Three phase din rial meter

SDM530D

user manual

current protection device is near the meter so that it is more convenience for the operator.
The over current protection device should comply with the specifications of the buildings
electrical design and all local regulations.

This meter can be installed indoor directly, or in a meter box which is waterproof outdoor,
subject to local codes and regulations.

To prevent tampering, secure the meter with a padlock or a similar device.

The meter has to be installed against a wall which is fire resistant.

The meter has to be installed in a good ventilated and dry place.

The meter has to be installed in a protection box when placed in dangerous or dusty
environment.

The meter can be installed and used after being tested and sealed with a letter press printing.

The meter can be installed on a 35mm DIN rail or direct on a meter board with screws.

The meter should be installed in an available height so that it is easy to read.

When the meter is installed in an area with frequent surges due to e.q. thunderstorms,
welding machines, inverters etc, protect the meter with Surge Protection Devices

After finishing installation, the meter must be sealed to prevent tampering.

Connection of the wires should be done in accordance with the underneath connection
diagram.

Direct connect type

CT connect type

1.8 Operating
Consumption indication
On the SDM530D’S front panel, there are four LED, in which three LED are for three phase voltage and
another one for impulse. The constant of the impulse is shown on the nameplate of the meter.

Reading the meter
The SDM530D energy meter is equipped with 6+1 or 5+2 LCD display, which is used as recording
consumption and can’t be reset to zero. The number system is based on units of 10. And unit is kWh.
On the front panel, there are two rubber buttons, which are used to scroll down the meter display
information.

Pulse output
SDM530D series DIN rail energy meter is equipped with a pulse output which is fully separated from
the inside circuit. That generates pulses in proportion to the measured energy. They are test pulse
output (pins 8 & 9). Usually, the test pulse output is used as testing accuracy or reading purpose in
close quarters.
The test pulse output is a polarity dependant, passive transistor output requiring an external voltage
source for correct operation. For this external voltage source, the voltage (Ui) should be 5-27V DC,

                    

                                             

                          

Содержание SDM530D

Страница 1: ...WIRE ENERGY METER WITH S0 PULSE OUTPUT SEVEN MODULE User manual 1 1 Safety instruction 1 2 Foreword 1 3 Performance criteria 1 4 Specifications 1 5 Basic errors 1 6 Dimension material 1 7 Installation 1 8 Operating 1 9 CT ratio setting SDM530D CT only 1 10 Technical support ...

Страница 2: ...r the application specified in the catalogue and the user manual and only be connected with devices and components recommended and approved by Eastron Electronic Proper handling The prerequisites for perfect reliable operation of the product are proper transport proper storage installation and assembly as well as proper operation and maintenance When operating electrical equipment certain parts of...

Страница 3: ...the most advanced type electronic kWh meter available at the market With the Eastron product range we have introduced a large scale of energy meters on the market suitable for 110V AC to 400V AC 50 or 60Hz The Eastron SDM530D has two versions direct connection version and CT connection version The direct connection version SDM530D can be connected to load up to 100A While the SDM530D CT version sh...

Страница 4: ...withstand 30Imax for 0 01s Operational frequency range 50Hz 10 Internal power consumption 2W 10VA per phase Test output flash rate PULSE LED Directly connect CT connect 400imp kWh 1600imp kWh Test pulse output rate pins 8 9 Directly connect CT connect 400imp kWh 1600imp kWh Power missing indicator Phase A B C LED the LED will burning if the phase power is missing Consumption indicator PULSE SO LED...

Страница 5: ... more convenience for the operator The switch or circuit breaker should comply with the specifications of the buildings electrical design and all local regulations An external fuse or thermal cut off which will be used as a over current protection device for the meter must be installed on the supply side wire and it is recommended that the over CAUTION Turn off all the power before working on it A...

Страница 6: ...ter with Surge Protection Devices After finishing installation the meter must be sealed to prevent tampering Connection of the wires should be done in accordance with the underneath connection diagram Direct connect type CT connect type 1 8 Operating Consumption indication On the SDM530D S front panel there are four LED in which three LED are for three phase voltage and another one for impulse The...

Страница 7: ...hase power Does not shine Bright Bright B phase power Bright Does not shine Bright C phase power Bright Bright Does not shine Only AB power Does not shine Does not shine Bright Only AC power Does not shine Bright Does not shine ABC together on the power Does not shine Does not shine Does not shine LCD display When the meter is power on the meter will display Full screen 2S Software version 7P 1 0 ...

Страница 8: ...l the LCD backlit mode and choose CT ratio Backlit Setting SDM530D is equipped with highlight blue color backlit which provide a clear view of reading when the meter is installed in a dark condition There are three modes optional ONLED the backlit always on OFFLED the backlit always off OPEN30S the backlit will turn on after each click of button ...

Страница 9: ...CT only The SDM530D CT measure the secondary energy consumption via external current transformer If the user wants to read the primary energy reading he can program the CT ratio to the meter by the front buttons The meter has 27 pre set and common CT ratios optional to the user ...

Страница 10: ......

Отзывы: