background image

 

22 

mode   

Faults mode 

Working mode displays 

FAULT, numerical 

value area displays the 

corresponding error 

code 

Long 

beep 

Flash 

always 

Flash 

always 

Note:

   

 

End user need to provide below information when require to maintain the UPS. 

 

UPS Model No. & Serial No. 

 

Date of fault occurrence. 

 

Fault details (LCD status, noise, AC power situation, load capacity, battery capacity 

configuration ect.) 

Table 3: Alarm code display 

The alarm code will be displayed in four digital tubes on the right of the numerical part 

of the LCD screen (red mark), as shown below: 

 

The alarm truth table during operations is shown as below

 

‘●’ 

signifies the alarm occurs, blank signifies no alarm appears 

 

The first 

digital tube 

from right to 

left 

Display 

 

Bypass lost 

Remote 

 

overload 

Battery 

 

 

 

 

 

● 

 

 

 

 

● 

 

 

● 

● 

 

 

 

 

● 

 

● 

 

● 

 

 

● 

● 

 

● 

● 

● 

 

 

 

 

● 

● 

 

 

● 

 

● 

 

● 

Alarm code

 

Alarm

 icon

 

Содержание EA900Pro Series

Страница 1: ......

Страница 2: ...STALLATION INFORMATION 7 3 3 INSTALLATION AND OUTPUT CONNECTION 8 3 4 EXTERNAL BATTERIES CONNECTION LONG BACKUP MODEL 8 4 Network Functions 10 4 1 COMMUNICATION PORT 10 4 2 EPO PORT OPTIONAL 10 4 3 IN...

Страница 3: ...ded CAUTION UPS has high voltage inside do not repair it by yourself If any questions please contact local service center or dealer 1 2 Battery safety information Environmental factors impact battery...

Страница 4: ...ic Do not connect the positive pole and negative pole directly otherwise it will cause electric shocks or will be on fire The battery circuit is not isolated from the input voltage high voltage may oc...

Страница 5: ...Hz PFC 0 99 THDI 6 Bypass voltage range 25 15 settable Output Output voltage 208 Vac 220 Vac 230 Vac 240 Vac settable Voltage accuracy 1 Output PF 0 9 Inverter overload capability 105 125 load transf...

Страница 6: ...ion Battery discharge protection Communication port Standard RS232 Options USB SNMP card dry contacts Display LCD Environmental Operating humidity 0 90 RH 0 40 C non condensing Storage temperature 25...

Страница 7: ...C input socket RS232 port Overcurrent protector Intelligent slot Fan Surge protection for network fax modem USB port Output sockets EPO Emergency Power Off port Battery connector Note The figure is fo...

Страница 8: ...nel air intake hole rear panel air outtake hole will be unobstructed The ambient temperature around the UPS should be within 0 4 non condensing If dismantling the machine at low temperatures there may...

Страница 9: ...Input Output Battery Non isolated Neutral Ground 1kVAS_DC24V 1mm 1mm 6mm 1mm 1mm 1kVAS_DC36V 1mm 1mm 4mm 1mm 1mm 1kVAH_DC36V 1mm 1mm 4mm 1mm 1mm 2kVAS_DC48V 1 5mm 1 5mm 6mm 1 5mm 1 5mm 2kVAS_DC72V 1 5...

Страница 10: ...ct batteries correctly and make sure the total battery voltage is available for UPS Correctly connect the long battery cable to battery terminals first red wire is to positive plate while black is to...

Страница 11: ...2 3 4 Indication 5V date date GND 4 2 EPO port optional Normally pin1 and pin2 are connected so that the machine can be working normally When some emergencies happen and when users have to cut off the...

Страница 12: ...card on UPS is compatible with the most software hardware and network operating system it is a network management of UPS with this function UPS can login on internet which can supply information of UP...

Страница 13: ...de Press or for more than half a second less than 2 seconds display the items orderly Press for more than 2 seconds Circularly and orderly display the items every 2 seconds when press the key for some...

Страница 14: ...50 51 75 and 76 100 When the capacity of battery get low or battery disconnected the battery status icon will flash UPS status information In non setting mode it displays UPS output information when...

Страница 15: ...f test function When the self test finishes it will turn to online mode Turn on the UPS by battery without mains power When main power is disconnected press the ON key for more than half a second to s...

Страница 16: ...numerical value press and hold the function setting for more than half a second less than 2 seconds Now the setting function is completed and the numerical value illuminates without flashing Exit fro...

Страница 17: ...tomatically varies with loads including 21 5 hours discharge protection Bypass mode setting LCD display Settings Enable or disable Bypass function You may choose the following two options ON Bypass en...

Страница 18: ...ple as the following graphics shows the WATT of the load is 800W VA is 1 0kVA when disconnect loads it is a normal phenomenon to show a small numerical value of WATT and VA Version and Temperature Ind...

Страница 19: ...ass setup is ON Turn off the UPS in line mode and the bypass setup is ON Overload in line mode Note When UPS is working in bypass mode it has no back up function Line mode Being in line mode are as fo...

Страница 20: ...ot be affected by utility to meet input needs of some precision equipment and make users load more stable and secure After opening CUCF mode setup LCD displays CUCF Under the CUCF mode when the output...

Страница 21: ...yes 55 56 57 58 59 Line NTC break yes 60 61 62 63 64 Shutdown fault yes 65 66 67 68 69 AC input fuse open yes unused 70 71 72 73 74 Communication fault yes unused 75 76 77 78 79 Communication fault ye...

Страница 22: ...capacity of the UPS later working mode displays Line or byPASS bat icon flash all the time 6 beeps Flash always Flash always Flash always 5 Output overload protection Warning for mains power overload...

Страница 23: ...D status noise AC power situation load capacity battery capacity configuration ect Table 3 Alarm code display The alarm code will be displayed in four digital tubes on the right of the numerical part...

Страница 24: ...ital tube from right to left Display Overcharging Mains Start up Charger fault 0 1 2 3 4 5 6 7 8 9 A B C D E F The third digital tube from right to left Display EEPROM Fan Low battery Median abnormal...

Страница 25: ...24 E F The fourth digital tube from right to left Display Over load fault Mains lost Bypass 0 1 2 3 4 5 6 7 Example If the alarm code 2000 appears on the LCD screen it indicates loss of mains power...

Страница 26: ...side Be sure that the UPS are not overloaded and the fan vent is not obstructed as well as the indoor temperature is not high Leave alone the UPS 10 minutes for cooling and restart it If the problem p...

Страница 27: ...e power key more than 2 seconds to start the UPS The input connection is not ready or UPS internal battery disconnect Connect the input well if the battery voltage is too low disconnect the input and...

Отзывы: