C. Installation instruction

8. When unit operation, put the unit in a well-ventilated place and non-blocking the air vent, so that the

machine can be able to inhale and exhaust enough air, to achieve hot water supply function.

9. There should be with drain around the system unit for drainage. And the surrounding should have

enough space for maintenance. Because the top cover can be opened, at the top side of the unit
should have 

800mm space for maintain.

10. Nearby the system unit, there should be reserved a water supply pipe and hot water pipe interface

equipped with valves, the water inlet pipe should be with filter (for cleaning).

11. For waterway connection of this integrated unit, please refer to the following  (Fig.4)  “Waterway

installation diagram”. On the system unit, there should be installed Three-port valve, Safety valve and
Filter. Connect them to the water inlet and outlet of the unit.

12. If the Heat pump equip with 

“Circulation Water Hole”

 (optional), It can be connected with SOLAR

WATER HEATER, HEAT RECOVERY SYSTEM and other water heating equipment to heat the water
tank by circulation. Retain original if no need external connection.

13. The working pressure of this water heater tank must 

0.7MPa. Water inlet must connect the safety

valve, and its operation pressure is 0.7MPa, Connect another end of the safety valve to water supply
pipe. The safety valve should be connected by a small rubber pipe interlinked with atmosphere; this
pipe must not be blocked, in order to drain the water when the tank’s pressure exceeds 0.7MPa.

14. Water inlet pressure should >0. 1MPa, if the pressure is lower, can connect the pressure pump on

inlet pipe to get the high water flow.

15. Ensure the water tank is full fill with water before turn on the system: First, open the valve on the

water supply inlet, then switch on either valve of the water outlet, and then you can affuse water to the
tank until the water overflow the water outlet valve. After which you can turn off the water outlet valve
and check for leakage. Make sure there is no water leaking.

NOTE:

 

For the first time use, ensure the water tank has been filled with water before turn on the

system.

16. In order to ensure the water tank filled with water, require a certain section of hot water outlet side

should be about 10cm higher than the water heater tank section.

17. The water heater temperature thermal sensor was put and sealed well in a tank by the factory before

launch to market. No need to install it when installation.

18. This water heater unit is filled with refrigerant by the factory, and no need to vacuumize or refill

refrigerant.

19. In the winter cold regions, the water heater unit can not turn off the power, if the system stops running

for a long period in winter, should be drain the tank water to avoid water pipe or tank frost crack.
Meanwhile, we should strengthen or check the external pipe to prevent the pipe frozen.

V.4

Содержание E190WHF

Страница 1: ...E190WHF ACUMULADOR AEROT RMICO ACS HEAT PUMP WATER HEATER MANUAL DE INSTRUCCIONES INSTRUCTION MANUAL V V 4...

Страница 2: ...en STOP cuando desconecte la fuente de alimentaci n de la unidad Desconecte todas las fuentes de alimentaci n el ctrica antes de realizar cualquier mantenimiento 3 Este producto no est dise ado para...

Страница 3: ...e causar da os personales o en el sistema 9 Para que el sistema sea m s eficiente instale la unidad principal en un lugar con buena ventilaci n 10 No coloque ni instale el panel de funcionamiento en u...

Страница 4: ...leado L nea el ctrica Orificio agua en circulaci n Orificio de la tuber a del sensor de temp Orificio agua en circulaci n Orificio de drenaje del condensado Salida de agua caliente Observaciones 1 La...

Страница 5: ...se puede instalar en el medio de la pared y conectar las tuber as de entrada y salida de aire para el intercambio de aire La distancia de la unidad y la pared u otro obst culo no debe ser demasiado co...

Страница 6: ...Conecte otro extremo de la v lvula de seguridad a la tuber a de suministro de agua La v lvula de seguridad debe estar conectada por un peque o tubo de goma interconectado con la atm sfera esta tuber a...

Страница 7: ...del sistema de agua el usuario o la empresa de instalaci n deben proporcionarlos 3 Antes de la instalaci n es mejor reservar una conexi n de tuber a de suministro de agua una conexi n de tuber a de s...

Страница 8: ...6 D Instrucciones del panel de funcionamiento 1 Panel Funcionamiento V 4...

Страница 9: ...de apoyo Estado HTG Heating calentamiento DEF Defrost descongtelaci n WARM Keep warm Mantiene caliente Modo de funcionamiento Ajuste de hora Periodos temporizador Temperatura agua Gradiente de temper...

Страница 10: ...or Descongelaci n Alarma Ajuste de funciones Ajuste de temperatura Diferencia en temperatura Determina la temperatura ambiente de parada de la bomba de calor Temperatura m s alta para la bomba de calo...

Страница 11: ...n Descongelamiento forzado refrigeraci n Panel de control muestra AdF Arranca el compresor la v lvula de 4 v as y el motor del ventilador Presione cualquier tecla para salir o en 20 minutos saldr aut...

Страница 12: ...de temperatura ambiente o cortocircuito 1 Compruebe la conexi n del sensor de temperatura ambiente 2 Cambie el sensor de temp ambiente Alarma de presi n alta baja 1 1 Protecci n por alta presi n apag...

Страница 13: ...mucho tiempo puede haber agua de condensaci n cerca de la salida o tuber a de aire especialmente en condiciones de humedad esto es un fen meno normal use una toallita seca para limpiarla o secarla al...

Страница 14: ...5 de la parte inferior de la cubierta superior 4 Suelte la l nea de alimentaci n de la cubierta superior del terminal fijo para evitar que la l nea de alimentaci n se atasque cuando suba la cubierta...

Страница 15: ...auxiliar SENSOR TEMP RETORNO DE GAS SENSOR TEMP DE ESCAOE SENSOR TEMP BOBINA SENSOR TEMP AMBIENTE V lvula de expansi n electr nica PROTECTOR DE PRESI N PROTECTOR RESISTENCIA DE APOYO AMARILLO VERDE V...

Страница 16: ...que ser recogidos selectivamente para optimizar la recuperaci n y reciclado de los componentes y materiales que los constituyan y reducir el impacto en la salud humana y el medio ambiente El s mbolo d...

Страница 17: ...ad exterior En toda instalaci n tanto nueva como ya existente se debe realizar una limpieza a fondo de las tuber as utilizando un producto de limpieza qu mico adecuado y despu s lavar las tuber as par...

Страница 18: ...causas fortuitas o siniestros de fuerza mayor o como consecuencia de un uso anormal negligente o inadecuado del aparato 7 Responsabilidades civiles de cualquier naturaleza 8 P rdidas o da os en el sof...

Страница 19: ...es que puedan tener acceso al interior de la m quina o sus puntos de conexi n 17 Da os derivados de terrorismo mot n alboroto o tumulto popular manifestaciones y huelgas legales o ilegales hechos de a...

Страница 20: ...unit is STOP operation when disconnecting the power supply to the unit Disconnect all electric power supplies before servicing 3 This appliance is not intended for use by persons including children w...

Страница 21: ...at pump it may cause the dangerous to people or damage the system 9 To make the system more efficiency please install the main unit at a place with good ventilation 10 Do not put or install the operat...

Страница 22: ...te Drain Hole Circulation Water Hole Wiring Hole Power Line Temp Sensor Tube Hole Circulation Water Hole Hot Water Outlet Remark 1 The above drawing is for reference to identify the name of each part...

Страница 23: ...middle of the wall and connect the air inlet and outlet pipe for air exchange The distance of the unit and wall or other obstacle should not be too short Keep a certain distance 4 If install as Fig 3...

Страница 24: ...The safety valve should be connected by a small rubber pipe interlinked with atmosphere this pipe must not be blocked in order to drain the water when the tank s pressure exceeds 0 7MPa 14 Water inlet...

Страница 25: ...on parts see the annex detail list of parts As for other water system components the user or installation company should provide by themselves 3 Before installation it s better to reserve a water supp...

Страница 26: ...D Operation panel instruction 1 Panel Operation V 4...

Страница 27: ...gh Temperature Alarm Auxiliary Heater Status HTG Heating DEF Defrost WARM Keep warm Working Mode Time adjustment Time Timer On Timer Off Timer Period Water Temperature Temperature Gradient Note When t...

Страница 28: ...temp amendment 5 5 0 C Compressor F21 Compressor start delay 0 10 3 minute F28 Econ mode turn on or off electric heater 0 1 1 F29 Heat pumps working or not in heater mode 0 1 1 Defrost F31 Defrost sta...

Страница 29: ...EEV F70 EEV opening query 0 480 F71 EEV control mode 0 2 0 F72 Manually set EEV opening 100 480 350 F73 Set EEV superheat degree 15 15 5 F74 Set EEV discharge temp 85 110 92 F79 Return gas temp Syste...

Страница 30: ...emp is too high 2 Change the Electric heater A7 Exhaust temperature too high 1 Lack of refrigerant 2 Mix with air in system 3 Lack of lubricating oil 1 Supply refrigerant 2 Re vacuumizing and fill in...

Страница 31: ...ion for a long time there may have condensation water hereabout the air outlet or pipe especial in humidity weather this is a normal phenomenon use a dry washcloth to clean it or by air dry 6 The adva...

Страница 32: ...ative strip vertically 15 20mm then pull it out horizontally to separate hook A 2 from hook A 3 until exposed butt splice connector 2 Disconnect control panel with butt splice connector 3 Remove all s...

Страница 33: ...y electric heater RETURN GAS TEMP SENSOR EXHAUST TEMP SENSOR COIL TEMP SENSOR AMBIENT TEMP SENSOR Electronic expansion valve PRESURE PROTECTOR ELECTRIC HEATER PROTECTOR YELLOW GREEN FAN MOTOR 4 WAY VA...

Страница 34: ...ste stream appliances must be collected separately in order to optimize the recovery and recycling of the materials they contain and reduce the impact on human health and the environment The crossed o...

Страница 35: ...5 Water hardness 50ppm Before connecting the outdoor unit In any installation both new and existing a thorough cleaning of the pipes should be carried out using a suitable chemical cleaning product an...

Страница 36: ...sed by fortuitous causes or accidents of force majeure or as a result of abnormal negligent or inappropriate use of the device 7 Civil liabilities of any nature 8 Loss or damage to software or informa...

Страница 37: ...dents and other animals that may have access to the interior of the machine or its connection points 17 Damages derived from terrorism riot or popular tumult legal or illegal demonstrations and strike...

Отзывы: