EasyIO EIO-75 Series Скачать руководство пользователя страница 2

EasyIO

EIO-75 032719

EasyIO Holdings
www.easyio.com

Technical Data

Power Supply

Power Supply

24VAC/DC -10%/+15%, max. 80mA

Display

Touchscreen

3.5" Backlit Touchscreen, 320 x 480 pixels, 255K colours

Network Signal Outputs

Relay Output

1 x 5A(res.) 24Vac Relay, SPST

Network Signal Inputs

Built-In Sensor

0..50°C (32..122°F) ±0.5°C/±0.9°F @ 25°C (77°F)

External Sensor Inputs

2 x External NTC10K3 Sensors

Digital Input

1 x Digital Input, Volt-Free Contact, Impedance <1KOhm

Optional Sensing 

Humidity (RH Models)

Characteristics

Range

0..100%rH

Accuracy

±2% rH (within 20..80% rh)

Communication

Modbus (-MOD models)

Protocol

Modbus RTU

Interface

RS485; maximum 63 devices per segment

Addressing

1 to 247 via Touchscreen

Communication

9k6/19k2/38k4/57k6/76k8 Baud; Parity None/Even/Odd, 1 or 
2 Stop Bits (adjustable through Touchscreen)

BACnet (-BAC models)

Protocol

BACnet MS/TP

Interface

RS485; maximum 63 devices segment

MAC Addressing

0 to 127 via Touchscreen

Device ID

Default  MAC Address, User Configured

Communication

9k6/19k2/38k4/57k6/76k8 Baud; Parity None/Even/Odd, 1 or 
2 Stop Bits

Connections

Terminal Connections (Relay 
& Power Supply)

Solid and Stranded Cable
Maximum Size: Solid; 0.05-2.5mm

2

, Stranded: 0.05-1.50mm

/ 14 to 30 AWG (UL)
Rising Clamp: Size 2.5 x 2.2mm

Terminal Connections (Low 
Voltage Terminals)

Solid and Stranded Cable; 90° Angle for Wiring
Maximum Size: 0.05 to 1.5mm

2

 (EN ISO) / 14 to 30 AWG (UL)

Rising Clamp: Size 2.5 x 1.9mm

Environmental Conditions

Operating

Temperature

0°C...+50°C (32..122°F)

Humidity

0...95%rh (non-cond.)

Storage

Temperature

-30°C...+70°C (-22..158°F)

Humidity

0...95%rh (non-cond.)

Standards

CE Conformity

CE Directive 2004/108/EC (EMC), 2006/95/EC (LVD) 
EN61000-6-3: 2001 (Generic Emission) 
EN61000-6-1: 2001 (Generic Immunity)

UL Listing

Pending

Degree of Protection

IP20

Housing

Housing Material

Polycarbonate Plastics, Self Extinguishing (V1 rated)

Mounting

Wall or Junction Box Mounting, Silver and Black

Dimensions

W88mm (3.46") x H112mm (4.41") x D43mm (1.68")
Flush: W88mm (3.46") x H112mm (4.41") x D14.5mm (0.57")

Weight

220g

Содержание EIO-75 Series

Страница 1: ...rides Measurement EIO 75 Model Type EIO 75 BAC BACnet MSTP Touchscreen LCD Room Interface 24Vac dc Power Supply 24V rated relay degF default EIO 75 BAC CO2 BACnet MSTP Touchscreen LCD Room Interface C...

Страница 2: ...ssing 0 to 127 via Touchscreen Device ID Default 651000 MAC Address User Configured Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits Connections Terminal Connections Re...

Страница 3: ...YOUT 24VAC 30VDC 5A Relay Contact RELAYCOM 24VAC 30VDC 5A Relay Contact 24V 24Vac dc Supply 0V 0V Supply Rin1 Remote NTC10 Temperature Sensor Input 1 Rin2 Remote NTC10 Temperature Sensor Input 2 Din V...

Страница 4: ...BLUE DISPLAY SRI 75 WITH FAN SPEED DEG C 21 5 C Room 20 1 C A CONTROL MODE AUTO HEATING COOLING FAN VENTILATION FAN F C F C F C The EIO 75 room interface home screen has four touch sensitive areas tha...

Страница 5: ...ration pages By setting the description to Disabled the sensor reading is not displayed on the screen Target Units Note If all sensor displays are Disabled the ACTION CIRCLE displays the last drawn im...

Страница 6: ...5 has fan icon and line bar to indicate the fan speed It is also possible to use the line bar only to indicate other signals by disabling the fan icon The fan and line bar display is configured by a p...

Страница 7: ...ents M and Auto A When auto is selected the display returns to show the speed set over the network 3 STEP AUTO fan speed rotates between OFF M 2 segments M 4 segments M 6 seg ments M and Auto A When a...

Страница 8: ...mode OFF Mode Icon OFF MODE CANCEL ICON Room 73 1 F 46 0 F OFF MODE ICON TO ACTIVATE OFF MODE Room 73 1 F 71 5 F OFF MODE ACTIVE OFF MODE INACTIVE TARGET VALUE DIMMED WHEN OFF MODE ACTIVE F C F C The...

Страница 9: ...frosting 71 5 F Room 20 1 F Target A FROST ICON F C Cleaning Mode After entering FURTHER INFORMATION screen by selecting the CLEANING icon it is possible to activate the cleaning mode The EIO 75 will...

Страница 10: ...the Programmed Times NO INPUT All Buttons Locked Alarm Display When entering FURTHER INFORMATION AND SETTINGS screen and an alarm is active select the alarm icon for more information FURTHER SETTINGS...

Страница 11: ...e humidity sensor for room space humidity measurement The humidity reading is displayed inside the SMALL ACTION CIRCLE display as default enabled option to disable through configuration pages and avai...

Страница 12: ...n Range Sensor 1 Source Sensor 1 Source When set to Hardware reads RI1 status monitoring over the network is always active 0 Hardware RI1 1 Network Default Sensor 2 Source Sensor 2 Source When set to...

Страница 13: ...light Brightness 0 20 default 5 Enable Lights Icon Enable Lights Icon Network Variable 0 Disabled default 1 Enabled Enable AC Icon Enable AC Icon Network Variable 0 Disabled default 1 Enabled Enable L...

Страница 14: ...sabled removes Sensor1 Text and Measurement from Display Sensor 3 Text Description for the Sensor3 Built In Sensor Network Default 1 Room Note Disabled removes Sensor1 Text and Measurement from Displa...

Страница 15: ...101 Relay Output Status 0 1 Off On 102 Time Clock Status not available 0 1 Off On 103 Light Switch Status 0 1 Off On 104 A C Switch Status 0 1 Off On 105 OFF Mode Status 0 1 Off On 106 Screen Lock Sta...

Страница 16: ...8 0 122 0 C F Default 0 0 109 Fan Manual Control Mode Unsigned 16 0 4 0 Disabled default 1 1 Step 2 2 Step 3 3 Step 4 6 Step 5 1 Step Auto 6 2 Step Auto 7 3 Step Auto 8 6 Step Auto 9 Advanced 110 Fan...

Страница 17: ...None default 1 Override On 2 Override Off 132 Override Lock Mode Note The parameter returns automatically to 0 allowing local control Unsigned 16 0 2 0 None default 1 Lock Screen 2 Cancel Lock Mode 1...

Страница 18: ...end Switching Time 1 Unsigned 16 0 2400 0 2400 Default 0600 211 Tuesday Weekend Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 212 Tuesday Weekend Switching Time 3 Unsigned 16 0 2400 0 2400 D...

Страница 19: ...t 1700 255 Saturday Switching Time 1 Target Unsigned 16 0 1 0 1 Default 0 256 Saturday Switching Time 2 Target Unsigned 16 0 1 0 1 Default 0 257 Saturday Switching Time 3 Target Unsigned 16 0 1 0 1 De...

Страница 20: ...or 1 RI1 AI 4 Sensor 2 RI2 Analogue Value 5 AV 0 Nominal Setpoint AV 1 Sensor 1 Temp AV 2 Sensor 2 Temp AV 3 Sensor 3 Temp AV 4 Brightness Binary Input 4 BI 0 Digital Input DI1 BI 1 Boost Party Mode S...

Страница 21: ...Name ID Attributes Range Default Object Identifier R W 20 Object Name R W 32 Characters Max Concatenation of product type and MAC address i e SRI001 Object Type R Device System Status R STATUS_OPERAT...

Страница 22: ...1 On Off Boost workable only 2 Temp settings only available 3 All buttons disabled 40118 Show Unit Swap Icon Unsigned 0 Disabled 1 Enabled default 40119 Built In Sensor Calibration REAL 10 0 10 0 C F...

Страница 23: ...Default 0 Disabled Note Disabled removes the text and measurement from the display Unsigned 40141 Sensor 3 Text Built in Network Sensor Default 1 Room Note Disabled removes the text and measurement fr...

Отзывы: