This can be used to confidence check that the unit is triggering on PD.  For example, if the T/cycle 
indicator is in the hundreds, it is likely that the trigger levels have entered the noise floor.  PD is 
nominally between 1 

 30 T/cycle. 

 

3.1.5

 

Controlling the Locator probe from the UltraTEV Plus

2

  

The Locator probe settings can be changed from the UltraTEV Plus

2

.  This can be useful if you are 

using  the  extension  cable  with  the  Locator  probe  fixed  in  place  while  moving  around  with  the 
UltraTEV Plus

2

The highlight around the trigger level indicator shows which sensor is being controlled from the 
UltraTEV Plus

2

.  By default, this is on the UltraTEV Plus

2

 channel, press on the left half of the screen 

to switch control to the Locator probe, indicated by that channel highlighted in red.  Press on the 
right side of the screen to switch control back to the UltraTEV Plus

2

.  

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjusting the Locator probe

 

Adjusting the UltraTEV Plus

2

 

 

3.2

 

 Locator Advanced Mode 

When more detail is required than simply knowing which probe a PD source is closest to, for example 
when there is more than one source, Locator Advanced mode can provide more information than 
the standard Locator mode. 

The controls, trigger levels and basic operation is the same as standard mode, however the UltraTEV 
Plus

2

 display shows a histogram of all received pulses.  This can show not only which probe is closest 

to the source but can be used to locate multiple sources. 

 

Содержание UTL2

Страница 1: ...ating Manual Model Number UTL2 Version V01 03 00 Date July 2021 EA Technology Limited Capenhurst Technology Park Capenhurst Chester CH1 6ES UK Tel 44 0 151 339 4181 http www eatechnology com Registere...

Страница 2: ...EA Technology UltraTEV Locator Probe Operating Manual 2852 MANUL V01 03 00...

Страница 3: ...responsible for the plant should be notified Warnings The UltraTEV Plus and Locator probe are designed for use at ground potential only When testing electrical plant ensure that the metalwork is earth...

Страница 4: ...ltraTEV Plus 3 2 2 Calibrate 4 2 3 Locator probe Function Check 5 3 Operating Instructions 6 3 1 Locator Mode 7 3 2 Locator Advanced Mode 10 4 Technical Specification 13 4 1 General 13 4 2 Environment...

Страница 5: ...tor mode shows which probe detected the signal first indicating the source is closer to that probe In some cases of PD such as when multiple sources are present it can be useful to have more informati...

Страница 6: ...oustic emission from partial discharge activity occurs over the whole acoustic spectra Audible detection is possible but depends on the hearing ability of the individual Using an instrument to detect...

Страница 7: ...e and a 6m extension cable for a maximum location range of 8 metres The Locator probe is plugged directly into the UltraTEV Plus accessory port When the Locator probe is connected the UltraTEV Plus wi...

Страница 8: ...3 00 Page 4 of 19 2 2 Calibrate Each time a Locator probe is connected to an UltraTEV Plus it will need to be calibrated to the UltraTEV Plus With the Locator probe connected to the UltraTEV Plus sele...

Страница 9: ...then toggle on the Locator Test Source and navigate back to the Locator Advanced screen Hold the Locator probe and the UltraTEV Plus2 together TEV plate to TEV plate the Locator Advanced screen will s...

Страница 10: ...r levels and indicators are on the correct sides of the UltraTEV Plus screen When locating across larger distances the Locator probe can be attached to the switchgear using the magnet which is located...

Страница 11: ...For accurate determination of precedence it is important that the trigger levels are set to a suitable value The trigger level sets the threshold of the detection circuits so that no pulses signals b...

Страница 12: ...ottom centre of the screen If the button contains the following text Manual trigger the unit is currently in Auto Trigger Mode In Manual Trigger mode the trigger levels are manually controlled using e...

Страница 13: ...pleted on both probes independently To complete the level function on the Locator probe Press the level button on the Locator probe Press the Locator probe channel level button on the UltraTEV Plus2 s...

Страница 14: ...is being controlled from the UltraTEV Plus2 By default this is on the UltraTEV Plus2 channel press on the left half of the screen to switch control to the Locator probe indicated by that channel highl...

Страница 15: ...peak is on the left hand side of 0 the source is determined to be closer to the Locator probe When the histogram peak is on the right hand side of 0 the source is determined to be closer to the Ultra...

Страница 16: ...or Probe Operating Manual 2852 MANUL V01 03 00 Page 12 of 19 The trigger levels Auto Trigger Manual Trigger modes Level functionality and T Cycle indicators function the same in Locator Advanced mode...

Страница 17: ...njection moulded plastic case Indicators Power indicator LED Controls 3 x Push Buttons Connectors Cable to UltraTEV Plus2 Operating Time 5hrs 4 1 4 Dimensions Size 201mm x 76mm x 34mm Weight 0 36kg 4...

Страница 18: ...id storage in damp and humid conditions and do not subject it to temperature extremes excessive vibration or shocks 7 Warranty Policy What Does the Warranty Policy Cover EA Technology products and acc...

Страница 19: ...EA Technology UltraTEV Locator Probe Operating Manual 2852 MANUL V01 03 00 Page 15 of 19 product support eatechnology com 44 0 151 347 2293...

Страница 20: ...EE EA Technology is a member of an approved compliance scheme as defined by the WEEE directive When an EA Technology product reaches the end of its operational life it must be recycled by a licensed w...

Страница 21: ...Park Chester UK CH1 6ES Tel 44 0 151 339 4181 For details of our international offices and distributors please visit our website www eatechnology com contact us corporate offices Sales Email sales eat...

Страница 22: ...ANUL V01 03 00 Page 18 of 19 13 Record of Changes Date Version Changes June 2018 V01 00 00 First Issue August 2019 V01 01 00 Specification calibration section updated July 2021 V01 02 00 Removed DoC t...

Страница 23: ...ll rights reserved No part of this publication may be reproduced or transmitted in any form or by any means electronic mechanical photocopied recorded or otherwise or stored in any retrieval system of...

Страница 24: ...stribution partners Our Expertise We provide world leading asset management solutions for power plant and networks Our customers include electricity generation transmission and distribution companies...

Отзывы: