Document Reference No.: ES_000005
USB2-F-7x01 Full-Speed USB to 1-Port CANbus Adapter User Guide
Version 1.3
Clearance No.: ES#02
©2008 - 2010 EasySYNC Ltd.
20
4.1.5
Enable Time Stamp (Z)
Summary
Sets or clears time stamp on received frames. This value is persistent in EEPROM across reset or
restart. Four (4) bytes are added to the end of a received frame. This value is a rolling 16-bit
counter that increments once every millisecond and rolls over at 60,000mS (1 minute). Valid hex
values are 0x0000 through 0xEA5F.
NOTE:
The CAN channel will revert to its prior state after execution. For example if the channel
is Open when this command is executed, the channel will update the setting and return to the
Open state.
Definition
Zn<CR>
Parameters
n =
0 = disable time stamp feature
1 = enable time stamp feature
Remarks
Default is OFF (disable time stamp)
Only use when required to change functionality.
Example:
Z1<CR>
Enable time stamp.
Return Codes
<CR> = OK
<BELL> = ERROR