European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)208 740 4200 
Document No. D190-00-301-IS-SC     Issue:  8                        24-04-19               Sheet 4 of 8 

 

4) 

Installation 

 

4.1 Safe Installation Requirements 
 

The  product  must  only  be  installed  by  suitably  qualified 
personnel  in  accordance  with  the  latest  issues  of  the  relevant 
standards. 
 
The  installation  of  the  units  must  also  be  in  accordance  with 
the  NEC  /  CEC  and  any  local  regulations  and  should  only  be 
carried  out  by  a  competent  electrical  engineer  who  has  the 
necessary training. 

 
4.2 Specific Conditions of Use 
 

The  Equipment  must  not  be  installed  with  the  horn  facing 
upwards of horizontal. 

 

To  maintain  the  ingress  protection  rating  and  mode  of 
protection,  the  cable  entries  must  be  fitted  with  suitably  rated 
cable  entry  and/or  blanking  devices  during  installation.  If 
conduit  is  used  for  installation,  seal  conduit  within  18  inches 
from the enclosure. 
If entries are fitted with adaptors they must be suitably rated for 
the application. Fitting of blanking elements into adaptors is not 
permitted. 
 
If  a  high  IP  (Ingress  Protection)  rating  is  required  then  a 
suitable  sealing  washer  or  O-ring  must  be  fitted  under  any 
cable gland or blanking device with metric threads. 

 

Only  the  explosionproof  cover  is  to  be  used  for  access  to  the 
enclosure for installation, service and maintenance. 
 
Connections  are  to  be  made  into  the  terminal  blocks  using 
solid  or  stranded  wire,  sizes  0.5-2.5mm

2

  /  AWG  20-14.  Wire 

insulation  needs  to  be  stripped  6-7mm.  Wires  may  be  fitted 
securely  with  crimped  ferrules.  Terminal  screws  need  to  be 
tightened down with a tightening torque of 0.4 Nm / 3.5 Lb-in. 
 
Earthing  connections  should  be  made  to  the  Internal  Earth 
terminal  in  the  explosionproof  chamber  or  the  external  earth 
stud. 

 

Check that the ‘O’ ring seal is in place before replacing the 
explosionproof cover. 
 
If temperature exceeds 70°C at entry or 80°C at branching 
point use suitable rated cable and cable glands:

 

 
 
 
 

 
 
 
4.3 Mounting 

 
 

 
 

 
 
 
 
 
 
 

Fig. 1 Fixing locations. 

 
The D1x Alarm Horn may be secured to any flat surface using 
the  three  7mm  fixing  holes.  The  enclosure  provides  IP66 
protection  and  is  suitable  for  installation  in  exterior  locations 
providing  it  is  positioned  so  that  water  cannot  collect  in  the 
horn, and the cable entry is sealed. 

 
4.4 Installation procedure 
 

a.  Secure the D1x alarm horn to a flat surface via the  

three 7mm fixing holes in the mounting bracket. 

 

b.  Remove  the  explosionproof  cover  of  the  alarm  horn  by 

unscrewing  it,  taking  care  not  to  damage  the 

explosionproof threads in  the process  (Refer to section 

6).  

 

c.  Fit  an  M20/NPT  suitably  rated  cable  gland  or  conduit 

entry into the hole in the enclosure and connect the field 

wiring to the appropriate alarm horn terminals as shown 

in fig. 6 (AC) or fig 8. (DC). The power supply terminals 

are  duplicated  so  that  units  may  be  connected  in 

parallel. An end of line monitoring resistor may be fitted 

to  DC  units  only  (see  section  14).  If  the  second  and 

third  M20/NPT  entries  are  not  used,  suitably  rated 

stopping plugs must always be fitted.  

 

d.    Replace  the  explosionproof  cover  of  the  loudspeaker, 

taking  care  not  to  damage  the  explosionproof  threads. 

Tighten fully. 

 

4.5 Hornless Variants 

 

The D1x Sounder is also available as a variant with no 
horn  fitted  in  the  factory.  The  Horn  threaded  nose 
portion  has  a  fitment  thread  of  1-

3/8”  –  18  UNF  (to 

BS1580 or ANSI B1.1). The customer is responsible for 
sourcing and correctly fitting a suitable horn that meets 
all of the relevant safety requirements. 
 

5)  Access to Explosionproof Enclosure 

 
In  order  to  connect  the  electrical  supply  cables  to  the  alarm 
horn it is necessary to remove the explosionproof cover to gain 
access  to  the  explosionproof  chamber.  This  can  be  achieved 
by  unscrewing  the  explosionproof  cover,  taking  extreme  care 
not to damage the explosionproof threads in the process.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 2 Accessing the Explosionproof Enclosure. 

On 

completion 

of 

the  cable 

wiring 

installation 

the 

explosionproof threads should be inspected to ensure that they 
are  clean  and  that  they  have  not  been  damaged  during 
installation. Also check that the ‘O’ ring seal is in place, on the 
thread  diameter  in  contact  with  the  flat  face  of  the 
explosionproof cover. When replacing the explosionproof cover 
ensure that it is tightened fully. 
 
 
 
 
 

 

Max. ambient 
temperature 

70ºC 

75ºC 

Req. Cable / 
Cable Gland 
Rating: 

D1xC1X05DC024, 
D1xC1X05AC115 

 

 

85ºC 

D1xC1X05AC230

 

85°c 

90ºC 

External Earth 
Assembly 

Explosionproof 
cover 

Stopping plug 

(Appropriate 
cable glands to 
be customer 
supplied) 

Содержание D1xC2 Series

Страница 1: ...S DE 18 POUCES QUIPEMENT NE DOIT PAS TRE INSTALL AVEC LE KLAXON TOURN E VERS LE HAUT DE HORIZONTAL NE PAS OUVRIR UN PRESENCE D ATMOSPHERE EXPLOSIVE NE PAS OUVRIR ENERGIE DANGER POTENTIEL CHARGE LECTRO...

Страница 2: ...h the following standards for hazardous locations EN60079 0 2018 IEC60079 0 ed 7 0 2017 EN60079 1 2014 IEC60079 1 ed 7 0 2014 The D1xC1X05DC024 Combined Alarm Horns are rated as follows Ex db IIC T4 G...

Страница 3: ...0Vac 60Hz D1xC2X05 DC024 24Vdc 924 mA 323 mA 1247 mA 20 28Vdc 1477 mA 20Vdc D1xC2X05 AC115 115Vac 60Hz 268 mA 130 mA 398 mA 110 120Vac 50 60Hz 446 mA 110Vac 60Hz D1xC2X05 AC230 230Vac 50Hz 159 mA 79 m...

Страница 4: ...ee 7mm fixing holes The enclosure provides IP66 protection and is suitable for installation in exterior locations providing it is positioned so that water cannot collect in the horn and the cable entr...

Страница 5: ...s on first and second stages and which tones are available for the third and fourth stages dependent on the Stage 1 DIP switch setting 8 Stage Switching Polarity DC Units Only The D1xC2 and D1xC1 DC a...

Страница 6: ...itch 1 alters stage 4 tone Fig 8 DC Terminals 11 Earthing The unit has both a primary internal and secondary external earth fixing point Internal earth connections should be made to the internal Earth...

Страница 7: ...9 34 1 10 1000Hz 1s on 1s off x7 7s on 1s off IMO Code 1a 1 0 0 1 0 0 10 34 1 11 420Hz 0 5s on 0 5s off x3 1s gap ISO 8201 Temporal Pattern 0 1 0 1 0 0 11 1 8 12 1000Hz 0 5s on 0 5s off x3 1s gap ISO...

Страница 8: ...0 1 48 24 12 49 560 1055Hz 0 18Hz Sweeping 0 0 0 0 1 1 49 24 12 50 560 1055Hz 3 3Hz Sweeping 1 0 0 0 1 1 50 24 12 51 600 1250Hz 0 125Hz Sweeping 0 1 0 0 1 1 51 24 12 52 660 1200Hz 1Hz Sweeping 1 1 0 0...

Отзывы: