Conducted immunity

Per SAE J1113/3, Severity Level 

L6 (0.5W)

Manual restart required for 

pulses 1, 2b, and 4

Radiated RF immunity - bulk current 

injection

Per SAE J1113/4, Class C, 

Region 2, 80mA

Immunity to radiated RF

Per SAE J1113/25 to 500 MHz
Per SAE J1113/27 500 MHz to 

2 GHz

Load dump

Per SAE J1455, Rev. JUN2006, 

Sec. 4.11.2.2.1

Jump start test

Per SAE J1455, Rev. JUN2006, 

Sec. 4.11.1
24 Vdc Applied to DC Terminals

The inverter system should 

restart without a fault.

Reverse polarity test

Per SAE J1455 Sec. 4.11.1
–24 Vdc Applied to DC Terminals

The inverter shall present no 

safety hazard. Internal fuses 

will open in the inverter system, 

requiring factory service for 

replacement.

Table 18.  Regulatory Requirements

UL458

Comply with the requirements of 

the standard.

ETLus Mark

CSA C22.2, No. 107.1

Comply with the requirements of 

the standard.

cETL Mark

47 CFR FCC Part 15, Subpart B, 

Class B 2016

Comply with the requirements of 

the standard.

FCC Mark

Содержание 12-110-1250y

Страница 1: ...Eaton 1250W 1500W 1800W Inverter Operation and Installation Guide True Sine Wave Inverter...

Страница 2: ...al loss of power additional expenses in the use of existing power facilities or claims against the purchaser or user by its customers resulting from the use of the information recom mendations and des...

Страница 3: ...splay 2 Setting battery type and charge current 3 Fault codes and troubleshooting 6 Troubleshooting 8 Charger and AC transfer 9 Specifications 10 INSTALLATION Installation types and definitions 15 Cho...

Страница 4: ...operly secured and protected from chaffing WARNING Failure to follow these instructions could result in death personal injury or property damage Personal precautions when working with batteries WARNIN...

Страница 5: ...otect itself Some models include a three stage temperature compensated battery charger that maximizes the life of the batteries It can be configured for AGM flooded or Gel lead acid batteries Eaton in...

Страница 6: ...5 Flooded 14 4 14 4 13 5 Gel 14 2 14 2 13 8 AGM 14 3 14 3 13 4 WARNING Fire hazard Programming the incorrect battery type may result in battery damage and a fire risk To change display and read curre...

Страница 7: ...ent value setting is displayed Press and hold the POWER button for 5 seconds 2 Press the SELECT button to switch between the different current ratings in Amps 40 2 5 10 20 3 To choose a new setting st...

Страница 8: ...Press SELECT button to toggle between the two alarm on off settings AL0 this indicates the alarm is OFF AL1 this indicates the alarm is ON 3 To choose a new setting stop at the desired value press an...

Страница 9: ...tes Fixed setting FLo this indicates Flooded battery setting gEL this indicates Gel battery setting Ag this indicates AGM battery setting 3 To choose a new setting stop at the desired value press and...

Страница 10: ...p 1Hz 12 110 1500 xx Warning 100W 1700 E06 Beep 0 33Hz Shutdown 100W 1800 E03 Beep 1Hz 12 110 1250 xx Warning 100W 1450 E06 Beep 0 33Hz Shutdown 100W 1550 E03 Beep 1Hz AC output short circuit protecti...

Страница 11: ...harge current reduced to 0A AC transfer relay 70 C System shutdown no auto reset Max charge current resumes normal level when ChargerTransformer sensor temperature drops below 90 C Table 7 Location Wa...

Страница 12: ...he unit in a location with lower ambient temperature or improve air flow around the unit E05 DC Input Under Voltage Warning Unit is detecting an input DC voltage which is too low and it is warning the...

Страница 13: ...ypass mode is available To reset error code remove AC Input and turn unit off and on Dead battery charging Battery voltage must meet the following conditions or Error code E11 will display Initial bat...

Страница 14: ...tput power 5 seconds 2000W Surge output power 3600W 300ms Operating temperature range 0 C to 50 C Storage temperature range 40 C to 85 C THD Resistive load 5 max 2 5 typical Output power rated at 25 C...

Страница 15: ...sorption voltage Float voltage 10V 5V Charge current setting Float current Maximum charge current setting 15 min 8 hrs max 5 hrs max NOTE If an external DC load is connected to the battery and it drai...

Страница 16: ...c 4 9 Table 2 Must operate per specification after the test Table 17 Electromagnetic Specifications Conducted immunity Per SAE J1113 3 Severity Level L6 0 5W Manual restart required for pulses 1 2b an...

Страница 17: ...nnectors DC input M8 x 1 25 Stud Chassis ground M6 x 1 00 Stud AC output AC NEMA outlet with knockouts for AC Input and optional AC output Built in AC NEMA outlet is GFCI protected The built in AC GFC...

Страница 18: ...take note of any precautions concerning the installation Prior to engaging in any service all AC and DC power sources need to be disabled Follow proper cable routing and strain relief guidelines Insta...

Страница 19: ...r an AC generator In the case of multiple sources an automatic or manual AC source selector switch can be used The AC source going into the inverter must have a neutral conductor bonded to ground i e...

Страница 20: ...current protec tion and the disconnect switch for the AC power supply AC load panels can utilize an AC output circuit breaker and breakers for each subsequent load circuit AC cabling AC cabling includ...

Страница 21: ...of fire Installing the inverter in a compact compartment will be detrimental and may result in overheating IMPORTANT Location s must conform to these required parameters Dry Do not allow water or oth...

Страница 22: ...asten the inverter to the mounting surface using pan head wood or sheet metal screws if mounting to a wall or bulk head Do not block vents on bottom of inverter Figure 6 Approved mounting orientation...

Страница 23: ...Bxy 2 150 12 20 14 1 2 3 12 110 1500y 2 175 14 20 14 1 3 12 110 1500 Bxy 2 175 12 20 14 1 2 3 12 110 1800y 1 200 12 30 12 1 3 12 110 1800 Bxy 1 200 10 30 12 1 2 3 1 AC output fuse is not required as a...

Страница 24: ...utput All AC wiring source to inverter inverter to AC panels AC panels to circuit breakers and GFCIs must be rated to at least the current rating of the fuses and or circuit breakers and also must be...

Страница 25: ...ld be in accordance with wiring codes DO NOT connect any AC input source to the output terminals of the inverter IMPORTANT The Eaton Inverter will not operate if connected to high power consumption lo...

Страница 26: ...g wires improperly i e the neutral wire into the line termination will cause the inverter to break down and possibly cause permanent damage 4 It is very important to not confuse the connections i e pu...

Страница 27: ...ion or fire Proper ventilation is crucial To make connections to DC terminals 1 Ensure the inverter is OFF and no connections are being made to DC or AC circuits 2 Remove nuts and washers from the DC...

Страница 28: ...gative post of the battery to the negative DC terminal of the inverter 2 Install flat washer then the lock washer and nut back on to the inverter Tighten to 12 2 13 6 Nm 9 10 ft lbs Grounding The grou...

Страница 29: ...on for the panel should be dry out of direct sunlight free of corrosive fumes and suitable for mounting an electronic device 2 Draw the area to cut away with a pencil on the wall 3 Cut away the area a...

Страница 30: ...verify it functions properly Hint H If the appliance functions as expected the installation is a success If it was a hardwire installation continue reading Testing in UTILITY GRID MODE 1 Using the sam...

Страница 31: ...ton Boulevard Cleveland OH 44122 United States Eaton com 2019 Eaton All Rights Reserved Publication No IM SP180164 August 2017 Eaton is a registered trademark All trademarks are property of their resp...

Отзывы: