CLINK II SCU MANAGER
functional description scu
version 5.0
46
The two registers together represent the status for each protection, see table 32.
Trip and warning signals
The lamp on the motor starter tray is connected to a digital output (DO_3, 4, 5, 6 or 7) of the SCU. See table
32 for a description of generated trip and warning signals (for information regarding the digital outputs of the
SCU see 5.4.1 on page 26).
Trip current
The moment a protection function is activated, the motor current is measured and stored. This value is stored
until the protection is confirmed by means of an acknowledge command. See table 33.
Warning Status
Reserved
Motor Overload
Phase Unbalance
Earth Leakage
Process Overload
Process Underload
External Protection
Over Voltage Protection
Under Voltage Protection
Under Current Protection
Actual
Warning Acknowledge Status
See description Warning Sta-
tus (above)
Actual
Table 32: Meaning of protection status registers and trip/warning signals
Status (Trip or
Warning)
Acknowledge Status
(Trip or Warning)
Status of the protection
Trip/warning signal
0
0
no fault is present
low
1
0
protection activated, mes-
sage not yet confirmed by an
acknowledge/reset command
flashing
0
1
not applicable
not applicable
1
1
message acknowledged, but
fault is still present
high
Table 33: Read-out of Trip Current by DeviceNet
Name
Range
Unit
Parameter
type
Trip Current L1
0-10.00
I/In
Actual
Trip Current L2
0-10.00
I/In
Actual
Trip Current L3
0-10.00
I/In
Actual
Trip Current L1
0-1200.000
A
Actual
Table 31: Read-out of protection status registers
Name
Description
Parameter
type