16 Technical data
ESR5-NO-41-24VAC-DC
12/19 MN049009EN
www.eaton.com
25
Conformance / Approvals
Conformance
CE-compliant
Approvals
Safety data
Stop category according to IEC 60204
0
Safety parameters for IEC 61508 - High demand
SIL
1 (up to SIL 3 depending on the application)
PFH
d
4.05 x 10
-10
per hour
Demand rate
< 12 months
Proof test interval
240 months
Duration of use
240 months
The specifications apply assuming the following calculation basis:
B
10d
230000 (at 3
A
AC-15)
Cycles
8760 per year
Safety parameters for IEC 61508 - Low demand
SIL
1 (up to SIL 3 depending on the application)
PFD
avg
1.49 x 10
-4
Proof test interval
78 months
Duration of use
240 months
Safety characteristic data according to EN ISO 13849
Category
1 (up to Cat. 4 depending on the application)
Performance Level
c (up to PL e depending on the application)
Duration of use
240 monts
For applications in PL e, the required demand rate for the safety function is once per month.
Calculation basis:
B
10d
230000 (at 3
A
AC-15)
Cycles
8760 per year
Safety parameters for EN 62061
SILCL
1 (up to SILCL 3 depending on the application)
ID 0600000000
Product Safety
Functional
Safety