15. Tone Table 

45

Tone 34

Tone 38

0  0  1  1  0  1

1KHz 1s on, 1s off Intermittent

PFEER Gen. Alarm

Tone 5

Tone 2

1  1  0  1  0  1

Motor Siren - slow rise to 2400Hz

44

Tone 5

Tone 2

0  1  0  1  0  1

1200Hz Continuous

43

Tone 5

Tone 2

1  0  0  1  0  1

Motor Siren - slow rise to 800Hz

42

Tone 5

Tone 2

0  0  0  1  0  1

Motor Siren - slow rise to 1200Hz

41

Tone 27

Tone 31

1  1  1  0  0  1

544Hz (100mS)/440Hz (400mS)
- NF S 32-001

40

Tone 17

Tone 23

0  1  1  0  0  1

800Hz 0.25 sec on, 1 sec off Intermittent

39

Tone 45

Tone 34

1  0  1  0  0  1

2000Hz Continuous

38

Tone 45

Tone 9

0  0  1  0  0  1

1000Hz Continuous - 

PFEER Toxic Gas

37

Tone 5

Tone 35

1  1  0  0  0  1

500-1200Hz 3.75 sec /0.25 sec 
Australian Evac.

36

Tone 5

Tone 36

0  1  0  0  0  1

420Hz @ 0.625 Sec Australian Alert

35

Tone 45

Tone 38

1  0  0  0  0  1

1000 & 2000Hz @ 0.5 sec 

Aletrnating - Signapore

34

Tone 5

Tone 2

0  0  0  0  0  1

745Hz @ 1Hz Intermittent

33

Tone 15

Tone 26

1  1  1  1  1  0

Two tone chime

32

Tone 5

Tone 26

0  1  1  1  1  0

660/1200Hz @ 1Hz Sweeping

31

Tone 5

Tone 2

1  0  1  1  1  0

300Hz Continuous

30

Tone 5

Tone 7

0  0  1  1  1  0

800/1000Hz @ 7Hz Sweeping

29

Tone 5

Tone 2

1  1  0  1  1  0

440Hz Continuous

28

Tone 5

Tone 26

0  1  0  1  1  0

554Hz Continuous

27

Tone 15

Tone 2

1  0  0  1  1  0

Bell

26

Tone 5

Tone 29

0  0  0  1  1  0

2400/2900Hz @ 50Hz Sweeping

25

Tone 5

Tone 29

1  1  1  0  1  0

800/1000Hz @ 50Hz Sweeping

24

Tone 5

Tone 6

0  1  1  0  1  0

800Hz @ 2Hz Intermittent

23

Tone 5

Tone 2

1  0  1  0  1  0

544Hz @ 0.875 sec Intermittent

22

Tone 5

Tone 2

0  0  1  0  1  0

554Hz/440Hz @ 1Hz Alternating

21

Tone 5

Tone 2

1  1  0  0  1  0

660Hz Continuous

20

Tone 5

Tone 2

0  1  0  0  1  0

1.4KHz - 1.6KHz 1s, 1.6KHz - 1.4 
KHz 0.5s - NFC48-265

19

Tone 5

Tone 2

1  0  0  0  1  0

660Hz 1.8 sec on, 1.8 sec off Intermittent

18

Tone 27

Tone 2

0  0  0  0  1  0

544Hz (100mS)/440 Hz (400m/S)
- NF S 32-001

17

Tone 5

Tone 18

1  1  1  1  0  0

660Hz 150mS on, 150mS off Intermittent

16

Tone 5

Tone 2

0  1  1  1  0  0

800Hz Continuous

15

Tone 5

Tone 4

1  0  1  1  0  0

800Hz 0.25 sec on, 1 sec off Intermittent

14

Tone 5

Tone 15

0  0  1  1  0  0

2400Hz @ 1Hz Intermittent

13

Tone 5

Tone 4

1  1  0  1  0  0

800/1000Hz @ 0.875Hz Alternating

12

Tone 5

Tone 2

0  1  0  1  0  0

1000Hz @ 1Hz Intermittent

11

Tone 5

Tone 7

1  0  0  1  0  0

2400/2900Hz @ 2Hz Alternating

10

Tone 2

Tone 15

0  0  0  1  0  0

1200/500Hz @ 1Hz - DIN 

PFEER P.T.A.P.

9

Tone 5

Tone 2

1  1  1  0  0  0

500/1200/500Hz @ 0.3Hz Sweeping

8

Tone 5

Tone 10

0  1  1  0  0  0

2400/2900Hz @ 1Hz Sweeping

7

Tone 5

Tone 7

1  0  1  0  0  0

2400/2900Hz @ 7Hz Sweeping

6

Tone 20

Tone 3

0  0  1  0  0  0

2400Hz Continuous

5

Tone 5

Tone 6

1  1  0  0  0  0

800/1000Hz @ 1Hz Sweeping

4

Tone 5

Tone 2

0  1  0  0  0  0

500/1200Hz @ 0.3Hz sec
Slow Whoop

3

Tone 5

Tone 17

1  0  0  0  0  0

800/1000Hz @ 0.25 sec Alternating

2

1  2  3  4  5  6

Tone 5

Tone 2

0  0  0  0  0  0

340Hz Continuous

1

Stage 3

Stage 2

Switch

Frequency Description

Stage 1

 

Fig. 13 Sounder Dip Switch 

 

1=ON; 0=OFF 
Example shown: 100000 = Tone 2 (Default setting) 

 

Содержание E2xC1LD2R

Страница 1: ...ating Marking Information 3 1 ATEX IECEx UKEx certification The E2xC1LD2 combined alarm horn and LED beacon complies with the following standards Standards EN IEC 60079 0 2018 IEC60079 0 2017 Ed 7 Exp...

Страница 2: ...IC Dc T105 C Ta 20 C to 55 C Ex tc IIIC Dc T90 C Ta 20 C to 40 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Groups Category and Temperature Classificati...

Страница 3: ...e E2x combined sounder beacon should be secured to any flat surface using the three 7mm fixing holes on the stainless steel U shaped mounting bracket See Figure 1 The required angle can be achieved by...

Страница 4: ...tional area of 2 5mm Strip wires to 8mm Wires may also be fitted using ferrules Terminal screws on the sounder PCBA need to be tightened down with a tightening torque of 0 45 Nm 4 Lb in Terminal screw...

Страница 5: ...ing Independent Beacon and Sounder Operation Only The resistor must be connected directly across the ve and ve terminals as shown in the following drawing Form the resistor legs as shown in Fig 9a rem...

Страница 6: ...he equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and rec...

Страница 7: ...400 2900Hz 50Hz Sweeping 25 Tone 5 Tone 29 1 1 1 0 1 0 800 1000Hz 50Hz Sweeping 24 Tone 5 Tone 6 0 1 1 0 1 0 800Hz 2Hz Intermittent 23 Tone 5 Tone 2 1 0 1 0 1 0 544Hz 0 875 sec Intermittent 22 Tone 5...

Страница 8: ...HOWN ABOVE DRAWING TO BS8888 2000 GEOMETRIC TOLERANCES TO ISO1101 1983 LINEAR DIMENSIONAL TOLS ANGULAR DIMENSIONAL TOLS 05 08 2020 05 08 2020 DC E2XC1LD2 UNITS Line Monitoring Stage 1 Apply power to S...

Страница 9: ...Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standar...

Страница 10: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Страница 11: ...on Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 6007...

Страница 12: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Отзывы: