11. Operation and Operating Mode
Operational process of removing single UPS:
1) If want to remove UPS which is running normally, please press the close key of the
removing one continuously for 2 times
2) Shut off the UPSs own line switch, line output switch outside and battery switch, when
this UPS need to remove out.
3) Turn off other UPS which are running, take apart the maintain cover of every UPS and
turn all UPS maintain switch from “UPS” to “BPS” until all running UPS turn to BPS
mode. Then turn off every UPS own input switch.
4) After removing single UPS, if leaving UPS system is changed to single running, please
connect the short line between JP1 and JP2 of this UPS output port.
5) Take apart another UPS parallel cover and combine line connected with the UPS which
need to remove until all UPS panels become black, then lock up the cover of parallel
ports again.
6) Take apart UPS parallel cover and combine line when the UPS have to remove, then
lock up the cover of parallel ports again.
7) Shut input line switch of leaving UPS system, turn maintain switch from “BPS” to “UPS”
until all UPS turn to BPS mode and lock up the maintain cover, then turn on the
machine and turn all UPS to line inverter mode running.
Combine machine warning:
1) When UPS combine system work at inverter mode, make sure that all UPS maintain
switches at the same place, that is to say, be at the position of “UPS”, or be at the
position of “BPS”.
2) When turning on the UPS combine system before enter into inverter mode, UPS output
switch must at “OFF” model.
3) When UPS combine system work at inverter model, please do not operate any UPS
maintain switch.