DCPS-6K
Maintenance & Operation Manual
Issue 2.0 Sept-2016
DCPS-6K
Maintenance & Operation Manual
7 /23
● When cables are connected, battery should be separated from the
rectifier system except one point of the conductor at each cell.
● Start operation after all connections (battery, load, and grounding
wires/cables) are made but Circuit Breakers are OFF.
● Connect the battery wire, load and grounding wire while the load side
has been unloaded and Circuit Breakers are OFF.
● External transmission signal should be ≤ 60V level and ≤ 0.5A.
● Rectifier unit should be inserted and removed using the guide rail of
the rectifier system, to engage connectors without damage.
● ● Use caution during an AC failure event as the AC power may be
restored at any time. Use special care to lockout/tagout the AC
whenever necessary, check the presence of, and maintain the AC
input to the power shelf, as needed.