E2S E2xBL2 Скачать руководство пользователя страница 4

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D209-00-401-IS

 

Issue 1

 

20-08-22

 

 

Sheet 4 of 5

 

 

    N        E 

       

   

     + +        -  -      S2   S3 

Ambient Temp. 

40ºC 

45ºC 

50ºC 

55ºC 

Min. Rating of cables 
and cable glands 

90ºC 

95ºC 

100ºC  105ºC 

 

If  a  high  IP  (Ingress  Protection)  rating  is  required  then  a 
suitable sealing washer must be fitted under the cable glands 
or blanking plugs.  

 

For  use  in  explosive  dust  atmospheres,  a  minimum  ingress 
protection rating of IP6X must be maintained. 
 
For  use  in  explosive  gas  atmospheres,  a  minimum  ingress 
protection rating of IP54 must be maintained. 

 

8)  Cable Connections 

 

Electrical connections are to be made into the terminal blocks 
on  the  PCBA  located  in the  enclosure. See section 6  of  this 
manual for access to the enclosure.  

 

Wires  having  a  cross  sectional  area  between  0.5  mm²  to 
2.5mm²  can  be  connected  to  each  terminal  way.  If  an  input 
and  output  wire  is  required  the  2-off  Live/Neutral  or  +/- 
terminals  can  be  used.  If  fitting  2-off  wires  to  one  terminal 
way  the  sum  of  the  2-off  wires  must  be  a  maximum  cross 
sectional area of 2.5mm². Strip wires to 8mm. Wires may also 
be fitted using ferrules. Terminal screws need to be tightened 
down  with  a  tightening  torque  of  0.56  Nm  /  5  Lb-in.  When 
connecting wires to the terminals great care should be taken 
to dress the wires so that when the cover is inserted into the 
chamber  the  wires  do  not  exert  excess  pressure  on  the 
terminal  blocks.  This  is  particularly  important  when  using 
cables with large cross sectional areas such as 2.5mm². 
 

9)  AC Wiring 

 

3-off  2-way  terminal  blocks  are  provided  on  the  AC  beacon 
for power. There are 2-off Live, 2-off Neutral and 2-off Earth 
terminals in total. 

 

 

 

 

 

Fig. 4 E2XBL2 AC Terminals 

 

Refer  to  schematic  document  D209-06-401  for  further  detail 
on terminal connections. 

 
 
 
 
 

10) DC Wiring 

 

3-off  2-way  terminal  blocks  are  provided  on  the  AC  beacon 
for power. There are 2-off +ve, 2-off –ve, 1-off Stage 2 and 1-
-off stage 3 terminals in total. 
 

 
 

 

 

Fig. 6 E2XBL2 DC Terminals 

 

For further detail, refer to schematic document D209-06-401.  

 
10.2 

Line Monitoring 

 

On  E2xBL2  DC  units,  DC  reverse  line  monitoring  can  be 
used if required. All DC beacons have a blocking diode fitted 
in  their  supply  input  lines.  An  end  of line  monitoring  resistor 
can  be  connected  across  the  +ve  and  –ve  terminals.  If  an 
end of line resistor is used it must have the following values: 
 

 

Min. Resistance 

Min. Power 

24V DC 

3.9KΩ 

0.5W 

1KΩ 

2W 

48V DC 

15KΩ 

0.5W 

3.9KΩ 

2W 

 
The resistor must be connected directly across the +ve and  
-ve terminals as shown in the following drawing. Form the 
resistor legs as shown in Fig. 8a, remove the +ve and –ve 
terminal plugs and fit the resistor across the two terminal 
plugs before refitting them to the PCBA as shown in Fig. 8b. 
A spacing of at least 1/16” (1.58mm) must be provided 
through air and over surfaces between uninsulated live parts. 

 

 

Fig. 8a End of Line Resistor Forming 

Содержание E2xBL2

Страница 1: ...5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER 3 Rating Marking Information 3 1 ATEX IECEx UKEx certification The E2xBL2 LED beacon complies with the following standards Stan...

Страница 2: ...to 55 C Installation must be carried out in compliance with the Canadian Electric Code 4 Zones Gas Groups Category and Temperature Classification When connected to an approved system the E2XBL2 LED be...

Страница 3: ...wo large bracket screws in the side of the unit which allow adjustment of the beacon in steps of 18 On completion of the installation the two large bracket adjustment screws on the side of the unit mu...

Страница 4: ...when the cover is inserted into the chamber the wires do not exert excess pressure on the terminal blocks This is particularly important when using cables with large cross sectional areas such as 2 5...

Страница 5: ...nt should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation E...

Страница 6: ...IGHT Kg SURFACE FINISH MATERIAL ALTERNATIVE MATERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D209 06 401...

Страница 7: ...Assurance Notification Module D SIRA 05 ATEX M342 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standar...

Страница 8: ...e and Place of Issue London 22 08 2022 EU Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Страница 9: ...on Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 3G Ex ec IIC T4 T3 T2 Gc II 3D Ex tc IIIC 85 C 120 C Dc IP6X Dust Protection to EN60079 0 EN60079 31 Standards applied EN IEC 6007...

Страница 10: ...Place of Issue London 22 08 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the marke...

Отзывы: