background image

 

E2S Warning Signals

      Impress House, Mansell Road, Acton, London W3 7QH

 

www.e2s.com

 

Tel: +44 (0)208 743 8880

 

Document No. D191-00-621-IS

 

Issue 1

 

27-10-22

 

 

Sheet 9 of 15

 

 

The SIL 2 unit will also check for signal polarity. 
 
If a fault is found the SIL 2 unit will go into 

Fault mode

 
If power is disrupted the SIL 2 unit will go into 

Fault mode

, in 

fault mode the Power relay RLY1-1 will close whilst SIL 2 relay 
RLY1-2 will become an open circuit between terminals 1 & 2. 
 

 

Fault modes

 - The fault modes listed in sections 15-1 & 15-2 

will result in a change of state for relays RLY1-1 and RLY1-2. 
 
In fault mode the  Power relay RLY1-1 will close whilst SIL 2 
relay RLY1-2 will become open be circuit between terminals 1 
& 2. 

 

15-1 Beacon Failure 

 

 

Flash Failure 

 No flash detected. 

 

Beacon  Controller  Failure 

  No  flash  trigger  pulse 

detected. 

 

Flash Rate Failure 

 Regular 1 Hz flash cycle erratic. 

 

15-2 Power Failure / SIL 2 Failure 

 

 

SIL  2  Controller  Failure 

  Internal  function  and 

system checking flags fault. 

 

Rapid  Power  Cycling 

  System  indicates  power 

instability. 

 

Total Power Failure.  

 
It is possible to reset these faults if they were transitory. 
 
Resetting Failure (by power cycling) - It is possible that the SIL 
2 unit can be reset by powering the unit off for a period greater 
than 20 seconds.  On restarting the unit  and running through 
the commissioning cycle the fault may clear. 
 
Resetting Failure (by Hard Reset) - It is possible that the SIL 2 
unit  can  be  reset  by  hard  resetting  the  unit  using  the  reset 
jumper within the unit (see section 17-4) on hard resetting. On 
restarting  the  unit  and  running  through  the  commissioning 
cycle, the fault may clear. It is necessary to run the test function 
cycle again to see if the fault is still evident. 
 
If the hard reset process does not correct the latched fault the 
alarm horn sounder may require further investigation, please 
contact your local E2S representative. 
 
 
 
 
 
 
 
 
 
 
 
 

Commissioning  System  -  Functional  start-up  of  System 
(Normally in reverse polarity mode) 

 
When Commissioning system the power must not be disrupted 

to the SIL 2 Unit within the unit’s 

initialization cycle which is 

seconds

 
Once past this period the SIL 2 system is fully operational and 
will be in monitoring the beacon and power in Standby mode. 
 
The relay RLY1-2 on the SIL 2 unit will only remain open for a 
maximum of 1 second on commissioning start-up. RLY1-2 will 
subsequently  close  contacts  1  &  2  indicating  healthy 
operation. Contact 1 & 2 will only remain open in the event of 
a fault or a loss of power. 
 

System Testing (Active Mode normal polarity) 
 

The SIL 2 system will remain monitoring the power in standby 
mode until the polarity is changed to normal mode to enable 
an active system for beacon functional testing. 
 

Important

:  -  The  polarity  must  be  held  in  active  mode  for  a 

period in excess of 

15 seconds

 to ensure a full system check 

is performed. 
 
Once  the  test  period  has  been  completed  the  unit  can  be 
switched back to standby mode by reversing the polarity. 
 
If  no  faults  have  been  found  during  the  test  the  relays  will 
remain in steady state. 
 
The SIL 2 unit will continue to monitor the power and module 
function. 
 

Important

: - The automated test cycle 

must

 be undertaken on 

at least a weekly basis to maintain the SIL 2 units reliability. 
 

System Activation (Active Mode normal polarity) 

 
The SIL 2 system will remain monitoring the power in standby 
mode until the polarity is changed to Active mode to enable an 
active  system  for  beacon  to  function  as  a  warning  signaling 
device. 
 

Important

  :-  The  polarity  must  be  held  in  active  mode  for  a 

period in excess of 15 seconds to ensure a full system check 
is performed whilst in alarm mode, although it is expected that 
during  a  system  activation  this  period  will  be  significantly 
greater. 
 

Note

 :- The fault indication signal on TB1 can take up to 1.5 

seconds to indicate system fault.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 

Содержание D1xB2X05 Series

Страница 1: ...NETTOYER UNIQUEMENT AVEC UN CHIFFON HUMIDE HAUT TENSION RISK DE CHOC ATTENDEZ 5 MINUTES APRES AVOIR DEBRANCHE L ALIMENTATION AVANT D OUVRIR LA BOITIER NE PAS PEINTURER POUR RÉDUIRE LE RISQUE D INFLAMMATION DES ATMOSPHÈRES DANGEREUSES LE PREMIER CONDUIT DE CONDUIT DOIVENT AVOIR UN RACCORD D ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18 POUCES DE L ENFERMEMENT POUR SUBSÉQUENT LES CONDUITES DE CONDUIT LA DISTANC...

Страница 2: ...ass III Div 1 Ta 55 C to 80 C Installation must be carried out in compliance with the National Electric Code Canadian Electric Code 2 4 NEC Class Zone ratings US The D1xB2X Xenon beacons comply with the following standards UL 60079 0 Ed 7 2020 UL 60079 1 Ed 7 2020 UL 60079 31 Ed 2 2020 The D1xB2X05DC024 Xenon Beacons are rated as follows Class I Zone 1 AEx db IIC T4 Ta 55 C to 80 C Class I Zone 1 ...

Страница 3: ...st for a short time Zone 21 Explosive dust air mixture likely to occur in normal operation Zone 22 Explosive dust air mixture not likely to occur in normal operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen and Acetylene Temperature Classification T1 450ºC T2 300ºC T3 200ºC D1xB2X15DC up to 80 C ambient T4 135ºC D1xB2X...

Страница 4: ...79 14 Explosive atmospheres Electrical installations design selection and erection EN60079 10 1 IEC60079 10 1 Explosive atmospheres Classification of areas Explosive gas atmospheres EN60079 10 2 IEC60079 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres The installation of the units must also be in accordance with any local codes that may apply and should only be carrie...

Страница 5: ...e in explosive gas atmospheres a minimum ingress protection rating of IP54 must be maintained NPT plugs should be greased before insertion For high ambient temperatures the cable entry temperature or the cable branching point temperature may exceed 60ºC and therefore suitable heat resisting cables and cable glands must be used with a rated service temperature of at least the values stated below Ta...

Страница 6: ...th conductor should be at least equal in size and rating to the incoming power conductors External earthing connections should be made to the M5 earth stud using a ring crimp terminal to secure the earth conductor to the earth stud The external earth conductor should be at least 4mm in size Figure 6 Internal and External Earth Locations 11 Settings 11 1 Flash Rate Setting The D1xB2X beacon can pro...

Страница 7: ...gs MUST be fitted in the order shown above 13 Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive atmospheres Equipment repair overhaul and reclamation EN 60079 17 IEC60079 17 Explosive atmospheres Electrical installations inspection...

Страница 8: ...e and Active mode Health status of power supply Beacons correct function and flash pattern The SIL 2 beacon operates as part of a SIL 2 system The beacon will after commissioning remain powered in Standby mode reverse polarity until the beacon is required to operate When the signalling device is required to operate beacon the polarity is changed back to normal supply and the beacon will go into Ac...

Страница 9: ...require further investigation please contact your local E2S representative Commissioning System Functional start up of System Normally in reverse polarity mode When Commissioning system the power must not be disrupted to the SIL 2 Unit within the unit s initialization cycle which is 5 seconds Once past this period the SIL 2 system is fully operational and will be in monitoring the beacon and power...

Страница 10: ...gh it is highly recommended that the unit is wired as stated in section 17 1 as a 4 Wire System J1 Header Current Sense Resistor CSR Shown in factory default position A see section 17 3 places TB1 Current sense resistor in circuit J2 Header Fault Resistor FR Shown in factory default position A see section 17 3 removes power supply terminal block Fault resistor relay RLY 1 1out of circuit J7 Header...

Страница 11: ...he circuit Note a cable short circuit will not be detectable in this configuration For one unit only Beacon power supply terminal block Current drawn mA Active Mode 190mA Standby Mode 25mA SIL2 TB1 Current Sense Resistor value Current drawn mA 3 3kΩ 7 2mA On fault mode current drops to 0 as circuit goes open Figure 11 Schematic of SIL 2 system wiring for fault detection in standby and active mode ...

Страница 12: ...e SIL 2 alarm horn sounders are to be cabled in series the monitoring connections differ from that of a single beacon For more information see manual D197 00 621 IS available from the E2S website I Total Current drawn IFR Current drawn from Fault Resistor IEOL Current drawn from Customer EOL resistor ISIL Current drawn from SIL board INF Standby Mode Total Current drawn No Fault IFR 0mA IEOL See t...

Страница 13: ...ition B pins 2 3 linked Places power supply terminal Fault Resistor RLY 1 2 in circuit As used in 2 Wire Configuration Figure 14 J2 Header pin positions Fault Resistor FR 17 4 SIL 2 Hard Reset Function Power down the unit completely for a minimum of 30 seconds Move the hard reset header pin Jumper J7 to reset position B shown Then power the unit for a minimum of 5 seconds Power down the unit for 3...

Страница 14: ...andom Hardware Failures and Architectural constraints route 1H 2 As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed against failure modes Failure respond to an input by lighting a beacon Spurious light output despite no input Integrity in respect of failure to release SIL 2 Total Failure rate 0 35 pmh Hazardous failure rate revealed 0 287 pmh Hazardous failure r...

Страница 15: ...ed when ordering The values of resistors available are shown in table 5 below Code Resistor Value Default resistor coding is as follows D1xB2X05DC024AS1S1R A AFZ Example of a custom requirement resistor coding D1xB2X05DC024AS1S1R A GEF Where the FR Fault Resistor is G 3 9 kΩ CSR Current Sense Resistor is E 2 7 kΩ EOL End Of Line resistor is F 3 3 kΩ A 2 2 kΩ B 1 0 kΩ C 1 5 kΩ D 1 8 kΩ E 2 7 kΩ F 3...

Страница 16: ...TERIAL SHEET SCALE TITLE A3 IF IN DOUBT ASK DO NOT SCALE ALL DIMENSIONS IN MM DRAWING NUMBER A B C D E F G 10 9 G F E 7 8 6 5 D C 1 3 4 2 A B D191 06 621 M ABALOS B ISARD R N POTTS OF NTS 1 1 23 09 2022 23 09 2022 23 09 2022 D1xB2 GNExB2 STExB2 SIL2 DC XENON BEACON WIRING DIAGRAM INTRODUCTION INTRODUCTION 1 MA 23 09 2022 SIL2 WIRING DIAGRAM FOR THE FOLLOWING PRODUCTS D1xB2X05DC024 SIL D1xB2X10DC02...

Страница 17: ...3 Gb II 2D Ex tb IIIC T95 C T169 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN IEC 61000 6 1 2019 IEC 61000 6 1 2016 EN IEC 61000 6 2 2019 IEC 61000 6 2 2016 EN IEC 61000 6 3 2021 IEC 61000 6 3 2020 EN IEC 61000 6 4 2019 IEC 61000 6 4 2018 Dir...

Страница 18: ... Ex d IIC T6 T3 Gb II 2D Ex tb IIIC T95 C T169 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Compatibility Directive EMC Standards applied EN 61000 6 1 2007 EN 61000 6 2 2005 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007 A1 2011 Directive 2011 65 EU Restriction of the use of certain ha...

Отзывы: