Troubleshooting
ADC100 Alarm Stages
•
Flashes 1
- If damper prove does not close 90 seconds after AUX IN, go into alarm for 30 seconds, followed by a full retry
•
Flashes 2
- If initial PDS prove does not close 180 seconds after damper prove, go into alarm for 30 seconds, followed by a full
retry
•
Flashes 3
- If PDS loses proof for 15 seconds after initial PDS prove, AUX OUT de-energize, stay in alarm until PDS prove returns
and AUX OUT will re-energize
•
Flashes 4
- If at any point after AUX OUT proves the damper prove is removed, the board immediately goes into alarm for 30
seconds, followed by a full retry
•
Flashes 5
- *must have sw3 on* if PDS is proved prior to AUX IN, board will go into alarm and no further states can be achieved
until proof is removed