16
EASTRON SDM320Y User Manual
06-2018 V1.0
2018 EASTRON Electronic. All Rights Reserved. www.eastron.com.cn
40021
Modbus address
00
14
Set range
:
1~247
,
Default 1
Data length : 4 byte
Data type : Float
Modb
us
addre
ss
40023
Pulse 1
pulse constant
00
16
Set range 0~3
,
Default 0
0 Stands for 1000 imp/kWh
1 Stands for 100 imp/kWh
2 Stands for 10 imp/kWh
3 Stands for 1 imp/kWh
Note: if the pulse constant of pulse 1=1000imp/kWh
,
it is automatically fixed to 35ms , cannot be set.
Data length : 4 byte
Data type : Float
Pulse
1
pulse
consta
nt
40025
Password
00
18
Set range 0000 ~ 9999
,
Default1000
Data length : 4 byte
Data type : Float
Passw
ord
40029
Baud rate
00
1C
Settable value
:
0, 1, 2, 5
,
Default2.
0 Stands for 2400 bps
1 Stands for 4800 bps
2 Stands for 9600 bps
5 Stands for 1200 bps
Data length : 4 byte
Data type : Float
Baud
rate
40059
Automatic
scrolling display
00
3A
Set range 0~30
,
unit
:
second
,
Default0.
0 Stands for no scrolling display
。
Data length : 4 byte
Data type : Float
Auto
matic
scrolli
ng
displa
y
40061
Backlight time
00
3C
Set range 0 ~ 121
,
unit
:
minute
,
Default60.
0 Stands for Backlight normally on
;
121 Stands for
Backlight normally off.
Data length : 4 byte
Data type : Float
Backli
ght
time
41281
Current recharge
information
05
00
1
)
Recharge amount
,
length
:
4byte
,
data format
:
Float
2
)
The time recharge occurs
,
length
:
6byte
,
data
format
:
BCD
,
Year-Month-Date-Hour-Minute-Second
For example
(
Hex
):
42 C8 00 00
18 07 16 13 12 20,
42
C8 00 00
Stands for recharge amount
(
100
)
, 18 07 16
Curre
nt
rechar
ge
inform
ation