background image

 

 

European Safety Systems Ltd.

  Impress House, Mansell Road, Acton, London W3 7QH 

 

 

 

 

 

[email protected]  Tel: +44 (0)208 743 8880 

Document D154-00-251-IS   Issue 6  03-02-2020 

 

 

Sheet 1 of 5 

 

 

 

www.e2s.com  Fax +44 (0)208 740 4200 

 

GNExCP6B-PT,  GNExCP6C-PT  & 
GNExCP6D-PT

 

Manual Call Point – Tool reset  
With Resistor Modules 

For use in Flammable Gas and 
Combustible Dust Atmospheres. 
 
 
 
 

 
 
 

1) 

Introduction 

The GNExCP6B-PT/ GNExCP6C-PT/ GNExCP6D-
PT is a tool reset button manual call point which is 
certified to the European and International Gas and 
Dust  standards.  The  unit  meets  the  requirements 
of  the  ATEX  directive  2014/34/EU  and  IECEx 
scheme. 
 
The  call  point  can  be  used  in  hazardous  areas 
where  potentially  flammable  gas  and  dust 
atmospheres may be present. 
 

2) 

Ratings & Markings 

All  units  have  a  rating  label,  which  carries  the 
following important information: - 
 
Unit Type No.: 
GNExCP6B-PT Manual Call Point 
GNExCP6C-PT Manual Call Point 
GNExCP6D-PT Manual Call Point 
 
 

 
 
Input Voltages: 
48VDC nominal   56VDC Max   0.75A Max 
24VDC nominal   28VDC Max   5.0A Max Resistive 
Load; 3.0A Max Inductive Load 
12VDC nominal   15VDC Max   5.0A Max 
  6VDC nominal     9VDC Max   5.0A Max 
 
Code: 
GNExCP6B-PT 

    GNExCP6C-PT 

Ex db eb mb IIC T4 Gb    Ex db eb mb IIC T4 Gb 
Ex tb IIIC T80ºC Db 

    Ex tb IIIC T75ºC Db 

IP66 

 

    IP66 

–40ºC <= Ta <= +50ºC     –40ºC <= Ta <= +65ºC 
 
GNExCP6D-PT 

     

Ex db eb mb IIC T4 Gb     
Ex tb IIIC T80ºC Db 

     

 

    

IP66 
–40ºC <= Ta <= +70ºC    
 
Certificate No.: 
SIRA 09ATEX3286X 
IECEx SIR 09.0121X 
 
Epsilon x:                           II 2GD 
 
CE Marking 
Notified body No.               2813 
 
Year/Serial No. i.e. 20/1CP6BPT000001   
  

Or         20/1CP6CPT000001   
Or         20/1CP6DPT000001   
 

WARNING - DO NOT OPEN WHEN AN 
EXPLOSIVE ATMOSPHERE MAY BE PRESENT, 
ELECTROSTATIC HAZARD – CLEAN ONLY 
WITH A DAMP CLOTH 
 

3) 

Type Approval Standards 

The  call  point  has  an  EC  Type  examination 
certificate issued by SIRA and have been approved 
to the following standards: - 
 
EN60079-0:2018 / IEC60079-0:2017 
EN60079-1:2014 / IEC60079-1:2014 
EN60079-7:2015 / IEC60079-7:2017 
EN60079-18:2015 / IEC60079-18:2014 
EN60079-31:2014 / IEC60079-31:2013 
 
 
 
 

 
 
The equipment is certified for use in ambient 
temperatures in the range: 
 
GNExCP6B-PT  -40

o

C to +50

o

GNExCP6C-PT  -40

o

C to +65

o

GNExCP6D-PT  -40

o

C to +70

o

and shall not be used outside this range. 
 

4) 

Installation Requirements 

Installation  of  this  equipment  shall  only  be  carried 
out  by  suitably  trained  personnel  in  accordance 
with the applicable code of practice e.g.  
IEC 60079-14/EN 60079-14  
 
Repair of this equipment shall only be carried out 
by the manufacturer or in accordance with the 
applicable code of practice e.g. IEC 60079-19/EN 
60079-19. 
 
The  certification  of  this  equipment  relies  on  the 
following materials used in its construction: 
 
Enclosure:

 

GRP - Glass Reinforced Polyester 

 
Through enclosure mechanism: Plastic Nylon Zytel 
Injection Moulded 
 
Sealing  of  enclosure  and  mechanism:  O-ring 
Acrylonitrile-Butadiene Rubber  
 
Potting Compound of resistors where used: Epoxy 
Resin 
 
If the equipment is likely to come into contact with 
aggressive substances, then  it  is the responsibility 
of the user to take suitable precautions that prevent 
it from being adversely affected, thus ensuring that 
the type of protection is not compromised. 
 
“Aggressive substances” - e.g. acidic liquids, gases 
or solvents that may affect polymeric materials. 
 
“Suitable precautions” - e.g. regular checks as part 
of  routine  inspections  or  establishing  from  the 
material’s  data  sheet  that  it  is  resistant  to  specific 
chemicals. 
 
Leads connected to the terminals shall be insulated 
for the appropriate voltage and this insulation shall 
extend  to  within  1mm  of  the  metal  of  the  terminal 
throat.  They  shall  only  be  installed  and  wired  with 
cable in an ambient temperature of -10°C to +80°C 

 
All  terminal  screws,  used  or  unused,  shall  be 
tightened down to between 0.5 Nm and 0.7 Nm 
 
Refer  to  certificates  SIRA  09ATEX3286X  and 
IECEx SIR 09.0121X for special conditions of safe 
use. 
 
Under extreme conditions the unit may generate an 
ignition-capable  level  of  electrostatic  charges.  The 
unit must not be installed in a location where it may 
be  subjected  to  external  conditions  (such  as  high-
pressure  steam)  which  may  cause  a  build-up  of 
electrostatic  charges  on  non-conducting  surfaces. 
Cleaning of the unit must only be carried out with a 
damp cloth. 
 

5) 

Call Point Location and Mounting 

The location of the call point should enable ease of 
access  for  operation  and  testing.  The  unit  should 
be  mounted  using  the  4  off  fixing  holes  which  will 
accept up to M4 sized fixings. 
 

 

 

 

 

 

 

 

View of base unit showing fixing centres (in mm). 
 
To  gain  access  to the mounting  holes  in  the  base 
the front cover must be removed.  
This  is  achieved  by  removing  the  4  off  M4  cap 
head bolts holding on the cover. 
 
 
 
 
 
 
 
 

INSTRUCTION MANUAL  

GNExCP6B-PT, GNExCP6C-PT & GNExCP6D-PT Tool Reset Manual Call Point 

For use in Flammable Gas and Dust Atmospheres 