Product Manual Mona Switch V2 

EAE KNX Mona Series

                                                                                    

MONA Switch R3.0

 

©

EAE Technology                                              www.eaetechnology.com                                                               Page 34 / 34 

Parameter 

Settings 

Description 

Operation ( continues... ) 

 

Settings 

(continues…)

 

NOT Sum is 1 or 0: 

If the one of the input is “True” and 

rest  of  all  are  “False”  or  all  inputs  are  “False”,  the 
result will be “False”. If 2 or more inputs are “True”, 

the result will be “True”.

 

All 0’s or All 1’s:

 

If all inputs are “False” or “True”, the 

result will be “True”.

 

 

NOT All 0’s or All 1’s:

 

If all inputs are “False” or “True”, 

the result will be “False”.

 

Trigger 

operand update 

 

operand update 
with blocking 

condition 
 

operand update 

with set/reset 
STATE 

 

input select 

operand  update:  Output  will  be  processed  If  any 
operand value changed. 

 

operand  update  with  blocking  condition:  Output 

won’t be processed regardless to operand change, if 

blocking operand is active. 

 
operand  update  with  set/reset  STATE:  This  function 

should  be  used  with  STATE  operand.  This  function 

allows  to  change  the  output  state  according  to 
selected Input or Registered Output(if exist) value. 

 

input select: Output will be processed if the selected 
Input or Registered Output(if exist) has trigger value. 

Sending blocked when 

IN1 

… 15 or

 

REG OUT 1…15

 

This  function  is  used  to  block  the  output  sending  If 
selected Input or Registered Output has its selected 
value. 

Send pending telegram 

after unblocking 

unchecked

/checked  This    function  is  used  to  send  output  state  after 

unblocking. 

Send value when 
expression is 

False 
True 

True or False 

This function is used to send the output result if the 
Output expression value is as selected. 

False Value (1-bit) 

0

 / 1 

True Value (1-bit) 

0 / 

False Value (1-byte) 

0

…255

 

True Value (1-byte) 

0…

1

…255

 

False Value (2-bit) 

00b No Priority, OFF 

/  

01b No Priority, ON / 
10b Priority, OFF /  
11b Priority, ON

 

True Value (2-bit) 

00b No Priority, OFF

 

/  

01b No Priority, ON

 / 

10b Priority, OFF /  
11b Priority, ON

 

Send only on change 

unchecked

/checked 

This  function  is  used  select  the  type  of  output 
sending. 

Send initial state after KNX 
bus recovery 

unchecked

/checked 

This  function  is  used  to  send  initial  state  of  related 
output after KNX bus recovery. 

Initial state 

False

 / True 

This parameter is used to select initial value of related 

output when device energized(or reset). 

State after KNX bus 

recovery 

Initial

 / Last 

This  parameter  is  used  to  select  the  related  output 

state after KNX bus recovery. 

Timer 

none 

 

delayed sending 

 

periodical sending 

 

state hold timeout 

delayed sending: This parameter is used to determine 

delay for output sending. 

 

periodical sending: This parameter is used to send the 

output state cyclically. 

 

state hold timeout: This parameter allows to keep the 

state in case of state changes. 

 

Содержание MONA SWITCH V2

Страница 1: ...Product Manual Mona Switch V2 EAE KNX Mona Series MONA Switch R3 0 EAE Technology www eaetechnology com Page 1 34 EAE MONA SWITCH V2...

Страница 2: ...General 10 4 1 1 Parameters 10 4 1 2 Communication Objects 12 4 2 LED Brightness 13 4 2 1 Parameters 13 4 2 2 Communication Objects 13 4 3 LED Color 14 4 3 1 Parameters 14 4 3 2 Communication Objects...

Страница 3: ...ACK MN W S04 MONA 4 BUTTON SW WHITE MN B S05 MONA 5 BUTTON SW BLACK MN W S05 MONA 5 BUTTON SW WHITE MN B S06 MONA 6 BUTTON SW BLACK MN W S06 MONA 6 BUTTON SW WHITE MN B S07 MONA 7 BUTTON SW BLACK MN W...

Страница 4: ...of functional flexibility up to 12 programmable buttons Mona switches can be programmed for control lighting shutter blind drivers speakers make scene calls and mimic panic buttons Each button can be...

Страница 5: ...via the KNX bus Current drawn from bus 25 mA Connections KNX Bus Connection Operating Temperature Ambient 5 C 45 C Storage 25 C 55 C Humidity Max Air humidity condensation 95 no moisture Dimensions F...

Страница 6: ...12 Long Press Repeat 1 Button 1 12 Long Press Release 1 Value 1 bit 1 bit DPT 1 001 CT Value 1 bit HVAC Control Mode 1 bit DPT 1 100 CT Value 1 bit toggle 1 bit DPT 1 001 CT Value 2 bit priority contr...

Страница 7: ...ol Mode 1 bit DPT 1 100 CT Value 1 bit toggle 1 bit DPT 1 001 CT Value 2 bit priority control 2 bit DPT 2 001 CT Value 4 bit dimming control 4 bit DPT 3 007 CT Value 4 bit blind control 4 bit DPT 3 00...

Страница 8: ...d 2 Byte DPT 7 001 CT Value 2 byte signed 2 Byte DPT 8 001 CT Value 2 byte float 2 Byte DPT 9 001 CT Value 3 byte color 3 Byte DPT 232 600 CT Value 4 byte unsigned 4 Byte DPT 12 001 CT Value 4 byte si...

Страница 9: ...07 CW 75 LED Brightness Custom Level 0 Off 1 7 1 Byte DPT 5 010 CRW T LED Brightness Custom Level 0 0 Off 0 4 100 1 7 1 Byte DPT 5 001 CRW T LED Brightness Custom Level Raw 0 Off 0 4 100 1 Byte DPT 5...

Страница 10: ...Limiter checked Maximum number of telegrams to send in telegram limit period duration Telegram Transmission Delay 1 255 This parameter is used to set delay for sending the first telegram when device...

Страница 11: ...Parameter Settings Description LOGIC BLOCKS Logic Blocks None 1 2 This parameter is used to select logic block count DIAGNOSTICS Firmware Version Read Firmware Version Device Firmware version will be...

Страница 12: ...g Mode 0 Disable 1 Enable 1 bit DPT 1 003 CW 0 Enable 1 Disable 1 bit DPT 1 006 This object is used to activate lock for all buttons on device 146 161 IN1 IN2 OUT15 IN3 OUT14 IN15 OUT2 OUT1 Logic Bloc...

Страница 13: ...level for Status LEDs can be changed via object Parameter Setting Description BRIGHTNESS LEVELS Bright Level 0 OFF 1 2 3 4 5 6 7 The bright dim level can be set Dark Level 0 OFF 1 2 3 4 5 6 7 The dar...

Страница 14: ...ustom Color Red Yellow Green Cyan Blue Magenta White This parameter is used to select the type of color changes for custom color option Custom Color Object checked unchecked This parameter allows to c...

Страница 15: ...Cleaning Mode deactivation method If No selected Mode can be deactivated via object only If Any Button selected Mode can be deactivated touching long to any button as Long Press Duration below Long P...

Страница 16: ...aetechnology com Page 16 34 4 4 2 Communication Objects No Object Name Function Data Point Type Flags 73 Cleaning Mode 0 Disable 1 Enable 1 bit DPT 1 003 CW 0 Enable 1 Disable 1 bit DPT 1 006 This obj...

Страница 17: ...0 Night 1 Day 1 bit DPT 1 006 This object switches Day and Night information thru com object Device LEDs will be dimmed UP or DOWN If Ambient Light dim is properly configured Parameter Setting Descri...

Страница 18: ...nd Object This parameter is used select the proximity type Presence Timeout 1 10 255 s This parameter defines the timeout for Presence When it is reached the device will be in Absent mode and dimming...

Страница 19: ...Red Yellow Green Cyan Blue Magenta White Custom Push buttons also have status LEDs which can be configured to indicate state of the operation that is configured Parameter Settings Description Name Max...

Страница 20: ...ts button function when button touched Command on Release On Off Toggle No command Selects button function when button released Separate Switch Status Object checked unchecked This parameter defines t...

Страница 21: ...ty Start Stop and Step Wise Dimming Start Stop Type When push button touched and not released and touched duration exceeds Long Touch Duration time Increase 100 When button in Brighter mode or Decreas...

Страница 22: ...01 CRW Button 1 12 Lock T 1 bit DPT 1 001 CRW Parameter Settings Description Dim Operation Darker Short Touch Off Brighter Short Touch On Darker Brighter Short Touch Toggle Select push button dim oper...

Страница 23: ...Product Manual Mona Switch V2 EAE KNX Mona Series MONA Switch R3 0 EAE Technology www eaetechnology com Page 23 34...

Страница 24: ...on Function parameter enables the use of push button 3 different ways Up Long Press moves the blind upwards Short Press operates two different ways short pressed while the blind is moving stops the bl...

Страница 25: ...es the use of push button 3 different ways Up Short Press moves the blind upwards Short Press stops the blind Down Short Press moves the blind downwards Short Press stops the blind Toggle Short Press...

Страница 26: ...bit DPT 1 001 CRW Button 1 12 Lock T 1 bit DPT 1 001 CRW Parameter Settings Description Push Button Function Up Down Toggle See Chapter 4 6 3 Control Type Venetian Blind Roller Shutter button operati...

Страница 27: ...e unsigned 2 byte signed 2 byte float 3 byte color 4 byte unsigned 4 byte signed 4 byte float Data type can be selected individually for each Value field Value 0 1 Visible when Data Type selected as 1...

Страница 28: ...e learn Multi Press Timeout 20 200 x10 ms Double or Triple press action time period Long Press Duration 100ms 500ms 10s Select time period for long press operation Repeat Long Press Telegram checked u...

Страница 29: ...CT 3 9 15 21 27 33 39 45 51 57 63 69 Value 1 byte counter sequence 1 Byte DPT 5 010 CWT Value 1 byte scene activate 1 Byte DPT 18 001 CT Value 1 byte scene learn 1 Byte DPT 18 001 CT Value 2 byte uns...

Страница 30: ...ould be selected in this page Parameter Setting Description I O Config 1 Input 15 Output 2 Input 14 Output 3 Input 13 Output 4 Input 12 Output 5 Input 11 Output 6 Input 10 Output 7 Input 9 Output 8 In...

Страница 31: ...value the result will be True NOT equal If the Input value is NOT equal to ETS written value the result will be True in range If the Input value is in range between written values on ETS the result w...

Страница 32: ...sed as it is NOT Input will be reverted always True Process will always be True regardless to input value always False Process will always be False regardless to input value Initial State False True T...

Страница 33: ...r All 1 s Passthrough It should be used with single operand only Result will be the same as related operand value NOT It should be used with single operand only Result will be reverted according to re...

Страница 34: ...output sending If selected Input or Registered Output has its selected value Send pending telegram after unblocking unchecked checked This function is used to send output state after unblocking Send...