background image

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, London, W3 7QH, UK                [email protected]            Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 

Document No. D191-00-251-IS-SC_Issue_E  

27/04/2018  

Sheet 3 of 7

 

* Flash rates Public Mode Fire 

# nominal rms current at nominal voltage 

## max. rms current at worst-case voltage in voltage range.  

 
 

Surge Current for Fire Alarm use per UL Listing 
 

Surge Currents 

Model 

Nom. 

Voltage 

Voltage 

Range 

Flash Rate Setting 

Init, Peak Surge 

Current (A)

 

Init. RMS Surge 

Current (mA)

 

D1xB2XH1DC024

 

24Vdc 

20-28Vdc 

1Hz (60fpm) 

1150 mA 

697 mA 

1.5Hz (90fpm) 

1100 mA 

742 mA 

1.33Hz (80fpm) 

1090 mA 

680 mA 

Double flash

 

1070 mA 

639 mA 

D1xB2XH2DC024

 

24Vdc 

20-28Vdc

 

1Hz (60fpm) 

1590 mA 

1180 mA 

1.5Hz (90fpm) 

1590 mA 

1120 mA 

1.33Hz (80fpm)

 

1710 mA 

1130 mA 

Double flash 

1650 mA 

1200 mA 

Surge current given at worst case voltage 

 
 

Installation 

There are no restrictions on unit orientation. 

 

Safe Installation Requirements 

 

 

To maintain the ingress protection rating and mode of protection, the cable entries must be fitted with suitably rated cable 

entry and/or blanking devices during installation. If conduit is used for installation, seal conduit within 18 inches from the 

enclosure. 

If entries are fitted with adaptors they must be suitably rated for the application. Fitting of blanking elements into adaptors 

is not permitted. 

 

Connections are to be made into the terminal blocks using solid or stranded wire, sizes 0.5-2.5mm2 / AWG 20-14. Wire 

insulation needs to be stripped 6-7mm. Wires may be fitted securely with crimped ferrules. Terminal screws need to be 

tightened down with a tightening torque of 0.4 Nm / 3.5 Lb-in. 

 

Earthing connections should be made to the Internal Earth terminal in the explosionproof chamber or the external earth 

stud. 

 

Check that the ‘O’ ring seal is in place before replacing the explosionproof cover. 

 

 

Selection of Cable, Cable Glands, Blanking Elements & Adapters

 

 

 

When selecting  the  cable size,  consideration must  be  given  to  the  input current that  each  unit  draws  (see  Table), the  number  of 

beacons on the line and the length of the cable runs. The cable size selected must have the necessary capacity to provide the input 

current to all of the sounders connected to the line.  

 
When selecting the cable size consideration must be given to the voltage drop over the length of the cable run to ensure the min. input 

voltage at the point of use (voltage range) 

 

The voltage drop depends on: 

The total current draw if the devices installed on this cable run 

The wire size and total length of the cable run, determining the total resistance of this cable run 

The minimum output voltage supplied by the power supply 

 
The voltage drop and input voltage at the point of use can be calculated. 

 

Total Wire resistance =  

Wire resistance / 1000ft x length of cable run x 2 
 

Содержание D1xB2XH1

Страница 1: ...1 AEx db IIC T5 Ta 55 C to 80 C Class I Zone 1 AEx db IIC T6 Ta 55 C to 60 C Zone 21 AEx tb IIIC 107 CTa 55 C to 80 C Class Zone ratings for Canada Ex db IIC T5 Ta 55 C to 80 C Ex db IIC T6 Ta 55 C to 60 C Ex tb IIIC 107 C Ta 55 C to 80 C D1xB2XH2 21J Xenon Beacon Class Division Ratings for US Class I Div 1 Group ABCD T4A Ta 55 C to 80 C Class I Div 1 Group ABCD T5 Ta 55 C to 55 C Class I Div 1 Gr...

Страница 2: ...VOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER NE PAS PEINTURER POUR RÉDUIRE LE RISQUE D INFLAMMATION DES ATMOSPHÈRES DANGEREUSES LES CONDUITES DE CONDUIT DOIVENT AVOIR UN RACCORD D ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18 POUCES DE L ENFERMEMENT POUR PRÉVENIR L INFLAMMATION DES ATMOSPHÈRES DES GROUPES A B C ET D VOIR L INSTRUCTION POUR LA COMPATIBILITÉ CHIMIQUE Type Approval Standards UL 1203 C...

Страница 3: ...y must be suitably rated for the application Fitting of blanking elements into adaptors is not permitted Connections are to be made into the terminal blocks using solid or stranded wire sizes 0 5 2 5mm2 AWG 20 14 Wire insulation needs to be stripped 6 7mm Wires may be fitted securely with crimped ferrules Terminal screws need to be tightened down with a tightening torque of 0 4 Nm 3 5 Lb in Earthi...

Страница 4: ... drop Flash Rate Settings The D1xB2XH1 D1xB2XH2 beacons can produce different flash patterns as shown in Table The flash patterns are selected by operation of the flash setting DIP switch on the PCBA setting permitted for use as public mode fire alarm device Fig 8 Dip Switch 1 ON 0 OFF Example shown 10 Flashing 1 5Hz Default setting is 00 1Hz Line Monitoring All DC units have a blocking diode fitt...

Страница 5: ...Intensity cd at 1 5Hz flash rate 90FPM Intensity cd at 1 33Hz flash rate 80FPM 0 100 86 37 51 65 58 57 5 25 90 77 73 46 49 52 71 30 45 75 64 78 38 74 43 93 50 55 47 50 28 41 32 21 55 45 38 87 23 24 26 36 60 40 34 55 20 66 23 43 65 35 30 23 18 08 20 50 70 35 30 23 18 08 20 50 75 30 25 91 15 50 17 57 80 30 25 91 15 50 17 57 85 25 21 59 12 91 14 64 90 25 21 59 12 91 14 64 Compound 45 to Right 24 20 7...

Страница 6: ... cd at 1 33Hz flash rate 80FPM 0 100 86 37 51 65 58 57 5 30 90 77 73 46 49 52 71 35 65 56 14 33 57 38 07 40 46 39 73 23 76 26 94 45 34 29 37 17 56 19 91 50 27 23 32 13 95 15 81 55 22 19 00 11 36 12 89 60 18 15 55 9 30 10 54 65 16 13 82 8 26 9 37 70 15 12 96 7 75 8 79 75 13 11 23 6 71 7 61 80 90 12 10 36 6 20 7 03 D1xB2XH2 Vertical Light Output Dispersion for Wall Mounting Viewing Angle Of Rating I...

Страница 7: ...ate 60FPM Intensity cd at 1 5Hz flash rate 90FPM Intensity cd at 1 33Hz flash rate 80FPM 0 100 86 37 51 65 58 57 5 25 90 77 73 46 49 52 71 30 45 75 64 78 38 74 43 93 50 55 47 50 28 41 32 21 55 45 38 87 23 24 26 36 60 40 34 55 20 66 23 43 65 35 30 23 18 08 20 50 70 35 30 23 18 08 20 50 75 30 25 91 15 50 17 57 80 30 25 91 15 50 17 57 85 25 21 59 12 91 14 64 90 25 21 59 12 91 14 64 D1xB2XH2 Vertical ...

Отзывы: