Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
164201687—Rev 06
www.eaton.com/powerquality
4.3.4
Internal Battery String Connection
All battery cabinets arrive at the site with each battery connection string electrically disconnected. To
interconnect the battery tray strings:
1.
Verify that all battery breakers are in the OFF position.
2.
FOR 1085 ONLY:
Connect the string of battery trays by mating the loose red connector from each tray to
the fixed black connector mounted on the front edge of the tray above. Connect the top and bottom tray
connectors to the mating cabinet connectors to complete the battery string connections (see Figure 4-14).
3.
FOR 1085HR ONLY:
Connect the string of battery trays by mating the loose black connector with the blue
locking mechanism from each tray to the fixed black connector mounted on the front edge of the tray
below. Connect the top and bottom tray connectors to the mating cabinet connectors to complete the
battery string connections (see Figure 4-15).
4.
Repeat Step 2 or Step 3 for each battery cabinet, and then proceed to Step 5.
5.
Replace the doors that were removed in paragraph 4.2.
6.
Secure all battery cabinets by closing and latching the doors.
7.
Return to the appropriate Power Xpert 9395 UPS Installation and Operation manual, as referenced in
paragraph 1.7 to complete the UPS wiring.
Figure 4-14. 1085 Battery String Connection
Battery Breaker
Fixed Right Battery
Power Connector
(black)
String Connectors
(red)