SDM220-MBUS 

Single-Phase Two Module DIN rail Meters 

 

 

 

Measures kWh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.   

 

Bi-directional measurement IMP & EXP 

 

Two pulse outputs 

 

MBUS 

 

Din rail mounting 36mm 

 

100A direct connection 

 

Better than Class 1 / B accuracy   

 

User Manual V1.8 

2016

 

Содержание SDM220-MBUS

Страница 1: ...ngnan Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email ssales eastron com cn 1 SDM220 MBUS Single Phase Two Module DIN rail Meters Measures kWh Kvarh KW Kvar KVA PF Hz dmd V A etc Bi directional measurement IMP EXP Two pulse outputs MBUS Din rail mounting 36mm 100A direct connection Better than Class 1 B accuracy User Manual V1 8 2016 ...

Страница 2: ...ice for solar PV energy metering PART 1 Specification General Specifications Voltage AC Un 230V Voltage Range 176 276V AC Base Current Ib 5A Max Current Imax 100A Mini Current Imin 0 25A Starting current 0 4 of Ib Power consumption 2W 10VA Frequency 50 60Hz 10 AC voltage withstand 4KV for 1 minute Impulse voltage withstand 6KV 1 2uS wavform Overcurrent withstand 30Imax for 0 01s Pulse output rate ...

Страница 3: ... output 2 is non configurable It is fixed up with Import kWh The constant is 1000imp kWh MBUS M Bus Meter Bus is a hierarchical system that consist of a Master several Slaves and a pair of connecting cables All the devices are serially connected to the Bus and all the the serial communication process on the Bus are controlled by the major device The work status of Mbus are Data transmission status...

Страница 4: ...tput 1 and Pulse output 2 7 Measurement units 8 PF power factor Hz frequency 9 Bar display of Power 10 Communication indicator 11 Time information 12 Low battery warning 13 Lock symbol PART 2 Operation Initialization Display When it is powered on the meter will initialize and do self checking Full screen software version MBUS ID Secondary address Secondary address high bit low bit Baud rate total ...

Страница 5: ...order by scroll button Total kWh import kWh export kWh total kVarh import kVarh export kVarh Max power demand voltage current W Var VA power factor frequency pulse constant MBUS primary address MBUS secondary address baud rate Page Display Descriptions 1 Total active energy Example 70 00kWh 2 Import active energy Example 50 00kWh 3 Export active energy Example 20 00kWh 4 Total reactive energy Exam...

Страница 6: ...dress No 1369 Chengnan Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email ssales eastron com cn 6 6 Export reactive energy Example 5 00kVarh 7 Total max demand Example 6930W 8 Voltage Example 229 8V 9 Current Example 30 156A 10 Active Power Example 4700W 11 Reactive Power Example 1030Var 12 Apparent power Example 4811VA ...

Страница 7: ...ales eastron com cn 7 13 Power factor Example 1 000 14 Frequency Example 49 99Hz 15 Pulse Constant Example 1000 16 MBUS primary address Example 001 MBUS Secondary address 17 High bit of MBUS Secondary address Default 00 00 18 Low bit of MBUS Secondary address Default 00 01 Example if the Secondary address high bit is 0000 low bit is 0001 that means the integral Secondary address is 00 00 00 01 19 ...

Страница 8: ...r button for 3 second Page Display Descriptions The setting is done correctly The entering information is wrong The operation fails 1 Password To get into Set up mode it asks a password confirmation Default password 1000 2 Address ID Default ID is 001 Range 001 250 2 1 Press the Enter button the first digit flash Press the Scroll button to change the value After choose the new address value the us...

Страница 9: ...croll button to change the value After choose the new baud rate the user need pressing the Enter button to confirm the setting 5 Parity Default None Option None Even Odd 5 1 Press the Enter button the red part flash Press the Scroll button to change the option After choose the new Parity the user need pressing the Enter button to confirm the setting 6 Pulse Output Default kWh Option kWh KVarh Imp ...

Страница 10: ...ion the user need pressing the Enter button to confirm the setting 8 Pulse duration Default 100mS Option 200 100 60ms 8 1 Press the Enter button the red part flash Press the Scroll button to change the option After choose the new Pulse duration option the user need pressing the Enter button to confirm the setting 9 Demand Integration Time Default 15 minutes Option 0 5 10 15 30 60 9 1 Press the Ent...

Страница 11: ...astron com cn 11 10 1 Press the Enter button the red part flash Press the Scroll button to change the option After choose the new Scrl option the user need pressing the Enter button to confirm the setting 11 Password Default 1000 11 1 Press the Enter button the red part flash Press the Scroll button to change the value After choose the new password the user need pressing the Enter button to confir...

Страница 12: ...axing Eastron Electronic Instruments Co Ltd Tel 0086 573 83698881 83698882 Fax 0086 573 83698883 Address No 1369 Chengnan Road Jiaxing Zhejiang 314001 China Web www eastron com cn Email ssales eastron com cn 12 Dimensions Installation ...