background image

 

 
 

13 

 

having completed burr removal. (not 
possible to put them on after flaring work). 
(Figure 16)

 

D: Flaring Work 

     

Caution

 Main cause for refrigerant 

leakage is due to defect in the flaring 
work. Be sure to follow specific flaring tool 
instructions when flaring the copper 
tubing.   
Firmly hold the copper pipe into the flaring 
tool (Figure 17) and flare until the cone is 
properly formed. 

 

E: Tightening Connection 

 Align the center of the pipes. (Figure 18) 

 Sufficiently tighten the flare nut with 

fingers, and then tighten it with a wrench 
and torque wrench as shown in Fig 19 & 
20. 

     

Caution

 Excessive torque can break 

the nut. 
 

 

3.7 Electrical Work 

Electrical safety regulations for the initial installation 

 

If there is an unsafe power supply, the 

technician should refuse to install the heat 

pump mini-split and explain to the client what 

the problem is. 

 

Power voltage should be in range of 

90%~110% of rated voltage. 

 

Ground Fault Protection must be provided, 

see page 30 for more details. 

 

Refer to the Electrical Connection Diagram 

located on the panel of the outdoor unit to 

connect wires. 

 

All wiring must comply with local and national 

electrical codes and be installed by licensed 

electricians. 

 

An individual branch circuit and single 

receptacle used only for this heat pump 

mini-split must be available.   

Outer Diameter  Torque 

Additional Torque 

¼” 

11.06 Ft. Lbs. 

11.8 Ft. Lbs. 

½” 

25.80 Ft. Lbs. 

26.55 Ft. Lbs. 

Flare Nut 

Copper Tube 

Figure 16 

Yoke 

Handle 

Bar 

Clamp Handle 

Red Arrow Mark 

Cone 

Indoor Unit Tubing 

Flare Nut 

Tube 

Figure 18 

Figure 19 

Figure 20 

Figure 17 

Содержание ENE ACDC12

Страница 1: ...replacement must be performed by authorized personnel only Installation work must be performed in accordance with the NEC and local codes You should contact a licensed service technician for installa...

Страница 2: ...lecting Installation Location 7 3 4 Indoor Air Handler Installation 9 3 5 Outdoor Condenser Installation 11 3 6 Refrigerant Tube Connection 12 3 7 Electrical Work 13 3 8 Evacuation Refrigerant 15 4 Te...

Страница 3: ...work in compliance with local building and electrical codes Are there any restrictions on the purchase of R410A refrigerants R410a is not an ozone depleting substance At this time the purchase of R410...

Страница 4: ...se the correct rating and main circuit for the model to be installed Use a dedicated circuit If electrical circuit capacity or electrical work is not proper it can cause electrical shock or fire Wirin...

Страница 5: ...time to time when operating it together with a stove etc to eliminate the risk of fire or electrical shock Turn the main power off when cleaning or maintaining the product to eliminate the risk of fi...

Страница 6: ...ges and the fins on the condenser and evaporator This equipment must be installed with DC ground fault protection NEC 2005 Article 690 5 Refer to grounding section in this manual Install drainage line...

Страница 7: ...or use by young children without supervision Young children should be supervised to ensure that they do not play with the air conditioner Do not touch the metal parts of the product when removing the...

Страница 8: ...ir Handler Installation Plate Model R L H Dimension of installation hole ENE ACDC12 6 6 2 2 5 2 3 Outdoor Condenser Model W D H W1 A B ENE ACDC12ODU 29 9 11 22 23 23 32 4 20 87 11 42 Air inlet Air inl...

Страница 9: ...mote Controller Holder 1 3 2 Recommedned Tools Level Gauage Hex Wrench 4mm Screwdriver Leak Detector Electric Drill Vacuum pump Hole Saw Bit Gaugage Manifold Flaring Tool Users Manual Torque Wrench Th...

Страница 10: ...ronic instrument There should not be any direct sunlight on the indoor unit sunlight may fade the color of the unit Outdoor Condenser If an awning is built over the outdoor condenser it must be done i...

Страница 11: ...e 3 Fit the installation bracket on the wall with six 6 anchor screws Note Fit the installation bracket and drill holes in the wall according to the wall structure and corresponding mounting points on...

Страница 12: ...easily be made by lifting the indoor air handler with a cushioning material between the indoor air handler and the wall Remove material after it is not needed 4 Push the lower part of the indoor air h...

Страница 13: ...Determine the air outlet direction where the discharged air is not blocked In the case that the installation site is exposed to strong wind make sure the fan is operating properly by putting the unit...

Страница 14: ...air handler and the outdoor condenser 3 Cut the pipes a little longer than the measured distance Caution Minimum length required is 10 FT to minimize vibration and excessive noise Maximum length is 65...

Страница 15: ...initial installation If there is an unsafe power supply the technician should refuse to install the heat pump mini split and explain to the client what the problem is Power voltage should be in range...

Страница 16: ...ectrical box cover by loosening the screw Figure 24 4 Release the coupler plugs connected with the front display panel Figure 25 5 Connecting cable between indoor air handler and outdoor condenser sha...

Страница 17: ...ard with the cord clamp 4 To prevent the ingress of water form a loop of the connective cable as illustrated in the installation diagram of indoor and outdoor units 5 Insulate unused cords conductors...

Страница 18: ...e Check gauge for proper vacuum 6 Run evacuation for 30 minutes or more and check that the vacuum sensor indicates less than 400 microns After the evacuation is complete fully close the LOW valve of t...

Страница 19: ...32 155 PSI 65 F 471 435 386 368 339 PSI 80 F 135 129 132 140 162 PSI 75 F 489 457 403 381 362 Make sure the refrigerant is added into the heat pump mini split in a liquid form Caution Please contact a...

Страница 20: ...in this guide when installing the modules Local codes should also be followed in such installations Before installing a solar photovoltaic system the installer should become familiar with the mechani...

Страница 21: ...igure 33 Caution When disconnecting wires from a photovoltaic module that is exposed to sunlight an electric arc may result Such arcs may cause burns combustion and may otherwise create problems There...

Страница 22: ...s in the OFF state push the switch to OFF position Figure 37 Solar modules produce electrical energy when light strikes on their front surface The DC voltage may exceed 30V If modules are connected in...

Страница 23: ...module frame must be properly grounded The grounding wire must be properly fastened to the module frame to assure good electrical contact Use the recommended type or an equivalent connector for this w...

Страница 24: ...will void the warranty Modules must be securely attached to the mounting structure using four mounting points for normal installation If additional mounting points are also used The support frame mus...

Страница 25: ...g a module on a roof or building ensure that it is securely fastened and cannot fall as a result of wind or snow loads When installing the module on a roof or building do so in calm winds Installing a...

Страница 26: ...Any penetrations that are made to the wall to mount the modules must be sealed to prevent leaks 5 5 General Installation Do not install in rainy weather it may cause insulation failure due to moistur...

Страница 27: ...is any problem with module If modules used in solar photovoltaic system are not the specified brand of the manufacturer it must comply with the electrical requirement The cross section area of the ca...

Страница 28: ...bles only The cable can resist UV rays and climate of rapid change The rated voltage of the cable is more than 600V The cross section area of the cable depends on the maximum short circuit current and...

Страница 29: ...itable for use in solar electric systems If you want to use the connector purchased by yourself the following requirements must be complied Use only connector special designed for solar electric syste...

Страница 30: ...28 Wiring the Combiner Box...

Страница 31: ...29 Wiring the DC Disconnect Ground From Outdoor Condenser Ground From Combiner Box Positive From Combiner Box Negative From Combiner Box Negative From Outdoor Condenser Positive From Outdoor Condenser...

Страница 32: ...d fault occurs when a current carrying conductor comes into contact with the frame or chassis of the faulty appliance or an electrical box A person who touches the frame or chassis of the faulty appli...

Страница 33: ...ding The grounding resistance must be less than 10 ohms Ground fault protection Roof mounted DC PV arrays located on dwellings must be provided with DC ground fault protection NEC 2005 Article 690 5 G...

Страница 34: ...bility is assumed by us for any infringement of patents or other rights of third parties which may result by using the PV product No license is granted by modification or otherwise under any patent or...

Отзывы: