background image

CREATED ON: May 24, 2018

 

 

  
 
    

  

OPERATING 

CONDITION

/MODE  

TIMING 

SEQUENCE 

STATUS 

RELAY 

LED 

CH1 

ON TIME 

RLY1 ON 

ON 

OFF TIME 

RLY1 OFF 

OFF 

CH2 

ON TIME 

RLY2 ON 

ON 

OFF TIME 

RLY2 OFF 

OFF 

CH3 

ON TIME 

RLY3 ON 

ON 

OFF TIME 

RLY3 OFF 

OFF 

CH4 

ON TIME 

RLY4 ON 

ON 

OFF TIME 

RLY4 OFF 

OFF 

 

 

a) The Set time changed when timing in progress is effective for the next 
cycle onwards (after the completion of the off time of ch4). 

b) The Set time changed when S1-S2 is open is effective for the immediate 
timing irrespective of hold/restart (i.e. Power is not interrupted).   

c) The Range settings shall not be done in the forbidden area.

 

 

Technical Specification     

Function 

Sequential timer with 4 channels. 

Rated supply Voltage 

240V AC 

Operating voltage  
range 

± 10% of the rated voltage 

Rated Frequency 

50Hz ± 5% 

Power consumption 

AC Approx. 20VA / 4W. 

Control output 

4 O/P'S (5A @ 250 VAC/28  VDC resistive) 

Start Signal (S1, S2) 

Potential free closure (CONTINUOUS). 

On time range 

0.1 to 1 S/M/H for each channel 

Off time range 

0.1 to 1 S/M/H for each channel 

Setting accuracy 

± 10 % max. w.r.t full scale ± 100 mSec 

Repeat accuracy 

 

± 1 % max. ± 100 mSec 

Recovery Time 

1Sec minimum 

Variation due to 
voltage change 

± 2% max. ± 100 mSec 

Variation due to 
temperature change 

± 5% max. ± 100 mSec 

Variation due to 
frequency change     

 

± 2% max. ± 100 mSec 

Ambient temperature 

Operating    :          -10

˚

C to +55

˚

Storage 

    :          -25

˚

C to +80

˚

Humidity 

MAX 85% RH @ 40

˚

 

 

 

          

  

 

Disposition 

Once the product life is over, you may send Back the unit to 
 EAPL for disposition. 

 

Contact

 

Electronic Automation Pvt. Ltd 
#20, KHB Industrial area 
Yelahanka 
Bangalore -64 
Ph:+91-80-28567561/2,/42802345 
Customer care :Ph:+91-80-42802323 

Email : 

[email protected]

 

            

www.eaplindia.com

 

     

 

 

 

 

 

 

 

 

 

 

 

                                   

OD RK AN 050011

 

REV 02/24-05-2018

 

Page 2 of 2 