cause a built-up of electrostatic charges on non-conducting 
surfaces. 
 
The equipment has not been assessed as a safety-related 
device (as referred to by Directive 94/9/EC Annex II, clause 
1.5). 
 
To maintain the ingress protection rating and mode of 
protection, the cable entries must be fitted with suitably rated 
ATEX / IECEx certified cable glands and/or suitably rated 
ATEX / IECEx certified blanking devices during installation 
according to EN / IEC60079-14. If a high IP (Ingress 
Protection) rating is required then a suitable sealing washer 
must be fitted under the cable gland. 
 
For use in explosive gas atmospheres, a minimum ingress 
protection rating of IP54 must be maintained. For use in 
explosive dust atmospheres, a minimum ingress protection 
rating of IP64 must be maintained. 
 
The enclosure is accessed by removing the 4 M4 Hex cover 
bolts fastening the enclosure. Do not open other joints of the 
enclosure for installation, service and maintenance. 
 
Connections are to be made into the terminal blocks using 
solid wire, sizes 0.5-4mm

2

 or stranded wire, sizes 0.5-2.5 mm

2

Wire insulation needs to be stripped 8mm. Stranded wires may 
be fitted securely with crimped ferrules. Terminal screws need 
to be tightened down with a tightening torque of 0.45 Nm. 
 
Earthing connections should be made to the Internal Earth 
terminal on the PCBA. The internal earth bonding wire 
connects the PCBA earth terminal to the internal earth terminal 
in the enclosure. 
 
Check that the earth bonding wire between the two enclosure 
parts is secure and the ‘O’ ring seal is in place before closing. 

 
4.2 Maintenance, Repair and Overhaul 

 
Maintenance, repair and overhaul of the equipment should only 
be carried out by suitably qualified personnel in accordance 
with the current relevant standards: 
 
EN60079-19 / IEC60079-19  

Explosive atmospheres - 

Equipment repair, overhaul and reclamation 
EN 60079-17/ IEC60079-17 

Explosive atmospheres - 

Electrical installations inspection and maintenance 
 
Units must not be opened while an explosive atmosphere is 
present. 
 
If opening the unit during maintenance operations a clean 
environment must be maintained and any dust layer removed 
prior to opening the unit. 
 
Electrostatic charging hazard - Clean only with a damp cloth 

__________________________________________________________________________________________________________________ 