background image

 

25

 
 
 
 
 
 
 
 
 
 

Programming Instructions for 

“EQUATOR” 

R24V Remote Control for 

models 

HI-30-40N2BR, HI-30-40P2BR 
HI-30-40N2SR, HI-30-40N2SR 

 

ERW-R (remote control receiver, factory installed in heater) 
 
ERW-S (hand held remote control sender) 
 
For individual control of multiple heaters (i.e. up to 4 heaters individually) OR groups of 
many heaters – with one remote sender. 
 
Ensure that the dial on the back of the hand held sender is set to “G” 
Ensure that the sliding switch on the front of the hand held sender labeled

 

1,11,111,1V is set to 1 

1. Remove the access panel on the heater to expose the ERW-R1 that     has been factory 
installed. 
 
2. Turn the “manual-remote” switch on the exterior of the heater to “Remote”. 
 
3. Identify the yellow button on the factory installed ERW-R which is     directly below the 
green LED. 
 
4. Press and continue to hold in the yellow program button. It will flash once. 
 
5. While depressing the yellow program button on the ERW-R, depress and hold the “grey 
off button” labeled number 1, on the ERW-S hand held sender. The LED on the ERW-R will 
flash again. 
 
6. Release the yellow program button on the ERW-R and the grey button on the sender. 
 
7. Press and hold the green button (number 1) for 3 seconds and the heater will ignite. 
 
8. Press the grey button (number 1) and the heater will turn off. 
Move to heater number 2 and repeat the above steps but use number 2 on the hand held 
ERW-S 
Continue to heaters 3 and 4 and repeat above using numbers 3 and 4 
Several heaters can be turned on and off simultaneously by programming to “G” for group 
on the ERW-S rather than using numbers 1 – 4. 
 

Additional hand held senders can be programmed for the same heaters using the above 

method.

 

 

 
 
 
 

Содержание HI-30-40P2

Страница 1: ...1 This heater may be installed up to a 35 degree angle Installation above a 35 degree angle will voice warranty on the heater...

Страница 2: ...W added to the model no indicates wireless model The letter B added to the model no indicates black model The letter S added to the model no indicates stainless steel The letter R added to the model n...

Страница 3: ...esult in an improper installation which could result in faulty operation of The Equator causing property damage serious injury or death If you do not fully understand these instructions contact your s...

Страница 4: ...hat can be harmful Infrared energy travels by line of sight so the designer must be aware that doors panels or windows may obstruct the infrared energy from reaching the desired location Overlapping i...

Страница 5: ...building recesses or inside a soffit Fire sprinkler heads must be located an appropriate distance from The Equator or a sprinkler head with a high enough temperature rating that normal operation of Th...

Страница 6: ...ty or mechanical ventilation of the building 2 In conjunction with building ventilation system adequate fresh air into the building must be provided through fresh air inlets and or building openings 3...

Страница 7: ...s 3 All gas pipe connections to the heater s must be sealed with a gas pipe compound resistant to liquefied petroleum gases 4 Installation of a drip leg in the gas supply line going to each heater is...

Страница 8: ...gle mounted up to 35 degrees maximum When mounting above 20 degrees to a maximum of 35 degrees wind protection must be provided Note clearances to combustibles chart on page 4 Windy conditions can be...

Страница 9: ...aters can be placed below a supporting structure with angle mounting The Equator can be installed with up to 35 degree angle to face inward toward each other or outward away from each other Heater Ope...

Страница 10: ...an and reinstall 5 Check to insure heater is securely mounted and the clearance from combustible material is maintained 6 If additional service to The Equator is required contact your local representa...

Страница 11: ...Plate and Grill Remove Pilot Screen 2 srews COM COM HI M HIGH LOW OFF ON BLUE RED WHITE 36G54 TYP 214 OFF ON RED WHITE 36G22 C Disconnect Wiring From Valve Two Stage Single Stage FS TR GND P MV TH PV...

Страница 12: ...12 Removal of the Burner con t E Turn Burner Face Down And Remove 8 Screws And Remove Back Panel F Remove the screws 4 And Lift Burner From Enclosure...

Страница 13: ...high resistance check wire connectors c Check spark gap Should be 7 64 109 between electrode tip ground stop If gap is too large spark will occur at wrong location If gap is too small spark may not be...

Страница 14: ...ressure improperly sized gas line Variable voltage Wind exceeding 15 mph 24kmh Tip angle exceeding 30 degrees Debris inside burner Erratic winds Deterioration of the Front Grill The Equator must be in...

Страница 15: ...OTHER COSTS Such cost may include but not limited to a Labour charges for service removal or reinstallation of the heater or part thereof b Shipping and delivery charges for forwarding the new EQUATO...

Страница 16: ...16 HI ER 100...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...20...

Страница 21: ...21...

Страница 22: ...22...

Страница 23: ...23...

Страница 24: ...24...

Страница 25: ...y installed ERW R which is directly below the green LED 4 Press and continue to hold in the yellow program button It will flash once 5 While depressing the yellow program button on the ERW R depress a...

Страница 26: ...and the grey off button to go to the low input 30 000 BTU Buttons 2 3 4 will be inoperative They can be used to control additional heaters in future The G button will control a group of heaters Always...

Страница 27: ...tch to Manual In this position the hand held remote will not operate Multiple 2 8 2 Inputs EQUATOR heaters with On Off High Low hand held remote control Your remote control ERW S ERW R has been pre pr...

Страница 28: ...netrable tolocal wildlife debris and buildupsofdus tand dirt The following visual inspectionsshould be made periodicallyto ensure your safetyand continuedenjoymentofyou r appliance Duringthe winter mo...

Отзывы: