E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH [email protected] e2s.com D218-00-351-IS Issue 1 10/05/2021
S1 - LED Flash Mode Settings (AC & DC)
The Flash Mode Dip Switch can be changed to set the desired
flash pattern
Flash Mode DIP Switch – Shown with 1-OFF, 2-ON, 3-OFF (0 1 0),
This denotes Flash mode 1Hz. For further flash modes refer to
table:
Switch
Flash Mode
0 0 0
Steady on
1 0 0
Blinking
0 1 0
Flashing 1Hz
*
1 1 0
Flashing 1.5Hz
*
0 0 1
Flashing - Double Strike
1 0 1
Flashing - Triple Strike
0 1 1
Flashing 2Hz
*
1 1 1
Flashing - Temporal
1 2 3
ON
•
All models are approved for use as Audible Signal and Visual Appliance
for use as General Signaling: UL464A & CSA C22.2 No 205-17
•
Type 4 / 4X / 3R / 13, IP66
•
-
40°C to +66°C / -40°C to +151°F
General Signaling Canada:
DL105HDC: -40°C to +55°C / -40°F to +131°F
DL105HAC: -40°C to +40°C / -40°F to +104°F
•
To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
•
Mounting - Units can be mounted using the 2-off 10 x 7mm obround holes in the mounting lugs.
•
EOL Monitoring (DC Only): End of Line Devices may be fitted between the +ve & -ve terminals of the PCBA. Please ensure that the device
legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short. Refer to the compatible
control panel specification for EOL device values and ratings
Model
Nominal
Voltage
Voltage Range
Nominal Operating Current*
Max Operating RMS
#
Beacon
Sounder
Beacon
Sounder
DL105HDC024
12V dc
10-14Vdc
79.5mA
17mA
168mA
125mA
24V dc
16-33Vdc
87mA
33.5mA
183mA
DL105HDC048
48V dc
48-60Vdc
60mA
113mA
115mA
DL105HAC230
115V ac
48 - 260Vac
50/60Hz
34mA
25mA
42.5mA
166mA
230V ac
19mA
17mA
*Nominal Voltage, 1Hz Flash Pattern & Tone 12;
#
Worst-case input voltage and worst case flash pattern
Attention: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70 or CSA 22.1 Canadian Electrical
Code, Part I, Safety Standard for Electrical Installations, Section 32. / L'installation doit exclusivement être réalisée par du personnel qualifié, conformé
ment au code national d'électricité américain, NFPA 70 ou CSA 22.1 Code canadien de l'électricité, première partie, norme de sécurité relative aux
installations électriques, Section 32