background image

           

EasyIO FC20 User Reference v1.3

 

 
 
 

 

 

 

 

 

 

EasyIO FC 20 DDC User Reference 

V1.3 

 

 

Содержание FC 20

Страница 1: ...EasyIO FC20 User Reference v1 3 EasyIO FC 20 DDC User Reference V1 3...

Страница 2: ...erence v1 3 Document Change Log 1st April 2013 Document created 13th July 2013 Software configurations added 27th Sept 2014 FC now support pulse input 6th June 2015 Serial address image Serial Port se...

Страница 3: ...EasyIO FC20 User Reference v1 3 Disclaimer EasyIO FC 20 is a product by EasyIO Holdings Pte Ltd Sedona Framework is a trademark of Tridium Inc...

Страница 4: ...ns 6 Power supply Connection 6 RS485 Connection 7 Jumpers Setting 9 Digital Output Wiring Connection 11 Universal Input Connection 12 Analog Output Connection 13 Buttons and Indications 14 Software Co...

Страница 5: ...as Roof Top Units Fan Coils AHU s package units etc EasyIO FC20 controller comes with built in bootloader program Built in bootloader program will enable user to upgrade firmware without sending back...

Страница 6: ...specification for the working range In order to avoid damage on the controller input output devices and RS485 connection use individual power supply for each controller If a single power supply is use...

Страница 7: ...he controller should be wired in daisy chain network topology as shown as image below If wire branch can be avoided keep it as short as possible and never connect more than one device to the wire bran...

Страница 8: ...ACnet MSTP Modbus Baud Rate 19 2K Parity even Data Bit 8 Not editable Stop Bit 1 BACnet Baud Rate 19 2K Port 1 is used to perform Firmware flashing FwTool exe Virtual Device for program downloads FcVi...

Страница 9: ...rotocol toggle the 1 of the dip switch to ON The remaining DIP switch 2 8 are for BACnet MSTP ID or Modbus Serial ID address 0 is not available it will be set to 1 depending on DIP switch 1 selection...

Страница 10: ...tch number Functions Remarks 1 Protocol Setting On Bacnet MSTP Off Modus RTU 2 Serial Address Address 64 MSB 3 Serial Address Address 32 4 Serial Address Address 16 5 Serial Address Address 8 6 Serial...

Страница 11: ...ing Connection EasyIO FC 20 has four general purpose isolated digital output connections relay output Each relay output able to drive up to 1A 30VDC 48VAC load It does not output voltage or current It...

Страница 12: ...s 8 customizable temperature lookup tables for resistance to temperature translation The commonly used Thermistor like 10K 10K with Shunt 1K Balco and 1K Platinum are all supported b Voltage Two selec...

Страница 13: ...Output can be configured to drive voltage or current output via hardware jumper setting and internal register settings The working range for voltage is 0 10V and for current either 0 20mA or 4 20mA F...

Страница 14: ...ED to indicate its current state Button and LED indications LED Conditions Description 1 PWR PWR is used to indicate the presence of 24VAC power source and internal power 2 ERR ERR is to indicate when...

Страница 15: ...les and kits files Step 1 Get the required files from EasyIO technical support at support easyio com The files are the Sedona kits and platform manifest for the EasyIO FC series Step 2 Close the workb...

Страница 16: ...EasyIO FC20 User Reference v1 3 Step 5 For Niagara Ax 3 6 xx user Drag and drop it in to the sedona root folder Hit Yes on the pop up to merge the files...

Страница 17: ...6 For Niagara Ax 3 7 xx user Drag and drop it in to the sedona root folder Hit Yes on the pop up to merge the files Step 7 Re open workbench and connect to EasyIO FC 20 controller Refer to EasyIO FC 2...

Страница 18: ...EasyIO FC20 User Reference v1 3 Technical Support For technical issue please contact Email support easyio com...

Отзывы: