105U-2 wireless extension I/O  installation guide 

EATON_105U-2 Install Guide 

  

Instruction Leaflet 

IL032003EN

Effective December 2015
Version 2.0

© 2014 Eaton

All Rights Reserved

Printed in USA

Publication No. IL032003EN 

December 2015

Installation

Choose a power supply option:

• 

12–24 Vac, 1.5A CSA certified 

Class 2

• 

15–30 Vdc, 1.5A CSA certified 

Class 2

• 

11–15 Vdc, 1.5A

• 

Solar panel with battery

After choosing a power supply 

option, wire the module as 

shown in Figure 2.

otee:

N

All I/O must be SELV.

When the wiring is completed, 

connect the module to a 

computer (PC) and configure 

it using the configuration 

software. For details, refer to 

the user manual. 

Before operating the module, 

read the sections on operation 

and configuration in the user 

manual to take advantage of all 

product features.

WARNING 

EXPLOSION HAZARD

Do not disconnect while circuit 
is live unless area is known to be 
non-hazardous.

Figure 2. Wiring Diagram

11–15 Vdc Supply or 

Optional 12V Backup Battery

12 Ah for AC/DC

100 Ah for Solar

-

 

+AI 2

-

 

+AI 1

+24V

 

DI  3

 

SOL

 

DI  2

 

DI  1

GND

COM

 

DI  4

SUP2

SUP1

 

BA

T+

AI 3 +

AI 4 +

AI 6 +

AI 5 +

 GND

 +24V

 DOT

  

COM

 

 

 

 

OUTPUT

 

1

2

 

3

 

4

INPUTS

    

 COM

ELPRO 

105U-2 Multi I/O

2A

+ -

-

-

+

+ -

+

External-Powered

Analog Transducer

Loop-

Powered

Analog

Transducer

Digital Input

Voltage-Free

Contact or

Transistor

Device

To Earth Stake

DC Supply

15–30 Vdc

Min. 17 Vdc 

for Battery

Charging

 

SOL

GND

SUP2

SUP1

AC Supply

12–24 Vac

Min. 15 Vac

for Battery

Charging

Do not earth

SUP1 or SUP2

connection.

12V Solar 

Panel Supply;

Max. 20 Vdc

Max. 30 W

Panel

Digital Output

Max. 30 Vdc, 500 mA

DC Relay Supply

DC Load

Отзывы: